Loading...
HomeMy WebLinkAboutHOME2 SUITES AT HARMONY VILLAGE - PDP - PDP150031 - SUBMITTAL DOCUMENTS - ROUND 1 -1 Community Development and Neighborhood Services 281 North College Avenue PO Box 580 Fort Collins, CO 80522 970.221.6750 970.224.6134 - fax fcgov.com/developmentreview September 04, 2015 RE: Home2Suites - Preliminary Design Review, PDR150018, Round Number 1 JR Engineering Response to City Staff PDR Comments – December 14, 2015 Please see the following summary of comments from City staff and outside reviewing agencies for your submittal of the above referenced project. If you have questions about any comments, you may contact the individual commenter or direct your questions through the Project Planner, Ted Shepard, at 970-221-6343 or tshepard@fcgov.com. Comment Summary: Department: Planning Services Contact: Ted Shepard, 970-221-6343, tshepard@fcgov.com Topic: General Comment Number: 1. Comment Originated: 09/02/2015 09/02/2015: Please indicate with a diagram how the overall access and circulation and fire access for the overall commercial center is not impeded with the porte cochere. Pavement striping and directional arrows may be needed to direct through traffic from unintentionally passing under the porte cochere. Response: The Porte Cochere/Drop-Off lane and thru lane east of the Porte Cochere have been redesign to now align with the thru lanes both to the north and south of the Hotel Site. Additionally we have defined the Guest Drop-Off area with pervious concrete pavers to better identify the Hotel Drop-off area. Comment Number: 2. Comment Originated: 09/02/2015 09/02/2015: The north-south walkway that connects to Texas Roadhouse and Cinemark needs to be widened so it is more effective in achieving walkability among the three uses. Seven feet is too narrow. This walkway must include trees in grates or wells. In addition, this walkway should include features and amenities for pedestrians traversing the shopping center. Response: The east/west pedestrian walk on the north side of the hotel has been widened to 8 feet with Tree grates and street trees placed at approximately 40 feet on center. The north/south pedestrian Connection has been made as wide as possible while still allowing for adequate vehicular movement on the east side of the hotel both north and south. 2 Comment Number: 3. Comment Originated: 09/02/2015 09/02/2015: There does not appear to be a service court for deliveries of supplies. Most hotels dedicate an area in the rear for service trucks. Is there a designated loading zone? Response: There is no dedicated loading zone on the hotel site. However deliveries will be made from the west side of the hotel with trucks staging there deliveries from the 24 foot thru lane on the west side of the hotel. Deliveries are typically made in the early AM hours of the day and should not disrupt Hotel Guest Service or to the other nearby uses such as the Texas Roadhouse of Cinemark Theater Comment Number: 4. Comment Originated: 09/02/2015 09/02/2015: The area devoted to the trash enclosure appears inadequate to also provide for recycling containers. The applicant may not be aware that it is a violation of a City Ordinance to discard cardboard into the waste stream. This leads to a need to install the proper amount of recycling capacity. For information regarding proper sizing of trash and recycling containers, please contact Caroline Mitchell, Environmental Planner, 221-6288 Response: The Trash area has been redesigned to properly allow for Trash containers as well Cardboard Recycling. Additionally an Enclosed Storage area has been added to the Trash Enclosure to better allow for storage of Materials, and excess recycling of waste materials. Comment Number: 5. Comment Originated: 09/02/2015 09/02/2015: Please be aware that the areas described as “Shrubs” will also need to feature a mix of deciduous and evergreen trees. The westerly landscape area will need to include a dense screen of a variety of plant material to mitigate both the onsite and offsite parking lots. This planting of this area should achieve approximately 75% opacity at maturity. Response:The landscape plan has been revised to meet the City’s landscape standards related to the mix of plant material and screening opacity. Comment Number: 6. Comment Originated: 09/02/2015 09/02/2015: The narrative