C0.00
COVER SHEET
MARCH, 2013 CONTACT INFORMATION
PROJECT TEAM:
Northern Engineering Services, Inc.
Nick Haws, PE
200 South College Avenue, Suite 010
Fort Collins, Colorado 80524
(970) 221-4158
Northern Engineering Services, Inc.
Gary Gilliland, PLS
200 South College Avenue, Suite 010
Fort Collins, Colorado 80524
(970) 221-4158
E N G I N E E R I N G
� � � � � � ��
E N G I N E E R I N G
� � � � � � ��
PLANNER/
LANDSCAPE ARCHITECT
I hereby affirm that these final
construction plans were prepared
under my direct supervision, in
accordance with all applicable City
of Fort Collins and State of
Colorado standards and statutes,
respectively; and that I am fully
responsible for the accuracy of all
design. revisions, and record
conditions that I have noted on
these plans.
These plans have been reviewed by the City of Fort Collins for concept only. The review does not imply responsibility
by the reviewing department, the City of Fort Collins Engineer, or the City of Fort Collins for accuracy and correctness
of the calculations. Furthermore, the review does not imply that quantities of items on the plans are the final quantities
required. The review shall not be construed for any reason as acceptance of financial responsibility by the City of Fort
Collins for additional quantities of items shown that may be required during the construction phase.
DISCLAIMER STATEMENT:
CERTIFICATION STATEMENT:
PROJECT
LOCATION
VICINITY MAP
NORTH
OWNER
SITE ENGINEER
SURVEYOR
Sheet
Of 14 Sheets
GEICO OFFICE BUILDING
T���� �������� ���
����������� �� �������
�������� �� N�������
E���������� S�������, I��.
��� ��� ��� �� �� ���� ���
��� ���� �� ������������
������ ������ ��� ������ ��
� P����������� E������� ��
��� ������ �� N�������
E���������� S�������, I��.
NOT FOR CONSTRUCTION
REVIEW SET
200 S���� C������ A�����, S���� 010
F��� C������, C������� 80524
E N G I N E E R I N G
� � � � � � ��
PHONE: 970.221.4158 FAX: 970.221.4159
���.�������������������.���
C0.01
GENERAL & CONSTRUCTION NOTES
A. GENERAL NOTES
1. All materials, workmanship, and construction of ppublic improvements shall meet or exceed the standards and specifications set forth in the
Larimer County Urban Area Street Standards and applicable state and federal regulations. Where there is conflict between these plans and
the specifications, or any applicable standards, the most restrictive standard shall apply. All work shall be inspected and approved by the
City of Fort Collins.
2. All references to any published standards shall refer to the latest revision of said standard, unless specifically stated otherwise.
3. These public improvement construction plans shall be valid for a period of three years from the date of approval by the City of Fort Collins
Engineer. Use of these plans after the expiration date will require a new review and approval process by the City of Fort Collins prior to
commencement of any work shown in these plans.
4. The engineer who has prepared these plans, by execution and/or seal hereof, does hereby affirm responsibility to the City of Fort Collins, as
beneficiary of said engineer's work, for any errors and omissions contained in these plans, and approval of these plans by the City of Fort
Collins Engineer shall not relieve the engineer who has prepared these plans of all such responsibility. Further, to the extent permitted by
law, the engineer hereby agrees to hold harmless and indemnify the City of Fort Collins, and its officers and employees, from and against all
liabilities, claims, and demands which may arise from any errors and omissions contained in these plans.
5. All storm sewer construction, as well as power and other "dry" utility installations, shall conform to the City of Fort Collins standards and
specifications current at the date of approval of the plans by the City of Fort Collins Engineer.
6. The type, size, location and number of all known underground utilities are approximate when shown on the drawings. It shall be the
responsibility of the Developer to verify the existence and location of all underground utilities along the route of the work before commencing
new construction. The Developer shall be responsible for unknown underground utilities.
7. The Developer shall contact the Utility Notification Center of Colorado (UNCC) at 1-800-922-1987, at least 2 working days prior to beginning
excavation or grading, to have all registered utility locations marked. Other unregistered utility entities (i.e. ditch / irrigation company) are to
be located by contacting the respective representative. Utility service laterals are also to be located prior to beginning excavation or grading.
