HomeMy WebLinkAbout215 MATHEWS OFFICE BUILDING - PDP - PDP150020 - SUBMITTAL DOCUMENTS - ROUND 1 - HAZMATS (4)Century Environmental Hygiene, LLC
3201 E. Mulberry St, Unit C, Fort Collins CO 80524
(970) 266-8000 (970) 266-0022 (Fax) www.centuryenvironmental.com
November 26, 2014
Mr. Brad Oldemeyer
3116 Clyde Street
Fort Collins, CO 80524
Re: 215 Mathews Street, Fort Collins, CO – Lead Waste Stream via TCLP Sampling Report
(CEH: 4826.14)
Dear Mr. Oldemeyer:
The following report addresses the results of one sample we collected for Mr. Oldemeyer to
characterize the lead content with respect to determining whether the waste was a lead hazardous
waste.
The sample (111814PJ-30) was collected from the building prior to renovation. The contents
were plaster/drywall, lumber, roofing, wood trim, flooring, cabinetry/misc/wiring,
doors/windows, and floor stone/concrete components.
The sample was analyzed by ALS Environmental using SW846-1311-/7420 for lead (the
Toxicity Characteristic Leacheate Procedure (TCLP)). The sample contained lead at a level
above the Hazardous Waste definition for lead of 5 mg/kg (mg/l).
A grab sample TCLP contained a lead content that appeared to require that the whole house
would have to be disposed of as a hazardous waste. This would be very costly (as much as
$10,000 or more). We recommend repeating this test with a more accurate method, facilitated by
XRF pre-testing. The cost of a re-test would be approximately $500, but would have at least a
50% chance of allowing the waste to be re-classified as non-hazardous.
Laboratory reports with the pertinent results are attached. Please feel free to contact me if you
have any questions or need further assistance.
Attachments: Lab report
Disclaimer:
No evaluations beyond those described in the report have been made and CEH is not responsible for any hazards or
risks, apparent or otherwise, other than those included in this evaluation. As with any conclusions made based on
visual observations and/or random and limited sampling, there is an inherent possibility that undetected conditions
exist, and CEH does not accept liability for any not reasonably ascertainable from the data or observations made.
Sampling can be inherently obtrusive, and CEH does not accept liability for any damage to the property reasonably
occurring during the course of the work in connection with its duties. The only warrantee expressed or implied is that
the work conforms to standard industry practice at the time it was performed. In the unlikely event a defect in the work
is noted, the client has the option to request that the defect be remedied at no additional cost, or a pro rata deduction in
the fee billed. CEH’s maximum liability to any party shall not exceed the fee for the defective portion of the work.
Any reports issued are for the sole use of the client and reliance on it by others it at their sole risk.
ADDRESS 225 Commerce Drive, Fort Collins Colorado 80524 USA ⎜ PHONE +1 970 490 1511 ⎜ FAX +1 970 490 1522
ALS GROUP USA, CORP. Part of the ALS Group An ALS Limited Company
1411349
Metals:
The sample was analyzed following SW-846, 3rd Edition procedures. Analysis by Trace ICP followed
method 6010B and the current revision of SOP 834.
All acceptance criteria were met with the following exception:
The sample was received intact at ambient temperature by ALS on 11/08/14.
1 of 7
OrderNum: 1411349
Client Name: Century Environmental Hygiene, LLC
Client Project Name: 215 Mathews St, FTC
Client Project Number: 4826.14
Client PO Number:
Lab Sample
Number
Client Sample
Number
Matrix Date
Collected
Time
Collected
COC Number
Sample Number(s) Cross-Reference Table
ALS Environmental -- FC
111B14PJ-30 1411349-1 SOLID 18-Nov-14
111B14PJ-30 1411349-2 LEACHAT 18-Nov-14
Page 1 of 1 Date Printed: Tuesday, November 25, 2014
LIMS Version: 6.727
ALS Environmental -- FC
2 of 7
3 of 7
4 of 7
Project: 4826.14 215 Mathews St, FTC
Sample ID: 111B14PJ-30
Collection Date: 11/18/2014
Matrix: LEACHATE
Analyses Result Qual Units Date Analyzed
Report
Limit
Client: Century Environmental Hygiene, LLC
Work Order: 1411349
Dilution
Factor
Lab ID: 1411349-2
ALS Environmental -- FC
Date: 25-Nov-14
SAMPLE SUMMARY REPORT
Percent Moisture:
Legal Location:
TCLP ICP Metals SW6010 Prep Date: 11/21/2014 PrepBy: NAQ
LEAD 10 0.03 MG/L 1 11/23/2014 18:25
LIMS Version: 6.727 AR Page 2 of 3
ALS Environmental -- FC
5 of 7
Project: 4826.14 215 Mathews St, FTC
Sample ID: 111B14PJ-30
Collection Date: 11/18/2014
Matrix: LEACHATE
Analyses Result Qual Units Date Analyzed
Report
Limit
Client: Century Environmental Hygiene, LLC
Work Order: 1411349
Dilution
Factor
Lab ID: 1411349-2
ALS Environmental -- FC
Date: 25-Nov-14
SAMPLE SUMMARY REPORT
Percent Moisture:
Legal Location:
Explanation of Qualifiers
Radiochemistry:
U or ND - Result is less than the sample specific MDC.
Y2 - Chemical Yield outside default limits.