indicates that the hotel will be pet-friendly. To better accommodate pets, the sidewalk loop should also include pedestrian-scaled lighting, benches or seat walls and pet station (bag dispensers, trash containers and the like). If the L.I.D. basins are not intended for dog walking, then, as suggested, a continuous hedge or shrub border is recommended. Response: A “Dog Station” has been added on both the east and west sides of the building near the guest Entries. Additionally Parking lot Pole lighting has been added on both the north and west sides of the Hotel in order to complement and add to the already existing site lighting on the east side of the hotel and the building mounted lighting on the north side of the Cinemark Theater. Comment Number: 7. Comment Originated: 09/02/2015 09/02/2015: A recent site inspection of Cinemark, in conjunction with a proposed Minor Amendment, revealed four dead trees and eight trees in the process of dying due to lack of water. Any existing trees on Lot 11A that are dead or dying must be replaced with larger caliper trees to account for lost maturity. Response: Prior to the Resubmittal of the PDP a complete On/Off-Site Tree inspection will be conducted with the City Forester in order to determine any necessary tree replacement and tree mitigation quantities that may be needed to mitigate for any onsite trees that are dead or dying and trees that will need to be removed in order to accommodate the proposed development of the property. Comment Number: 8. Comment Originated: 09/02/2015 09/02/2015: The electrical transformer must be within ten feet of hard surface 3 from one side and be screened with a solid enclosure meeting the specifications of Light and Power or by dense landscaping. Response: The proposed location of the Transformer has be identified on the PDP Site Plan and should meet the City’s requirements for location to a hard surface and proper landscape screening. Comment Number: 9. Comment Originated: 09/02/2015 09/02/2015: Please describe the details of the enhanced crosswalks. Will these crosswalks be raised? Will there be use of different materials (colored concrete, stamped concrete)? Response: The “Enhanced Pedestrian Crosswalks” identified on the PDP Site Plan will be Scored and Colored Concrete that will provide both color and texture contrast with the adjacent asphalt pavement and the concrete pervious pavers. Comment Number: 10. Comment Originated: 09/02/2015 09/02/2015: The patio on the north side would benefit from a low open fence or screen wall to protect users from the vehicles using the 20-foot wide access drive. Response: A fence has been added to the North Patio area, see Architectural Elevations. Comment Number: 11. Comment Originated: 09/02/2015 09/02/2015: While architectural elevations were not provided, online images revealed a prototypical architectural character that appeared rather basic and unadorned. To mitigate this, staff recommends that the selected masonry material must be carried up the east elevation to at least the top of the second floor. On the remaining elevations, the masonry may be terminated at the top of the first floor. The columns of the porte cochere must be clad in matching masonry. Staff recommends that locally sourced stone be selected as the masonry material to firmly establish a sense of place and connection to the region. Response: See Architectural Elevations for the architects response to the above comments. Comment Number: 12. Comment Originated: 09/02/2015 09/02/2015: Keep in mind that Section 3.5.3(E)(6) requires that the building feature a distinctive recognizable top and that a flat wall not simply terminate at a flat roof. A recognizable top may consist of cornice treatments, sloping roof with overhangs and brackets, stepped parapets and the like. Response: See Architectural Elevations for the architects response to Section 3.5.3E-6 Comment Number: 13. Comment Originated: 09/02/2015 09/02/2015: The online images indicate that the building is topped with an illuminated cube feature. Please note that Section 3.5.3(E)(9) prohibits illuminated translucent materials as building components. Response: See Architectural Elevations for the architect response to Section 3.5.3E-9 Comment Number: 14. Comment Originated: 09/03/2015 09/03/2015: Along the north fire access lane, on the north side, please