It shall be the responsibility of the Developer to relocate all existing utilities that conflict with the proposed improvements shown on these
plans.
8. The Developer shall be responsible for protecting all utilities during construction and for coordinating with the appropriate utility company for
any utility crossings required.
9. If a conflict exists between existing and proposed utilities and/or a design modification is required, the Developer shall coordinate with the
engineer to modify the design. Design modification(s) must be approved by the City of Fort Collins prior to beginning construction.
10. The Developer shall coordinate and cooperate with the City of Fort Collins, and all utility companies involved, to assure that the work is
accomplished in a timely fashion and with a minimum disruption of service. The Developer shall be responsible for contacting, in advance,
all parties affected by any disruption of any utility service as well as the utility companies.
11. No work may commence within any public storm water, sanitary sewer or potable water system until the Developer notifies the utility
provider. Notification shall be a minimum of 2 working days prior to commencement of any work. At the discretion of the water utility
provider, a pre-construction meeting may be required prior to commencement of any work.
12. The Developer shall sequence installation of utilities in such a manner as to minimize potential utility conflicts. In general, storm sewer and
sanitary sewer should be constructed prior to installation of the water lines and dry utilities.
13. The minimum cover over water lines is 4.5 feet and the maximum cover is 5.5 feet unless otherwise noted in the plans and approved by the
POINT OF BEGINNING
FND #4 REBAR w/PLASTIC CAP
LS 38353 "THOMAS"
(S59�18'37"W 0.71' FROM TRUE LOCATION)
FND #4 REBAR
w/PLASTIC CAP
LS 38353 "THOMAS"
(S38�26'50"W 0.58'
FROM TRUE LOCATION)
FND #4 REBAR
w/PLASTIC CAP
LS 38353 "THOMAS"
FND #4 REBAR
w/PLASTIC CAP
LS 7839 "JHS&A"
FND #4 REBAR
w/PLASTIC CAP
LS 7839 "JHS&A"
HARMONY ROAD
(PUBLIC ROW-WIDTH VARIES)
(BOOK 1434, PAGE 322 AND
HARMONY VILLAGE P.U.D., REPLAT NO. 3)
TIMBERLINE ROAD
(PUBLIC ROW-WIDTH VARIES)
(REC. NO. 96058040, 2001059218 & 2003009675
AND HARMONY SCHOOL SHOPS, 1ST FILING)
POINT OF
COMMENCEMENT
SOUTHEAST CORNER
SECTION 31-7-68
3" ALUM CAP LS 17497
(PER MONUMENT RECORD)
WEST 71.21' (R)
N45�00'10"E 42.51' (R)
N00�26'24"E 84.17' (R)
NORTHEASTERLY 43.79' (R)
EAST 60' (R)
N89�31'41"W 2646.52'
S00�16'16"W 2657.42'
30' ROW
FND #4 REBAR
w/PLASTIC CAP
LS 7839 "JHS&A"
BASIS OF BEARINGS
SOUTH LINE OF THE
SE 1/4 SECTION 31-7-68
UNPLATTED
FND #4 REBAR
FND #4 REBAR
w/PLASTIC CAP
LS 7839 "JHS&A"
EAST 140.80' (R)
AVERY, BROWN AND PRESTON
DITCH EASEMENT (BK L PG 121)
15' ACCESS &
UTILITY EASEMENT
CONSTRUCTION &
MAINTENANCE EASEMENT TO
THE CITY OF FORT COLLINS
REC. NO. 90004622
T FO
VAULT
ELEC
F.O.
