BFE AT UPSTREAM EDGE OF
BUILDING = 4967.77*
FLOOR AREA DATA
BFE AT UPSTREAM EDGE OF
BUILDING = 4967.77*
PROPOSED BUILDING FOOTPRINT
EXISTING NEIGHBORING BUILDING
EXISTING NEIGHBORING BUILDING
PROPERTY BOUNDARY
PROPERTY BOUNDARY
EXISTING BUILDING FOOTPRINT
EXISTING 100-YR FLOODPLAIN LIMITS
SUPER-IMPOSED FROM THE FIRM
FLOODPLAIN CROSS SECTIONS
P.O. BOX 150894 Ŷ Lakewood, Colorado 80215
Ŷ ph: (720) 837-0648 Ŷ www.FloodplainSpecialists.com
SITE DEVELOPMENT
1 OF 2
FLOODPLAIN SITE PLAN
FOR
THE GREEN SOLUTION
AT
810 NORTH COLLEGE AVENUE
FT. COLLINS, CO
LARIMER COUNTY
FLOODPLAIN SITE PLAN
ORIGIN. SHEET DESCRIPTION
DATE
12-09-15 C5.0 FLOODPLAIN SITE PLAN
12-09-15 C5.1 FLOODPLAIN CROSS SECTION AND FLOODPROOFING NOTES
LEGEND
* VERTICAL DATUM = NAVD88
OVERALL FLOODPLAIN MAP (NTS)
NAVD88 = NGVD29 + 3.17'
PROPOSED NORTH ELEVATION
BFE AT UPSTREAM EDGE
OF BUILDING = 4967.6
BFE AT UPSTREAM EDGE
OF BUILDING = 4967.77*
REGULATORY FLOOD
PROTECTION ELEV. =
4969.77
2.0' FREEBOARD ZONE
FREEBOARD ELEV. = 4969.77 FREEBOARD ELEV. = 4969.77
WATER RESISTANT
MATERIALS REQUIRED
WITHIN FREEBOARD
ZONE, SEE NOTES THIS
SHEET FOR ADDITIONAL
INFOMRATION
(NTS)
ALL DUCT WORK, HEATING, VENTILATION,
ELECTRICAL SYSTEMS, ETC. TO BE ELEVATED
TO THE REGULATORY FLOOD PROTECTION
ELEVATION (RFPE)
P.O. BOX 150894 Ŷ Lakewood, Colorado 80215
Ŷ ph: (720) 837-0648 Ŷ www.FloodplainSpecialists.com
SITE DEVELOPMENT
2 OF 2
FLOODPLAIN SITE PLAN
FOR
THE GREEN SOLUTION
AT
810 NORTH COLLEGE AVENUE
FT. COLLINS, CO
LARIMER COUNTY
FLOODPLAIN CROSS SECTION
AND FLOODPROOFING NOTES
ORIGIN. SHEET DESCRIPTION
DATE
12-09-15 C5.0 FLOODPLAIN SITE PLAN
12-09-15 C5.1 FLOODPLAIN CROSS SECTION AND FLOODPROOFING NOTES
TABLE 2, SUGGESTED MATERIALS BELOW BFE (AND WITHIN THE FREEBOARD ZONE.) SEE FEMA TECHNICAL BULLETIN #2 FOR MORE INFORMATION
SUBSTANTIAL AND REDEVELOPMENT IMPROVEMENTS FOR NON-RESIDENTIAL STRUCTURES: (THE PROPOSED NON-RESIDENTIAL
ADDITION IS A SUBSTANTIAL IMPROVEMENT.)
A. A SUBSTANTIAL IMPROVEMENT OCCURS WHEN ALL OF THE CONDITIONS ARE MET:
a. A BUILDING PERMIT IS REQUIRED.
b. THE COST OF THE IMPROVEMENT, OR THE AMOUNT OF THE DAMAGE, EQUALS OR EXCEEDS 50 PERCENT OF THE MARKET
VALUE OF THE STRUCTURE EITHER BEFORE THE IMPROVEMENT OR REPAIRS IS STARTED OR BEFORE THE BUILDING WAS
DAMAGED.
c. THE COST IS CALCULATED CUMULATIVELY OVER THE LIFE OF THE STRUCTURE DURING THE TIME THE STRUCTURE HAS BEEN
LOCATED IN A DESIGNATED FLOODPLAIN.