consider a cross-section that includes 20 feet of drivable surface for fire apparatus, a roll-over curb, and a concrete walk (minimum six feet) that is also constructed and rated to support fire apparatus. Response: Emergency Vehicle Access and apparatus staging has been coordinated with PFA. 4 Department: Engineering Development Review Contact: Sheri Langenberger, 970-221-6573, slangenberger@fcgov.com Topic: General Comment Number: 1 Comment Originated: 09/01/2015 09/01/2015: Larimer County Road Impact Fees and Street Oversizing Fees are due at the time of building permit. Please contact Matt Baker at 224-6108 if you have any questions. Response: Noted Comment Number: 2 Comment Originated: 09/01/2015 09/01/2015: The City's Transportation Development Review Fee (TDRF) is due at the time of submittal. For additional information on these fees, please see: http://www.fcgov.com/engineering/dev-review.php Response: Noted Comment Number: 3 Comment Originated: 09/01/2015 09/01/2015: Any public improvements must be designed and built in accordance with the Larimer County Urban Area Street Standards (LCUASS). They are available online at: http://www.larimer.org/engineering/GMARdStds/UrbanSt.htm Response: Noted Comment Number: 4 Comment Originated: 09/01/2015 09/01/2015: This project is responsible for dedicating any right-of-way and easements that are necessary for this project. Information on the dedication process can be found at: http://www.fcgov.com/engineering/devrev.php Response: Noted Comment Number: 5 Comment Originated: 09/01/2015 09/01/2015: Utility plans will be required and a Development Agreement will be recorded once the project is finalized Response: Noted Comment Number: 6 Comment Originated: 09/01/2015 09/01/2015: A Development Construction Permit (DCP) will need to be obtained prior to starting any work on the site. Response: Noted Department: Environmental Planning Contact: Kelly Kimple, , kkimple@fcgov.com Topic: General Comment Number: 1 Comment Originated: 09/01/2015 09/01/2015: With respect to landscaping and design, the City of Fort Collins Land Use Code, in Article 3.2.1 (E)(2)(3), requires that you use low-water use plants and grasses in your landscaping or re-landscaping and reduce bluegrass lawns as much as possible. Response: Noted Comment Number: 2 Comment Originated: 09/01/2015 09/01/2015: The applicant should make note of Article 3.2.1(C) that requires developments to submit a landscape and tree protection plan, and if receiving water service from the City, an irrigation plan, that: "...(4) protects significant 5 trees, natural systems, and habitat, and (5) enhances the pedestrian environment". Note that a significant tree is defined as a tree having DBH (Diameter at Breast Height) of six inches or more. If any of the trees within this site have a DBH of greater than six inches, a review of the trees shall be conducted with Tim Buchanan, City Forester (970-221-6361, tbuchanan@fcgov.com) to determine the status of the existing trees and any mitigation requirements that could result from the proposed development. Response: A tree mitigation plan will be provide at the time of resubmittal of the PDP to the City. Comment Number: 3 Comment Originated: 09/01/2015 09/01/2015: Our city has an established identity as a forward-thinking community that cares about the quality of life it offers its citizens and has many sustainability programs and goals that may benefit your project. Of particular interest may be the: 1. ClimateWise program: http://www.fcgov.com/climatewise/ 2. Zero Waste Plan and the Waste Reduction and Recycling Assistance Program (WRAP): http://www.fcgov.com/recycling/pdf/_20120404_WRAP_ProgramOverview.pdf, contact Caroline Mitchell at 970-221-6288 or cmtichell@fcgov.com 3. Green Building and the Climate Action Plan: http://www.fcgov.com/enviro/green-building.php, contact Tony Raeker at 970- 416-4238 or traeker@fcgov.com 4. Nature in the City Strategic Plan: http://www.fcgov.com/planning/natureinthecity/? key=advanceplanning/natureinthecity/, contact Lindsay Ex at 970-221-6767 or lex@fcgov.com Please consider the City’s sustainability goals and ways for your development to engage with these efforts. Response: Noted Department: Light And Power Contact: Todd Vedder, 970-224-6152, tvedder@fcgov.com Topic: General Comment Number: 1 Comment Originated: 