HomeMy WebLinkAbout6617 S. COLLEGE AVE. - BASIC DEVELOPMENT REVIEW - BDR150011 - CORRESPONDENCE - RESPONSE TO STAFF REVIEW COMMENTS1
April 27, 2016
Meaghan Overton, Associate Planner
City of Fort Collins
Phone: 970.416.2283
E-mail: moverton@fcgov.com
6617 S College Avenue, BDR150011, Round Number 2
This letter is to address the City's BDR Review comments on the above referenced project. The
following includes the review comments. Our response follows each comment and is in bold.
All comments that require more information or revisions to the plans are also included in the plan
sets.
Hauser Architects Response: Project Architect
Stewart and Associates Response: Project Surveyor
Forbes Engineering Response: Project Civil Engineer
SRB Response: Project Electrical Engineer
Should you have any questions, or need additional information, please contact me at your
convenience.
Sincerely,
BJ DeForge
Hauser Architects, PC
970.669.8220
2
Community Development and
Neighborhood Services
281 North College Avenue
PO Box 580
Fort Collins, CO 80522
970.221.6750
970.224.6134 - fax
fcgov.com/developmentreview
March 25, 2016
BJ Deforge
HAUSER ARCHITECTS, P.C.
3780 E 15TH ST STE201
Loveland, CO 80538
RE: 6617 S College Ave, BDR150011, Round Number 2
Please see the following summary of comments from City staff and outside reviewing
agencies for your submittal of the above referenced project. If you have questions about
any comments, you may contact the individual commenter or direct your questions through
the Project Planner, Meaghan Overton, at 970-416-2283 or moverton@fcgov.com.
Comment Summary:
Department: Planning Services
Contact: Meaghan Overton, 970-416-2283, moverton@fcgov.com
Topic: General
Comment Number: 3. Comment Originated: 12/23/2015
03/23/2016: The revised site plan does not appear to include a connecting
walkway from the building to the public sidewalk. In addition, there is no
walkway delineated from the parking lot to the building entrance. Please clarify
and clearly show a walkway from the public sidewalk along S. College to the
main entrance of the building, and from the parking lot to the main entrance of
the building. The walkway shown along the property line of Lot 3 does not meet
the requirement for a connecting walkway from S. College to the building
entrance for Lot 1.
Hauser Architects Response: A 6 foot wide sidewalk was added. This connects the
public sidewalk to the main entry. The walkway from the parking to the main
entry is defined better on the site plan. This 5 foot wide walkway is concrete and is
located north of the parking area. The accessible walkway continuous from the
parking area and turns to an accessible ramp on the south side of the building. This
ramp leads to the front covered, concrete patio. The walkway from Lot 3 to Lot 1
was eliminated.
Forbes Engineering Response: Sidewalk connection added.
12/23/2015: A connecting walkway will be required that connects the building
entrance to the public sidewalk on S. College.
Hauser Architects Response: Provided. See response above.
3
Comment Number: 4. Comment Originated: 12/23/2015
03/23/2016: A walkway is now shown within an easement along the property
line of Lot 3, stubbed to the west property line of Lot 1. Note that this walkway
and any other connecting walkways must be 6 feet wide, instead of the 5 feet
currently proposed, as required in Section 3.2.2(C)(5) of the Land Use Code.
Hauser Architects Response: The sidewalk was revised to a 6 foot wide walk
Forbes Engineering Response: Sidewalk width changed to 6'
12/23/2015: A connecting walkway needs to be stubbed to the west property
line so that when Lot Two re-develops or changes use, then it will also be
connected to the public sidewalk along S. College. This connecting walkway
must be placed within an Access Easement. The purpose is to coordinate
future re-development with the current project to avoid more difficult issues in
the future.
Hauser Architects Response: Provided. See response above.
Comment Number: 5. Comment Originated: 12/23/2015
03/23/2016: The width of the access/emergency/utility easement shown on the
plat does not match the easement noted on the site and landscape plans. As
currently shown, the walkway along the property line of Lot 3 is not included in
the easement on the plat. Please adjust the plat to reflect the boundaries of the
easement as shown on the site and landscape plans.