B. IF A SUBSTANTIAL IMPROVEMENT OCCURS, THE LOWEST FLOOR OF A NON-CONFORMING STRUCTURE, INCLUDING THE BASEMENT
AND ALL HVAC AND ELECTRICAL, MUST BE ELEVATED OR FLOODPROOFED 24-INCHES ABOVE THE FLOOD ELEVATION.
C. A REDEVELOPMENT OCCURS WHEN THERE IS A SUBSTANTIAL IMPROVEMENT AND MORE THAN 50 PERCENT OF THE WALL
PERIMETER IS REMOVED BUT THE BUILDING FOOTPRINT IS NOT INCREASED.
FREEBOARD FOR NON-RESIDENTIAL STRUCTURES:
A. FREEBOARD IS 24-INCHES.
B. ALLOWED TO ELEVATE OR FLOODPROOF THE STRUCTURE.
C. IF ELEVATING, THE LOWEST FLOOR OF THE STRUCTURE INCLUDING THE BASEMENT, ALL HVAC AND ELECTRICAL EQUIPMENT MUST
BE ELEVATED ABOVE THE FREEBOARD HEIGHT.
D. IF FLOODPROOFING, THE STRUCTURE AS WELL AS ALL HVAC AND ELECTRICAL, MUST BE FLOODPROOFED TO THE FREEBOARD
HEIGHT.
FLOODPROOFING REQUIREMENTS: (THE NON-RESIDENTIAL STRUCTURES ARE PROPOSED TO BE DRY-FLOODPROOFED.)
A. MATERIALS BELOW THE FREEBOARD ELEVATION MUST BE CONSTRUCTED WITH MATERIALS AND UTILITY EQUIPMENT RESISTANT TO
FLOOD DAMAGE (SEE TABLE 2 OF FEMA TECHNICAL BULLETIN 3, "NON-RESIDENTIAL FLOODPROOFING - REQUIREMENTS AND
CERTIFICATION."
B. CONSTRUCTION OF A NONRESIDENTIAL ADDITION IS ALLOWED IN A FEMA 100-YEAR FLOOD FRINGE, AS LONG AS ALL DUCT WORK,
HEATING, VENTILATION, ELECTRICAL SYSTEMS, ETC. ARE ELEVATED 24-INCHES ABOVE THE BASE FLOOD ELEVATION (BFE). THIS
ELEVATION IS KNOWN AS THE REGULATORY FLOOD PROTECTION ELEVATION (RFPE).
FLOATABLE MATERIALS: (NO FLOATABLE MATERIALS ARE PROPOSED WITHIN THE FLOODWAY OR WITHIN THE FLOOD FRING; BIKERACK
AND COMPACTOR TO BE BOLTED THROUGH PERMANENT PAVEMENT- CONCRETE OR ASPHALT.)
A. "FLOATABLE MATERIAL" IS DEFINED AS MATERIAL THAT IS NOT SECURED IN PLACE OR COMPLETELY ENCLOSED IN A STRUCTURE
SO THAT IT COULD FLOAT OFF-SITE DURING A FLOOD AND POTENTIALLY CAUSE HARM TO DOWNSTREAM PROPERTY OWNERS OR
THAT COULD CAUSE BLOCKAGE OF A CULVERT, BRIDGE, OR OTHER DRAINAGE FACILITY.
B. IN THE FLOOD FRINGE, FLOATABLE MATERIALS ASSOCIATED WITH ANY NON-RESIDENTIAL USE IS NOT ALLOWED.
C. IN THE FLOOD FRINGE, OUTSIDE STORAGE OF MATERIAL OR EQUIPMENT THAT IS CONSIDERED "FLOATABLE MATERIAL" IS
ALLOWED.