08/31/2015 08/31/2015: There is existing three phase and single phase primary service available on the southwest corner of the lot. Response: Noted Comment Number: 2 Comment Originated: 08/31/2015 08/31/2015: New development charges and electrical capacity charges will apply. A link to our online electric development fee estimator is below. http://www.fcgov.com/utilities/business/builders-and-developers/plant-investmen t-development-fees/electric-development-fee-estimator?id=3 Response: Noted Comment Number: 3 Comment Originated: 08/31/2015 08/31/2015: A commercial service information form (C-1) will have to be filled out for all commercial services. Also please review the Light & Power's Electric 6 Construction Policies Practices & Procedures guidelines to reference our standard electrical requirements to include transformer clearances and meter requirements. A link for both of these documents is below: http://www.fcgov.com/utilities/business/builders-and-developers/development-fo rms-guidelines-regulations Response: Noted Department: PFA Contact: Jim Lynxwiler, 970-416-2869, jlynxwiler@poudre-fire.org Topic: General Comment Number: 1 Comment Originated: 08/26/2015 08/26/2015: PUBLIC-SAFETY RADIO AMPLIFICATION SYSTEM New buildings require a fire department, emergency communication system evaluation (TEST) after the core/shell but prior to final build out. For the purposes of this section, fire walls shall not be used to define separate buildings. Where adequate radio coverage cannot be established within a building, public-safety radio amplification systems shall be designed and installed in accordance with criteria established by the Poudre Fire Authority. Poudre Fire Authority Bureau Admin Policy #07-01 Response: Noted Comment Number: 2 Comment Originated: 08/26/2015 08/26/2015: ROOF ACCESS > IFC 504.3: New buildings four or more stories in height shall be provided with a stairway to the roof. Stairway access to the roof shall be in accordance with IFC 1009.12. Such stairways shall be marked at street and floor levels with a sign indicating that the stairway continues to the roof. Response: Noted Comment Number: 3 Comment Originated: 08/26/2015 08/26/2015: FIRE STANDPIPE SYSTEM IFC Sections 905 and 913: Standpipe systems shall be provided in new buildings and structures in accordance with Section 905 or the 2012 International Fire Code. Approved standpipe systems shall be installed throughout buildings where the floor level of the highest story is located more than 30 feet above the lowest level of fire department vehicle access. The standpipe system shall be capable of supplying at minimum of 100 psi to the top habitable floor. An approved fire pump may be required to achieve this minimum pressure. Buildings equipped with standpipes are required to have a hydrant within 100 feet of the Fire Department Connection. Response: Noted Comment Number: 4 Comment Originated: 08/26/2015 08/26/2015: WATER SUPPLY Hydrant spacing and flow must meet minimum requirements based on type of occupancy. The existing hydrant on the west side of the building may be relocated to an approved location but may not be removed. Hydrant spacing within the commercial complex, although sparse within the core of the site, currently meets minimum standards for distance and separation. A hydrant is still required within 100' of the FDC for any building equipped with a standpipe 7 system (See comment #5 below). The location of the FDC is typically on the front of the building (See comment #8 below) but in this case Assistant Fire Marshal, Joe Jaramillo believes we can locate the FDC on the west side of the building and meet the 100' distance requirement to the hydrant. > IFC 508.1 and Appendix B: COMMERCIAL REQUIREMENTS: Hydrants to provide 1,500 gpm at 20 psi residual pressure, spaced not further than 300 feet to the building, on 600-foot centers thereafter. Response: Noted Comment Number: 5 Comment Originated: 08/26/2015 08/26/2015: HYDRANT FOR STANDPIPE SYSTEMS 2012 IFC 507.1.1: Buildings equipped with a standpipe system installed in accordance with Section 905 shall have a fire hydrant within 100 feet of the fire department connections. Exception: The distance shall be permitted to exceed 100 feet where approved by the fire code official. Response: Noted Comment Number: 6 Comment Originated: 08/26/2015 