Hauser Architects Response: The Plat, Site Plan and Landscape plan was
coordinated and the same linework appears on each document.
12/23/2015: The plat indicates that the southerly property line for Lot 1 is not
the south edge of the Emergency Access Easement but, rather, extends 7.09
feet beyond. What is the purpose of leaving a 7.09-foot wide strip along the
south property line? Technically, this means that this strip needs to be
landscaped which, given its location, would be difficult to irrigate and maintain.
Why not place this strip within the boundary of Lot 3?
Hauser Architects Response: This was addressed. Refer to previous comment.
Comment Number: 6. Comment Originated: 12/23/2015
03/23/2016: Additional landscaping has been added. Please clarify whether
Fountain Grass or Feathergrass will be planted - the Landscaping Schedule
notes Fountain Grass, but the Latin name Pennisetum alopecuroides refers to
Feathergrass.
Hauser Architects Response: I sent you an email on April 6 to clarify the following:
"We use the Plant Guide from Colorado Nursery & Greenhouse Association
(CNGA) and I'm changing the plant to Feather Reed Grass ( Calamagrostis x
acutiflora)according to CNGA." Your email response accepted this change /
clarification.
12/23/2015: Additional landscaping needs to be added along the north side of
the new Grow Barn.
Hauser Architects Response: Provided. Please refer to previous comment and
response.
4
Comment Number: 8. Comment Originated: 12/23/2015
03/23/2016: Redlines are available at the front counter.
12/23/2015: Redline plans are available at the front counter.
Comment Number: 9. Comment Originated: 03/23/2016
03/23/2016: Comments from the South Fort Collins Sanitation District and the
Fort Collins-Loveland Water District indicate that the issues and concerns from
the last round of review (letter dated 12.22.15) have not been addressed. The
District requires another round of review. Please see letter dated 3.21.16, sent
to you via email. A copy of this letter is also available at the front counter.
Forbes Engineering Response: Comments from SFCSD have been addressed.
Hauser Architects Response: Comments received and our Civil Engineer will
contact Mr. Terry Farrill, P.E. to address his comments. Below is a summary of our
Civil Engineer's response to the letters;
1. “All water services to the proposed lots 2 and 3 are to be abandoned”, water
services to proposed lots are themselves proposed and something that doesn’t exist
generally doesn’t need to be abandoned. The buildings on the west side of the property
being used by Thermal Concepts (which will become lot 3) probably have a water
service and I don’t believe they will want it abandoned.
2. Regarding the fire line and emergency access easement, the construction plans
clearly state that the fire line is NOT to be used for domestic use. A reduced principle
Back-Flow-Prevention-Device has been added to the plans and the note for this has also
been modified to conform to the latest comment about being installed in accordance
with the manufacturer’s requirements. And as far as I know the emergency access
easement issues have been addressed (not sure how this is his concern). If the fire line
becomes the property of the FCLWD, then I suppose the easement will have to be on
the District’s standard easement form, I thought that PFA or the property owner
becomes the one that maintains the fire line?
3. “Is sanitary sewer required for the proposed lots 2 & 3?”, no & yes. Lot 2 will not
have a sewer service as it is a detention pond and lot 3, as mentioned previously, is an
existing business which probably has an existing service (in fact, I would imagine the
district has been applying fees to this address for quite some time).
4. This comment has to do with the property not within the service area of SFCSD,
which is odd since there is an existing 8” sanitary sewer stub on the property (in the
ROW) and if not into this where else has the sewer been discharged to?
5. This comment indicates that maybe the district has not been supplied a set of the
construction plans?
Hauser Architects Response: We contacted Mr. Farrill and requested a meeting
with his department and the Fire Department. We feel a meeting will be more
productive than exchanging emails and plan revisions. Mr. Farrill has not set up
the meeting yet but we hope this is done during this re-submittal.