Y1 - Chemical Yield is in control at 100-110%. Quantitative yield is assumed.
W - DER is greater than Warning Limit of 1.42
* - Aliquot Basis is 'As Received' while the Report Basis is 'Dry Weight'.
# - Aliquot Basis is 'Dry Weight' while the Report Basis is 'As Received'.
G - Sample density differs by more than 15% of LCS density.
M - Requested MDC not met.
L - LCS Recovery below lower control limit.
H - LCS Recovery above upper control limit.
P - LCS, Matrix Spike Recovery within control limits.
N - Matrix Spike Recovery outside control limits
NC - Not Calculated for duplicate results less than 5 times MDC
B3 - Analyte concentration greater than MDC but less than Requested
MDC.
B - Analyte concentration greater than MDC.
M3 - The requested MDC was not met, but the reported
activity is greater than the reported MDC.
D - DER is greater than Control Limit
Inorganics:
B - Result is less than the requested reporting limit but greater than the instrument method detection limit (MDL).
E - The reported value is estimated because of the presence of interference. An explanatory note may be included in the narrative.
U or ND - Indicates that the compound was analyzed for but not detected.
M - Duplicate injection precision was not met.
N - Spiked sample recovery not within control limits. A post spike is analyzed for all ICP analyses when the matrix spike and or spike
duplicate fail and the native sample concentration is less than four times the spike added concentration.
Z - Spiked recovery not within control limits. An explanatory note may be included in the narrative.
* - Duplicate analysis (relative percent difference) not within control limits.
Organics:
U or ND - Indicates that the compound was analyzed for but not detected.
E - Analyte concentration exceeds the upper level of the calibration range.
B - Analyte is detected in the associated method blank as well as in the sample. It indicates probable blank contamination and warns the data user.
J - Estimated value. The result is less than the reporting limit but greater than the instrument method detection limit (MDL).
A - A tentatively identified compound is a suspected aldol-condensation product.
X - The analyte was diluted below an accurate quantitation level.
* - The spike recovery is equal to or outside the control criteria used.
+ - The relative percent difference (RPD) equals or exceeds the control criteria.
G - A pattern resembling gasoline was detected in this sample.
M - A pattern resembling motor oil was detected in this sample.
D - A pattern resembling diesel was detected in this sample.
C - A pattern resembling crude oil was detected in this sample.
ALS Environmental -- FC Date: 11/25/2014 7:52
Project: 4826.14 215 Mathews St, FTC
Client: Century Environmental Hygiene, LLC
Work Order: 1411349
QC BATCH REPORT
Batch ID: IP141121-4-1 Instrument ID ICP6500 Method: SW6010
Qual
Analysis Date: 11/23/2014 18:21
Prep Date: 11/21/2014
Analyte Result %REC
Units: MG/L
ReportLimit
Client ID:
LCS
Run ID: IP141123-1A1
SPK Val
SPK Ref
Value
Control
Limit
DF: 1
Sample ID: EX141120-4
RPD Ref
Value RPD
RPD
Limit
LEAD 5.16 0.03 5 103 80-120 20
Qual
Analysis Date: 11/23/2014 18:17
Prep Date: 11/21/2014
Analyte Result %REC
Units: MG/L
ReportLimit
Client ID:
MB
Run ID: IP141123-1A1
SPK Val
SPK Ref
Value
Control
Limit
DF: 1
Sample ID: EX141120-4
RPD Ref
Value RPD
RPD
Limit
LEAD ND 0.03
Qual
Analysis Date: 11/23/2014 18:42
Prep Date: 11/21/2014
Analyte Result %REC
Units: MG/L
ReportLimit
Client ID: 111B14PJ-30
MS
Run ID: IP141123-1A1
SPK Val
SPK Ref
Value
Control
Limit
DF: 1
Sample ID: 1411349-2
RPD Ref
Value RPD
RPD
Limit
LEAD 15.1 0.03 5 10 98 80-120 20
Qual
Analysis Date: 11/23/2014 18:46
Prep Date: 11/21/2014
Analyte Result %REC
Units: MG/L
ReportLimit
Client ID: 111B14PJ-30
MSD
Run ID: IP141123-1A1
SPK Val
SPK Ref
Value
Control
Limit
DF: 1
Sample ID: 1411349-2
RPD Ref
Value RPD
RPD
Limit
LEAD 15 0.03 5 10 96.4 80-120 15.1 1 20
The following samples were analyzed in this batch: 1411349-2
QC Page: 1 of 1
LIMS Version: 6.727
ALS Environmental -- FC
7 of 7
4 - A pattern resembling JP-4 was detected in this sample.
5 - A pattern resembling JP-5 was detected in this sample.
H - Indicates that the fuel pattern was in the heavier end of the retention time window for the analyte of interest.
L - Indicates that the fuel pattern was in the lighter end of the retention time window for the analyte of interest.
Z - This flag indicates that a significant fraction of the reported result did not resemble the patterns of any of the following petroleum hydrocarbon products:
- gasoline
- JP-8
- diesel
- mineral spirits
- motor oil
- Stoddard solvent
- bunker C
LT - Result is less than requested MDC but greater than achieved MDC.
S - SAR value is estimated as one or more analytes used in the calculation were not detected above the detection limit.
LIMS Version: 6.727 AR Page 3 of 3