08/26/2015: FIRE LANES Fire access is required to within 150' of all exterior portions of the first floor. Buildings over 30' in height have additional fire access requirements. The site plan appears to be taking these requirements under consideration with the proposed Emergency Access Easement on the north side of the building, however that fire lane is required to be 30' in width (by local amendment), positioned no closer than 15' from the building. Deviations from these measurements require special approval. The EAE needs to be continuous and connect to the public way. Code language and fire lane specifications provided below to aid in future planning: > IFC 503.1.1: Approved fire Lanes shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. When any portion of the facility or any portion of an exterior wall of the first story of the building is located more than 150 feet from fire apparatus access, the fire code official is authorized to increase the dimension if the building is equipped throughout with an approved, automatic fire-sprinkler system. AERIAL FIRE APPARATUS ACCESS ROADS - WHERE REQUIRED > IFC D105.1: Where the vertical distance between the grade plane and the highest roof surface exceeds 30 feet, approved aerial fire apparatus access roads shall be provided. For purposes of this section, the highest roof surface shall be determined by measurement to the eave of a pitched roof, the intersection of the roof to the exterior wall, or the top of parapet walls, whichever is greater. AERIAL FIRE APPARATUS ACCESS ROADS - WIDTH > IFC D105.2; FCLUC 3.6.2(B)2006; and Local Amendments: Aerial fire apparatus access roads shall have a minimum unobstructed width of 30 feet, 8 exclusive of shoulders, in the immediate vicinity of the building or portion thereof. AERIAL FIRE APPARATUS ACCESS ROADS - PROXIMITY TO BUILDING 2012 IFC D105.3: At least one of the required access routes meeting this condition shall be located within a minimum of 15 feet and a maximum of 30 feet from the building, and shall be positioned parallel to one entire side of the building. The side of the building on which the aerial fire apparatus access road is positioned shall be approved by the fire code official. FIRE LANE SPECIFICATIONS A fire lane plan shall be submitted for approval prior to installation. In addition to the design criteria already contained in relevant standards and policies, any new fire lane must meet the following general requirements: > Shall be designated on the plat as an Emergency Access Easement. > Maintain the required 20 foot minimum unobstructed width & 14 foot minimum overhead clearance. > Be designed as a flat, hard, all-weather driving surface capable of supporting 40 tons. > Dead-end fire access roads in excess of 150 feet in length shall be provided with an approved area for turning around fire apparatus. > The required turning radii of a fire apparatus access road shall be a minimum of 25 feet inside and 50 feet outside. Turning radii shall be detailed on submitted plans. > Be visible by painting and/or signage, and maintained unobstructed at all times. > Additional access requirements exist for buildings greater than 30' in height. Refer to Appendix D of the 2012 IFC or contact PFA for details. International Fire Code 503.2.3, 503.2.4, 503.2.5, 503.3, 503.4 and Appendix D; FCLUC 3.6.2(B)2006 and Local Amendments. Response: Noted Comment Number: 7 Comment Originated: 08/26/2015 08/26/2015: AUTOMATIC FIRE SPRINKLER SYSTEM This building will require a full NFPA13 automatic fire sprinkler system under a separate permit. Please contact Assistant Fire Marshal, Joe Jaramillo with any fire sprinkler related questions at 970-416-2868. Response: Noted Comment Number: 8 Comment Originated: 08/26/2015 08/26/2015: FIRE ALARM AND DETECTION SYSTEMS (Group R-1) Fire alarm systems and smoke alarms shall be installed in Group R-1 occupancies as required in Sections 907.2.8.1 through 907.2.8.3 Response: Noted Comment Number: 7 Comment Originated: 09/02/2015 09/02/2015: HAZARDOUS MATERIALS A list of hazardous materials and quantities shall be provided no later than at time of building permit outlining pool chemistry and on-site, chemical storage. MSDS sheets are required as part of the submittal. Response: Noted 9 Comment Number: 8 Comment Originated: 09/02/2015 09/02/2015: FDC > IFC 912.2: Fire