Department: Engineering Development Review
5
Contact: Katie Sexton, 970-221-6501, ksexton@fcgov.com
Topic: General
Comment Number: 4 Comment Originated: 03/18/2016
03/18/2016: A development agreement will need to be recorded with final
project approval. Upon your request I will send you an information sheet to be
filled out and returned to me. Once I have received that I will put together a DA
for your review and signature.
Hauser Architects Response: We received this form and we will send it back once
they are complete.
Comment Number: 5 Comment Originated: 03/18/2016
03/18/2016: Before starting any construction on the site, a development
construction permit must be obtained. Upon your request I will send you the
application along with some more information about the DCP permit process.
Hauser Architects Response: We received this permit and we will send it back once
the application is complete.
Department: Forestry
Contact: Tim Buchanan, 970-221-6361, tbuchanan@fcgov.com
Topic: Landscape Plans
Comment Number: 1 Comment Originated: 12/28/2015
12/28/2015:
Contact the City Forester for an on-site meeting to evaluate and inventory
exiting trees on the site and determine if any mitigation for tree removal is
required.
Hauser Architects Response: I met with Ralph Zentz on April 13, 2016. We
analyzed (2) trees. The tree on S. College (Honey Locust, 30" dia. and 4 mitigation
points) will remain. A centrally located tree (Ash, 5" dia. and 0 mitigation points)
was inspected and this tree removal will be determined during construction.
Comment Number: 2 Comment Originated: 03/23/2016
03/23/2016:
Add the newly developed City Planning Department General Landscape notes
and the tree protection notes to the landscape plan. These notes are available
from the City Planner or from the City Forester.
Hauser Architects Response: Notes received and added to the Landscape Plan.
Department: Light And Power
Contact: Todd Vedder, 970-224-6152, tvedder@fcgov.com
Topic: General
Hauser Architects Response: Comments addressed with submittal 2.
Comment Number: 1 Comment Originated: 12/21/2015
12/21/2015: New development and system modification charges may apply. A
link to our online electric fee estimator is below.
http://www.fcgov.com/utilities/business/builders-and-developers/plant-investmen
t-development-fees/electric-development-fee-estimator?id=3
Comment Number: 2 Comment Originated: 12/21/2015
12/21/2015: Please provide a one line diagram and a Commercial Service
Form (C-1) form to Light and Power Engineering. It will need to be determined
6
whether single or three phase power is required. The C-1 form can be found at
the link below:
http://zeus.fcgov.com/utils-procedures/files/EngWiki/WikiPdfs/C/C-1Form.pdf
Comment Number: 3 Comment Originated: 12/21/2015
12/21/2015: If electric power lines cross between lots, then electric/utility
easements will have to be utilized.
Comment Number: 4 Comment Originated: 12/21/2015
12/21/2015: d.) Please contact Todd Vedder with Light & Power Engineering
Department if you have any questions at 970.224.6152. Please reference our
Electric Construction, Policies Practices & Procedures to ensure requirements
and policies are met.
http://www.fcgov.com/utilities/business/builders-and-developers
Comment Number: 5 Comment Originated: 12/21/2015
12/21/2015: c.) Contact Light and Power Engineering to coordinate the
transformer and electric meter locations, please show these locations on the
utility plans. Transformers need to have an 8’ frontal and 3’ side/rear clearance.
It also has to be 10’ within a drivable surface and cannot be located under the
drip zone of any trees.
Department: PFA
Contact: Jim Lynxwiler, 970-416-2869, jlynxwiler@poudre-fire.org
Topic: General
Hauser Architects Response: We received the following comments, from Jim Lynxwiler via email
on March 28;
03/28/2016: SIGNS
The full limits of the fire lane have not yet been labeled in the latest set of plans. The preferred fire lane signage as
shown in LCUASS Sign Detail 1418 is "Fire Lane - No Parking" however the words "by order of the fire marshal"
shall be omitted and replaced with directional arrows as typical. Code language provided below.