�
�
�
M
�
FO
�
�
�
TRAFFIC
VAULT
T S
G G G G G
G G G
G G
G
FO
FO FO
FO FO FO
FO FO FO FO
E E E E E
E
E E
E E
E
E
E E
W W W W W W W W W W W
W
W W W W W W W W
W
W
�
AC
FO
G G G G G G
G
G G G G G
CTV CTV CTV CTV CTV CTV CTV
E E E E E E
G
X X
X
�
AC
���
���
T
ELEC
FO
ELEC
�
M
�
HARMONY ROAD
(PUBLIC ROW-WIDTH VARIES)
UP
UP
VAN
X X
X
LINE TABLE
LINE
L1
L4
L5
L6
L7
L8
L10
L11
L12
L14
L15
L19
L20
LENGTH
11.38'
16.09'
32.00'
60.02'
142.85'
15.00'
15.00'
26.00'
17.24'
15.00'
61.00'
11.89'
16.11'
BEARING
N00�26'26.27"E
S00�26'39.67"W
N89�33'33.73"W
N00�26'39.67"E
S89�31'40.93"E
S00�27'57.48"W
S89�31'40.93"E
S00�27'57.48"W
N89�31'40.93"W
S00�28'19.07"W
N89�31'40.93"W
S00�26'26.27"W
N00�26'26.27"E
Curve Table
CURVE
C1
C2
C3
C4
C5
C6
DELTA
51�50'26"
128�09'21"
89�59'38"
UP
UP
VAN
T FO
VAULT
ELEC
F.O.
�
�
�
M
�
FO
�
�
�
TRAFFIC
VAULT
T S
G G G G G
G G G
G G
G
FO
FO FO
FO FO FO
FO FO FO FO
E E E E E
E
E E
E E
E
E
E E
W W W W W W W W W W
W
W W W W W W W W
W
W
�
G G G G G G
G
G G G G G
CTV CTV CTV CTV CTV CTV CTV
E E E E E E
X X
X
�
T
ELEC
FO
ELEC
M
�
W W W
W
W W
W W W W W W W W W W W W W W W W
SS SS
W W W
M
�
ST
X X X X
X
X X X
X
M
UP
UP
VAN
UD UD UD UD UD UD UD UD UD UD
FFE=66.00
PAVERS
LANDSCAPE WALL
MONITORING
BASINS
6" PERFORATED
UNDER DRAIN
MONITORING
BASIN
COMBINATION INLET
W/ ORIFICE PLATE
RIBBON
CURB
OUTFALL CURB
AND GUTTER
INFLOW CURB
AND GUTTER PROPOSED
AREA INLET
PROPOSED
AREA
INLET
PROPOSED
AREA
INLET
2' TRICKLE
PAN
EXISTING 30" VERTICAL
CURB AND GUTTER
30" VERTICAL
CURB AND GUTTER
EXISTING STREET ACCESS
6" PERFORATED
UNDER DRAIN
PROPOSED
HANDICAP
RAMP
RIBBON
CURB
INSTALL SCOURSTOP
TRANSITION MAT ABOVE
SC-250 NORTH AMERICAN
GREEN EROSION MAT
TRAFFIC RATED
CLEANOUT
ACCESS DRIVE TO BE REMOVED & REPLACED
WITH 30" VERTICAL CURB & GUTTER
APPROXIMATE LIMITS OF
ASPHALT TO BE REMOVED
M
�
ST
X X X X
X
X X X
X
M
UD UD UD UD UD UD UD UD UD UD
UP
UP
VAN
SF
SF SF SF
SF
SF SF SF
SF
SF SF SF
SF
SF SF SF
SF SF
SF SF SF SF SF
SF
SF SF SF SF SF
SF
SF SF SF
SF
SF
SF
SF SF SF
SF
SF
SF SF SF SF
SF SF
CWA
Sheet
Of 14 Sheets
GEICO OFFICE BUILDING
T���� �������� ���
����������� �� �������
�������� �� N�������
E���������� S�������, I��.
��� ��� ��� �� �� ���� ���
��� ���� �� ������������
������ ������ ��� ������ ��
� P����������� E������� ��
��� ������ �� N�������
E���������� S�������, I��.
NOT FOR CONSTRUCTION
REVIEW SET
200 S���� C������ A�����, S���� 010
F��� C������, C������� 80524
E N G I N E E R I N G
� � � � � � ��
PHONE: 970.221.4158 FAX: 970.221.4159
���.�������������������.���
NORTH
CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
Sheet
Of 14 Sheets
GEICO OFFICE BUILDING
T���� �������� ���
����������� �� �������
�������� �� N�������
E���������� S�������, I��.
��� ��� ��� �� �� ���� ���
��� ���� �� ������������
������ ������ ��� ������ ��
� P����������� E������� ��
��� ������ �� N�������
E���������� S�������, I��.