Department Connections shall be installed in accordance with NFPA standards. Fire department connections shall be located on the street side of buildings, fully visible and recognizable from the street or nearest point of fire department vehicle access. The location of the FDC shall be approved by the fire department. Response: Noted Department: Stormwater Engineering Contact: Jesse Schlam, 970-218-2932, jschlam@fcgov.com Topic: Erosion Control Comment Number: 1 Comment Originated: 08/24/2015 08/24/2015: The site disturbs more than 10,000 sq-ft, therefore Erosion and Sediment Control Materials need to be submitted for FDP. The erosion control requirements are in the Stormwater Design Criteria under the Amendments of Volume 3 Chapter 7 Section 1.3.3. Current Erosion Control Materials Submitted do not meet requirements. Please submit; Erosion Control Plan, Erosion Control Report, and an Escrow / Security Calculation. If you need clarification concerning this section, or if there are any questions please contact Jesse Schlam 970-218-2932 or email @ jschlam@fcgov.com Response: A full Erosion Control Plan will be provided at the time the Final Utility Plans are submitted to the City. Contact: Shane Boyle, 970-221-6339, sboyle@fcgov.com Topic: General Comment Number: 2 Comment Originated: 09/01/2015 09/01/2015: A drainage report, erosion control report, and construction plans are required and they must be prepared by a Professional Engineer registered in Colorado. The drainage report must address the four-step process for selecting structural BMPs. There is a final site inspection required when the project is complete and the maintenance is handed over to an HOA or another maintenance organization. The erosion control report requirements are in the Fort Collins Stormwater Manual, Section 1.3.3, Volume 3, Chapter 7 of the Fort Collins Amendments. If you need clarification concerning this section, please contact the Erosion Control Inspector, Jesse Schlam at 224-6015 or jschlam@fcgov.com. Response: Noted Comment Number: 3 Comment Originated: 09/01/2015 09/01/2015: If there is an increase in imperviousness greater than 1000 square feet a drainage report, erosion control report and construction plans are required and they must be prepared by a Professional Engineer registered in Colorado. The drainage report must address the four-step process for selecting structural BMPs. Standard operating procedures (SOPs) for all onsite drainage facilities need to be prepared by the drainage engineer. If there is less than 1,000 square feet of new impervious area on an existing development, a drainage letter along with a grading plan should be sufficient to document the existing and proposed drainage patterns. If there is less than 1,000 but more 10 than 350 square feet of new impervious area; a site grading and erosion control plan is required instead of a complete construction plan set. Response: Noted Comment Number: 4 Comment Originated: 09/01/2015 09/01/2015: Detention for the site has been provided by the downstream detention ponds as indicated in the memo. However, this design was done using outdated rainfall. The design for this site will need to show that sufficient capacity exists downstream if the site runoff is higher than the assumed runoff or additional detention volume will be required to make up the difference. Response: Noted Comment Number: 5 Comment Originated: 09/01/2015 09/01/2015: Fifty percent of the site runoff is required to be treated using the standard water quality treatment as described in the Fort Collins Stormwater Manual, Volume 3-Best Management Practices (BMPs). (http://www.fcgov.com/utilities/business/builders-and-developers/development-f orms-guidelines-regulations/stormwater-criteria) Extended detention is the usual method selected for water quality treatment; however the use of any of the BMPs is encouraged. Response: Noted Comment Number: 6 Comment Originated: 09/01/2015 09/01/2015: Low Impact Development (LID) requirements are required on all new or redeveloping property which includes sites required to be brought into compliance with the Land Use Code. These require a higher degree of water quality treatment for 50% of the new impervious area and 25% of new paved areas must be pervious. Standard operating procedures (SOPs) for all onsite drainage facilities will be included as part of the Development Agreement. More information and links can be found at: http://www.fcgov.com/utilities/what-we-do/stormwater/stormwater-quality/low-im pact-development Response: Noted Comment Number: 7 Comment Originated: 09/01/2015 09/01/2015: The city wide Stormwater development fee (PIF) is $7,817/acre ($0.1795 sq.