Ø IFC D103.6: Where required by the fire code official, fire apparatus access roads shall be marked with
permanent FIRE LANE - NO PARKING signs complying with Figure D103.6. Signs shall have a minimum
dimension of 12 inches wide by 18 inches high and have red letters on a white reflective background. Signs shall be
posted on one or both sides of the fire apparatus road as required by Section D103.6.1 or D103.6.2.
Hauser Architects Response: Sign detail and sign revisions are located on sheet
BDR2.
03/28/2016: SECURITY GATES
Gates blocking fire lanes shall be approved and meet minimum standards as provided below.
Ø 2012 IFC 503.6: The installation of security gates across a fire apparatus access road shall be approved by the
fire chief. Where security gates are installed, they shall have an approved means of emergency operation. The
security gates and the emergency operation shall be maintained operational at all times.
2012 IFC D103.5: Gates securing fire apparatus access roads shall comply with all of the following criteria:
1. The minimum gate width for vehicle access shall be 20 feet.
2. Gates shall be of the swinging or sliding type.
3. Construction of gates shall be of materials that allow manual operation by one person.
7
4. Gate components shall be maintained in an operative condition at all times and replaced or repaired when
defective.
5. Electric gates shall be equipped with a means of opening the gate by fire department personnel for emergency
access. Emergency opening devices shall be approved by the fire code official.
6. Manual opening gates shall not be locked with an unapproved padlock, or chain and padlock, unless they are
capable of being opened by means of forcible entry tools or when a key box containing the key(s) to the lock is
installed at the gate location.
7. Gate design and locking device specifications shall be submitted for approval by the fire code official prior to
installation.
8. Electric gate operators, where provided, shall be listed in accordance with UL 325.
9. Gates intended for automatic operation shall be designed, constructed and installed to comply with the
requirements of ASTM F 2200.
Hauser Architects Response: These requirements were added to sheet BDR2. Any items that
don't meet the conditions above will be adjusted in the field.
Comment Number: 1 Comment Originated: 12/29/2015
12/29/2015: FIRE LANES
Fire access is required to within 150' of all exterior portions of all new and
existing building perimeters. This distance is measured along an approved path
of travel, which in this case, would be as a fire hose is laid from a parked engine
around the building. The response letter dated December 2, 2015 indicates,
"The entire perimeter of the new/existing building is within 150' from the fire
access easement," however my assessment indicates this condition has not
been achieved at Lot 1 (which is approximately 55' out of access), nor for the
existing building at Lot 2 (which is approximately 220' out of access). Please
contact me should you require further assistance with code interpretation or fire
lane design. Code language provided below.
> IFC 503.1.1: Approved fire Lanes shall be provided for every facility, building
or portion of a building hereafter constructed or moved into or within the
jurisdiction. The fire apparatus access road shall comply with the requirements
of this section and shall extend to within 150 feet of all portions of the facility and
all portions of the exterior walls of the first story of the building as measured by
an approved route around the exterior of the building or facility. When any
portion of the facility or any portion of an exterior wall of the first story of the
building is located more than 150 feet from fire apparatus access, the fire code
official is authorized to increase the dimension if the building is equipped
throughout with an approved, automatic fire-sprinkler system.
Comment Number: 2 Comment Originated: 12/29/2015
12/29/2015: EMERGENCY ACCESS EASEMENT
The easement shall be dedicated and labeled as an Emergency Access
Easement (EAE) rather than Fire Access Easement as currently shown on the
plans.
Comment Number: 3 Comment Originated: 12/29/2015
12/29/2015: CUL-DE-SACS
Cul-de-sac turnarounds are required to be 100' in diameter to allow for
continuous movement of fire apparatus. The proposed diameter is shown as 80'
rather than 100'. One option would be to increase the diameter to 100'. Another
may be to incorporate a hammerhead turning movement on site, allowable by
code, rather than the circular turnaround. Depending upon design and
placement, a hammerhead may also allow the out of access condition in Lot 1
8
to be reduced to an acceptable measure. Hammerhead turning movement will
require 25' inside turning radii and a minimum "leg" of 50' each. Code language
provided below. Special approval of the fire marshal will be required in order to
reduce the diameter to 80'.