NOT FOR CONSTRUCTION
REVIEW SET
200 S���� C������ A�����, S���� 010
F��� C������, C������� 80524
E N G I N E E R I N G
� � � � � � ��
PHONE: 970.221.4158 FAX: 970.221.4159
���.�������������������.���
C5.01
CONSTRUCTION DETAILS
EROSION CONTROL
CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.
Call before you dig.
R
VEHICLE CONTROL TRACKING PAD
CURB INLET PROTECTION
IP
WATTLE INSTALLATION
FLOW
3'-4'
ADJACENT ROLLS SHALL
TIGHTLY ABUT
W1 NOTES:
INSTALLATION:
WHEN INSTALLING RUNNING LENGTHS OF WATTLES, BUTT THE SECOND
WATTLE TIGHTLY AGAINST THE FIRST, DO NOT OVERLAP THE ENDS. STAKE
THE WATTLES AT EACH END AND FOUR FOOT ON CENTER. FOR EXAMPLE:
A 25 FOOT WATTLE USES 6 STAKES
A 20 FOOT WATTLE USES 5 STAKES
A 12 FOOT WATTLE USES 4 STAKES
STAKES SHOULD BE DRIVEN THROUGH THE MIDDLE OF THE WATTLE.
LEAVING 2 - 3 INCHES OF THE STAKE PROTRUDING ABOVE THE WATTLE. A
HEAVY SEDIMENT LOAD WILL TEND TO PICK THE WATTLE UP AND COULD
PULL IT OFF THE STAKES IF THEY ARE DRIVEN DOWN TOO LOW. IT MAY BE
NECESSARY TO MAKE A HOLE IN THE WATTLE WITH A PICK END OF YOUR
MADDOX IN ORDER TO GET THE STAKE THROUGH THE STRAW. WHEN
STRAW WATTLES ARE USED FOR FLAT GROUND APPLICATIONS, DRIVE THE
STAKES STRAIGHT DOWN; WHEN INSTALLING WATTLES ON SLOPES, DRIVE
THE STAKES PERPENDICULAR TO THE SLOPE.
DRIVE THE FIRST END STAKE OF THE SECOND WATTLE AT AN ANGLE
TOWARD THE FIRST WATTLE IN ORDER TO HELP ABUT THEM TIGHTLY
TOGETHER. IF YOU HAVE DIFFICULTY DRIVING THE STAKE INTO EXTREMELY
T
�
ST
CTV CTV CTV CTV CTV CTV CTV CTV CTV CTV CTV CTV CTV CTV
X X X X
X
X X X
X
T
UD UD UD UD UD UD UD UD UD UD
UP
UP
VAN
6" PERFORATED
UNDER DRAIN
A1
A2
A3
A4
OE1
ON1
OS1
COMBINATION INLET
W/ ORIFICE PLATE
PERMEABLE
PAVER DETENTION
RIBBON
CURB
OUTFALL CURB
AND GUTTER
INFLOW CURB
AND GUTTER
PROPOSED AREA INLET
PROPOSED
AREA
INLET
PROPOSED
AREA
INLET
2' TRICKLE
PAN
30" VERTICAL
CURB AND GUTTER
30" VERTICAL
CURB AND GUTTER
EXISTING DRIVE ACCESS
a1
a2
a3
a4
on1
on1
os1
os1
oe1
MONITORING
BASIN
MONITORING
BASIN
MONITORING
Typical Gravity Wall Section
Compac Unit - 1" Setback
Foundation Soil
Finished Grade
Unreinforced Concrete or
Crushed Stone Leveling Pad
Design Height
Retained Soil
Unit Drainage Fill
(3/4" Crushed
Rock or Stone)
24"
8" Min. Low Permeable Soil Keystone Cap Unit
4" Perforated PVC Drainage Tile
Wrapped in Filter Fabric
(If Required)
Approximate Limits
of Excavation
Keystone Compac Unit
1" - 1 1/4"
8"
TOW Elevation
BOW Elevation
Section
Leveling Pad Detail
W
6"
W + 12"
Elevation
6" Crushed Rock or
Unreinforced Concrete
Leveling Pad
8" or 16"
Step
Note:
1. The leveling pad is to be constructed of
crushed stone or 2000 psi � unreinforced
concrete.