-ft.) for new impervious area over 350 sq.-ft., and there is a $1,045.00/acre ($0.024/sq.-ft.) review fee. No fee is charged for existing impervious area. These fees are to be paid at the time each building permit is issued. Information on fees can be found at: http://www.fcgov.com/utilities/business/builders-and-developers/plant-investmen t-development-fees or contact Jean Pakech at 221-6375 for questions on fees. There is also an erosion control escrow required before the Development Construction permit is issued. The amount of the escrow is determined by the design engineer, and is based on the site disturbance area, cost of the measures, or a minimum amount in accordance with the Fort Collins Stormwater Manual. Response: Noted Comment Number: 8 Comment Originated: 09/01/2015 09/01/2015: The design of this site must conform to the drainage basin design of the McClellands Creek Master Drainage Plan as well the Fort Collins Stormwater Criteria Manual. 11 Department: Traffic Operation Contact: Martina Wilkinson, 970-221-6887, mwilkinson@fcgov.com Topic: General Comment Number: 1 Comment Originated: 09/01/2015 09/01/2015: This site was assumed to be retail with the original approval of Harmony Village PUD. An extended stay hotel will produce very similar traffic volumes (within a few %) of the approved retail. Therefore, no further anticipated traffic analysis is likely needed. Response: Noted Department: Water-Wastewater Engineering Contact: Shane Boyle, 970-221-6339, sboyle@fcgov.com Topic: General Comment Number: 1 Comment Originated: 09/01/2015 09/01/2015: Existing water and sewer mains in the vicinity include 8-inch water and sewer mains along the western property boundary. Response: Noted Comment Number: 2 Comment Originated: 09/01/2015 09/01/2015: It appears water, sewer, and fire stubs were provided per the original Harmony Village PUD plans. The developer will need to verify whether these stubs were actually installed. If a different tap size is needed from what was stubbed out, the existing service(s) will need to be abandoned at the main. Response: Noted Comment Number: 3 Comment Originated: 09/01/2015 09/01/2015: The sewer modeling appears to show the hotel impacts on the existing sewer system are acceptable. Please submit the sanitary sewer modeling with the Utility Plan submittal. Response: Noted Comment Number: 4 Comment Originated: 09/01/2015 09/01/2015: The water conservation standards for landscape and irrigation will apply. Information on these requirements can be found at: http://www.fcgov.com/standards Response: Noted Comment Number: 5 Comment Originated: 09/01/2015 09/01/2015: Development fees and water rights will be due at building permit. Response: Noted Department: Zoning Contact: Noah Beals, 970-416-2313, nbeals@fcgov.com Topic: General Comment Number: 1 Comment Originated: 08/25/2015 08/25/2015: The sidewalk needs to connect to the existing sidewalk on each of the abutting properties. Response: Noted 12 Comment Number: 2 Comment Originated: 08/25/2015 08/25/2015: The trash enclosure needs a walk-in access separate from the main service gate. Response: A Walk-In Gate will be provided on the north side of the Trash enclosure. Comment Number: 3 Comment Originated: 08/25/2015 08/25/2015: Structures over 40ft in height require a shadow analysis Response: A Shadow Analysis will be submitted at the time the PDP Resubmittal is made. Comment Number: 4 Comment Originated: 08/25/2015 08/25/2015: The landscaped areas will need to include tree stocking. Response: A Tree Stocking Summery will be provided at the time of the PDP Resubmittal after the existing Tree analysis has been conducted with the City Forester. Comment Number: 5 Comment Originated: 08/25/2015 08/25/2015: Add a tree to the landscape island on the east side of the building and on the north property line. Response: Noted Comment Number: 6 Comment Originated: 08/26/2015 08/26/2015: The project is required to provide both covered and fixed bicycle spaces. Response: Noted