> FCLUC 3.6.2(B): Cul-de-sacs are permitted only if they do not exceed 660
feet in length and have a turnaround at the end with a minimum outside turning
radius of 50 feet (100 foot diameter).
Comment Number: 4 Comment Originated: 12/29/2015
12/29/2015: FIRE LANE SPECIFICATIONS
Fire lane specifications call for hard surfaces which shall be designed to carry
40 ton minimum load limits. The proposed gravel area overlapping with the
Emergency Access Easement shown in the current plan is not allowed without
special approval of the fire marshal. Fire lane specifications provided below.
FIRE LANE SPECIFICATIONS
A fire lane plan shall be submitted for approval prior to installation. In addition to
the design criteria already contained in relevant standards and policies, any
new fire lane must meet the following general requirements:
> Shall be designated on the plat as an Emergency Access Easement.
> Maintain the required 20 foot minimum unobstructed width & 14 foot minimum
overhead clearance.
> Be designed as a flat, hard, all-weather driving surface capable of supporting
40 tons.
> Dead-end fire access roads in excess of 150 feet in length shall be provided
with an approved area for turning around fire apparatus.
> The required turning radii of a fire apparatus access road shall be a minimum
of 25 feet inside and 50 feet outside. Turning radii shall be detailed on
submitted plans.
> Be visible by painting and/or signage, and maintained unobstructed at all
times.
> Additional access requirements exist for buildings greater than 30' in height.
Refer to Appendix D of the 2012 IFC or contact PFA for details.
International Fire Code 503.2.3, 503.2.4, 503.2.5, 503.3, 503.4 and Appendix
D; FCLUC 3.6.2(B)2006 and Local Amendments.
Department: Stormwater Engineering
Contact: Heather McDowell, 970-224-6065, hmcdowell@fcgov.com
Topic: Construction Drawings
Comment Number: 4 Comment Originated: 12/14/2015
03/15/2016: Your response indicated that a "bioretention sediment trap
forebay" has been included in the detention pond, please show this element on
the grading plan instead of the erosion control plan, as this is not an erosion
control measure, its a stormwater quality measure.
12/14/2015: Sheet C3.0 - Grading Plan
- Existing and proposed stormwater piping needs to be clearly labeled.
- The outlet structure for the detention pond needs to be an extended detention
outlet structure per Fort Collins standards. The updated strcture needs to be
drawn in the plans to scale.
- Detention pond information needs to be included in the plan. This info
includes: 100-yr water surface elevation, water quality surface elevation, release
rates, pond volume.
9
Forbes Engineering Response: Bioretention forebay details have been moved to the grading plans
- LID techniques need to be clearly shown and sized on the plans.
Topic: Drainage Report
Comment Number: 5 Comment Originated: 12/14/2015
03/15/2016: It looks like runoff is now calculated using City of Fort Collins
rainfall data, but the detention basins have been sized using UDFCD criteria
and rainfall. Please use your own mass balance spreadsheet to calculate
detention volumes. The City has a template for this if you need it. Please contact
Heather McDowell at 224-6065 for the file.
12/14/2015: Drainage was analyzed using Larimer County Stormwater Design
Standards. This project lies within the City of Fort Collins and the drainage
evaluation needs to be performed using the Fort Collins Stormwater Criteria
Manual and Fort Collins rainfall data.
Forbes Engineering Response: Revised & re-calculated using COF Criteria
Topic: General
Comment Number: 6 Comment Originated: 12/14/2015
03/15/2016: Existing and proposed impervious areas still need to be provided
somewhere in the plans. This is needed to calculate stormwater fees. Fees are
based upon additional amount of imperviousness.