REGARDING THE CITY OF FORT COLLINS FLOODPLAIN
REGULATIONS FOR THE POUDRE RIVER
* VERTICAL DATUM = NAVD88
NAVD88 = NGVD29 + 3.17'
BEFORE A FLOODPROOFED BUILDING IS DESIGNED, NUMEROUS PLANNING CONSIDERATIONS, INCLUDING
FLOOD WARNING TIME, USES OF THE BUILDING, MODE OF ENTRY TO AND EXIT FROM THE BUILDING AND THE
SITE IN GENERAL, FLOODWATER VELOCITIES, FLOOD DEPTHS, DEBRIS IMPACT POTENTIAL, AND FLOOD
FREQUENCY, MUST BE ADDRESSED TO ENSURE THAT DRY FLOODPROOFING WILL BE A VIABLE FLOODPLAIN
MANAGEMENT TOOL. CONSIDERATIONS INCLUDE:
A. WARNING TIME
B. SAFETY AND ACCESS
C. EMERGENCY RESPONSE AND PREPAREDNESS PLAN (ERPP)
x AN ERPP HAS BEEN PREPARED, AND HAS BEEN PROVIDED TO THE CITY OF FORT COLLINS. A COPY OF
THE ERPP IS TO BE POSTED IN THE STRUCTURE, REVIEWED, UNDERSTOOD, AND FOLLOWED BY THE
OCCUPANTS AT ALL TIMES.
D. ENGINEERING CONSIDERATIONS:
x $//2)7+(%8,/',1*¶66758&785$/&20321(1760867%(&$3$%/(2)5(6,67,1*7+(
HYDRO-DYNAMIC AND HYDRO-STATICE FLOOD-RELATED FORCES. REFER TO FEMA TECHNICAL
BULLETIN 3-93 FOR MORE INFORMATION.
x TO ACCOMPLISH A POST-PROJECT FLOOD CERTIFICATION, A STRUCTURAL ENGINEER WILL NEED TO
VERIFY THAT THE BUILDING CAN WITHSTAND THESE LOADS. IT IS SUGGESTED THAT THESE
CALCULATIONS OR CONCLUSIONS BE STATED ON THE STRUCTURAL PLANS PRIOR TO PLAN
APPROVAL.
E. FLOOD PROOF DOORWAYS:
x REFER TO THE ARCHITECTURAL PLANS FOR ALL FLOOD PROOF DOORWAY DETAILS.
x DOORS #101, 102A, 107A & 111 ARE TO BE FLOOD PROOF PER ARCHITECTURAL PLANS.
x ALL EXTERIOR OPENINGS ARE TO BE FLOODPROOFED; THE FRONT TWO (CUSTOMER ENTRY ALONG
THE WESTERN SIDE) ARE TO BE GLAZED ALUMINUM; THE OTHERS (NORTHERN AND EASTERN) DOORS
TO BE FLUSH HOLLOW METAL, SUCH AS HTTP://WWW.FLOODDOOR.COM/INDEX.HTML, OR
EQUIVALENT.
F. BUILDING MATERIALS:
x REFER TO THE ARCHITECTURAL PLANS FOR ALL BUILDING MATERIAL DETAILS.
x THE ENTIRE BUILDING HAS A BRICK WAINSCOT PER ARCHITECTURAL PLANS.
x ALL MATERIAL BELOW THE RFPE ARE TO BE FLOOD RESISTANT; SEE TABLE-2, FEMA TECHNICAL
BULLETIN #2 FOR MORE INFORMATION; REFER TO EXCERPTS INCLUDED ON THIS SHEET.
x TO ACCOMPLISH A POST-PROJECT FLOOD CERTIFICATION, AN ARCHITECT WILL NEED TO VERIFY
THAT THE MATERIALS OF THE BUILDING MEET THESE REQUIREMENTS.
DRY FLOODPROOFING CONSIDERATIONS