12/14/2015: The surface areas included in the Existing Site Conditions and
Proposed Site Conditions exhibits need to be verified and coordinated with the
Site Plan. Existing and Proposed impervious square footages also need to be
included on these exhibits.
Forbes Engineering Response: Existing & proposed impervious area have been added to the
construction set
Comment Number: 7 Comment Originated: 12/14/2015
03/15/2016: Please clarify in the narrative of the report what the allowable
release rate is from the site (2-yr historic rate minus undetained basins)
12/14/2015: This report needs to clarify which basins are running through and
into the detention pond. All site runoff needs to be captured into the extended
detention basin. If not all stormwater runoff can be routed toward and captured
in the detention basin, then over-detention will need to be provided so that the
overall release rate from the site is not exceeding the 2-year historic rate.
Forbes Engineering Response: The 2-year release rate has been added to the narrative
Comment Number: 9 Comment Originated: 12/14/2015
03/15/2016: The LID ordinance has been updated to the following
requirements:
Option A: no less than 75% of any newly developed or redeveloped areas must
be treated using one or a combination of LID techniques
Option B: no less than 50% of any newly developed or redeveloped areas must
be treating using one or a combination of LID techniques; and permeable
pavement must cover 25% of driveable surfaces.
Please include calculations and an exhibit showing how you meet the
percentage requirements. The bioretention calculation can be done using the
UDFCD RG spreadsheet.
10
Forbes Engineering Response: Size of the LID has been updated
12/14/2015: Low Impact Development (LID) is required for this site. LID
requires a higher degree of water quality treatment for 50% of the new
impervious area and 25% of new paved areas must be pervious. Standard
operating procedures (SOPs) for all onsite drainage facilities will be included
as part of the Development Agreement. More information and links can be
found at:
http://www.fcgov.com/utilities/what-we-do/stormwater/stormwater-quality/low-im
pact-development
Comment Number: 13 Comment Originated: 12/14/2015
03/15/2016: Your response indicated that this was provided in the updated
drainage report but I could not find it. Please provide.
12/14/2015: The proposed inlet requires hydraulic calculation to verify that the
proposed size is adequate.
Forbes Engineering Response: Added
Comment Number: 14 Comment Originated: 12/14/2015
03/15/2016: Please include the wq orifice sizing calculations.
12/14/2015: The proposed outlet structure needs to be an extended detention
outlet structure with hydraulic calculations included.
Forbes Engineering Response: Added
Comment Number: 15 Comment Originated: 12/14/2015
03/15/2016: Your response indicated that this was provided but I did not see it.
Please provide.
12/14/2015: The proposed storm pipe profiles need to include the 100-yr
hydraulic grade line in the profile view.
Forbes Engineering Response: That layer was turned off, it has now been turned on
Contact: Jesse Schlam, 970-218-2932, jschlam@fcgov.com
Topic: Erosion Control
Comment Number: 1 Comment Originated: 12/08/2015
3/9/2016: The submitted erosion control plan sheet has redlines that need to be
addressed based upon the changes to the plan. The erosion control report was
to the pre 2012 (old) standards. The Storm Drainage Criteria manual was
updated back in December of 2012; since that time, all materials have met
those standards. Please reference the accompanying document provided in the
erosion control report to help meet current standards for an eroison control
report. Erosion Control Escrow Calculation will also need to be provided and
example of that escrow calculation and the accompanying document can be
found at www.fcgov.com/erosion
12/08/2015: The site disturbs more than 10,000 sq-ft, therefore Erosion and
Sediment Control Materials need to be submitted. The erosion control
requirements are in the Stormwater Design Criteria under the Amendments of
Volume 3 Chapter 7 Section 1.3.3. Current Erosion Control Materials
Submitted do not meet requirements. Please submit; Erosion Control Plan (Has
redlines), Erosion Control Report (Was not found or was not routed), and an
Escrow / Security Calculation (Was not found or was not routed). If you need
11
clarification concerning the erosion control section, or if there are any questions
please contact Jesse Schlam 970-218-2932 or email @ jschlam@fcgov.com
Forbes Engineering Response: The redline comments have been addressed
Department: Technical Services
Contact: Jeff County, 970-221-6588, jcounty@fcgov.com
Topic: Building Elevations
Comment Number: 1 Comment Originated: 12/22/2015
03/23/2016: Not all plans were provided for review, so we cannot verify this
was addressed.
Hauser Architects Response: Full (2) sheet sets provided. Not sure what happened.
12/22/2015: There are line over text issues. See redlines.
Topic: Construction Drawings
Comment Number: 2 Comment Originated: 12/22/2015
03/23/2016: The titles in the sheet index do not match the titles on the noted
sheets. See redlines.
12/22/2015: The titles in the sheet index do not match the titles on the noted
sheets. See redlines.
Forbes Engineering Response: Noted and revised
Comment Number: 3 Comment Originated: 12/22/2015
03/23/2016: This has not been corrected.
12/22/2015: The City has moved to the NAVD88 vertical datum, and as of
January 1, 2015 all projects are required to be on NAVD88 datum. Please
provide the following information in the EXACT format shown below.
PROJECT DATUM: NAVD88
BENCHMARK # w/ DESCRIPTION
ELEVATION:
BENCHMARK # w/ DESCRIPTION
ELEVATION:
PLEASE NOTE: THIS PLAN SET IS USING NAVD88 FOR A VERTICAL
DATUM. SURROUNDING DEVELOPMENTS HAVE USED NGVD29
UNADJUSTED FOR THEIR VERTICAL DATUMS.
IF NGVD29 UNADJUSTED DATUM IS REQUIRED FOR ANY PURPOSE,
THE FOLLOWING EQUATION SHOULD BE USED: NGVD29 UNADJUSTED
= NAVD88 - X.XX¿.
Forbes Engineering Response: Benchmark datum note has been added
Comment Number: 4 Comment Originated: 12/22/2015
03/23/2016: There are line over text issues. See redlines.
12/22/2015: There are line over text issues. See redlines.
Topic: Landscape Plans
Comment Number: 6 Comment Originated: 12/22/2015
03/23/2016: There is text that needs to be masked. Mask all text in hatched
areas. See redlines.
Hauser Architects Response: Corrected.
12/22/2015: There is text that needs to be masked. Mask all text in hatched
areas. See redlines.
12
Topic: Lighting Plan
Comment Number: 25 Comment Originated: 03/23/2016
03/23/2016: No comments.
Topic: Plat
Comment Number: 22 Comment Originated: 03/23/2016
03/23/2016: Please add distances as marked. See redlines.
Stewart and Associates Response: Provided.
Comment Number: 23 Comment Originated: 03/23/2016
03/23/2016: The outer boundary of the plat needs to include the 26 feet of right
of way to be dedicated. The legal description needs to be revised as well.
Stewart and Associates Response: Provided.
Comment Number: 24 Comment Originated: 03/23/2016
03/23/2016: Please remove Notes 4 & 5. They are not appropriate for
subdivisions.
Topic: Site Plan
Comment Number: 20 Comment Originated: 12/22/2015
03/23/2016: There is text that needs to be rotated 180 degrees. See redlines.
12/22/2015: There is text that needs to be rotated 180 degrees. See redlines.
Department: Traffic Operation
Contact: Martina Wilkinson, 970-221-6887, mwilkinson@fcgov.com
Topic: General
Comment Number: 2 Comment Originated: 12/22/2015
03/22/2016: You'll need to obtain a change in use permit from CDOT. Let me
know if you have questions how to do that.
Hauser Architects Response: The application and supporting files were sent to CDOT.
12/22/2015: College Avenue is a state highway and is under the jurisdiction of
the Colorado Department of Transportation (CDOT). They may require a
change in use permit for the access point (depending on the traffic numbers
noted above). They will also indicated whether the access can stay full
movement or if left turns need to be restricted in some way.