1/2" x 5 1/4"
Fiberglass Pins
Front Face
Compac Unit
Compac Elevation
Compac Plan
Cap Unit Elevation
Cap Unit Plan
8'' �
12''
5'-4"'
2'-8"'
12''
7" �
12''
7" � 2'-8"'
Cap Unit Elevation
Cap Unit Plan
Universal
Cap Unit Option
Straight Split
Cap Unit Option
THICKENED
EDGE
PAVER SECTION WITH UNDERDRAIN
FLAPGATE STRUCTURE; STRM 4 OUTLET
Sheet
Of 14 Sheets
GEICO OFFICE BUILDING
T���� �������� ���
����������� �� �������
�������� �� N�������
E���������� S�������, I��.
��� ��� ��� �� �� ���� ���
��� ���� �� ������������
������ ������ ��� ������ ��
� P����������� E������� ��
��� ������ �� N�������
E���������� S�������, I��.
NOT FOR CONSTRUCTION
REVIEW SET
200 S���� C������ A�����, S���� 010
F��� C������, C������� 80524
E N G I N E E R I N G
� � � � � � ��
PHONE: 970.221.4158 FAX: 970.221.4159
���.�������������������.���
CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.
Call before you dig.
R
C7.01
CONSTRUCTION DETAILS
8 PAVER SECTION WITH UNDERDRAIN
6 DIMENSIONS FOR SLOTTED PVC PIPE
SCREEN SLOT TABLE
A B C D E
PIPE SIZE ROWS OF
SLOTS
MAXIMUM
SLOT
LENGTH
MAXIMUM
SLOT WIDTH
APPROX. SLOT
SPACING O.C.
MINIMUM
OPEN AREA
PER FOOT
6" 3 (MIN.) - 6 (MAX.) 1-3/8" 0.032" 0.516" 1.98 SQ. IN.
7 MONITORING BASIN
4" MIN
EXTEND MIN. 6" INTO SUBGRADE
6"
1.58'
INTEGRATED DUCTILE IRON
FRAME & SOLID GRATE TO MATCH
BASIN O.D.
Sheet
Of 14 Sheets
GEICO OFFICE BUILDING
T���� �������� ���
����������� �� �������
�������� �� N�������
E���������� S�������, I��.
��� ��� ��� �� �� ���� ���
��� ���� �� ������������
������ ������ ��� ������ ��
� P����������� E������� ��
��� ������ �� N�������
E���������� S�������, I��.
NOT FOR CONSTRUCTION
REVIEW SET
200 S���� C������ A�����, S���� 010
F��� C������, C������� 80524
E N G I N E E R I N G
� � � � � � ��
PHONE: 970.221.4158 FAX: 970.221.4159
���.�������������������.���
CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.
Call before you dig.
R
C7.02
CONSTRUCTION DETAILS
12" - 30" DRAIN BASIN 12" - 30" INLINE DRAIN
BACKFILL MATERIAL BELOW AND TO
SIDES OF STRUCTURE SHALL BE NATIVE SOIL
AND BE PLACED UNIFORMLY IN 12" LIFTS AND
COMPACTED TO A MIN OF 90%
DWG SIZE A SCALE 1:25 SHEET 1 OF 1 DWG NO. 7001-110-111 REV B
3130 VERONA AVE
BUFORD, GA 30518
PHN (770) 932-2443
FAX (770) 932-2490
���.���������-��.���
12 IN - 30 IN DB & ID NON TRAFFIC INSTALLATION
TITLE
PROJECT NO./NAME
MATERIAL
DATE
APPD BY
DATE 9-30-99
THIS PRINT DISCLOSES SUBJECT MATTER IN WHICH DRAWN BY CJA
NYLOPLAST HAS PROPRIETARY RIGHTS. THE RECEIPT
OR POSSESSION OF THIS PRINT DOES NOT CONFER,
TRANSFER, OR LICENSE THE USE OF THE DESIGN OR
TECHNICAL INFORMATION SHOWN HEREIN
REPRODUCTION OF THIS PRINT OR ANY INFORMATION
CONTAINED HEREIN, OR MANUFACTURE OF ANY
ARTICLE HEREFROM, FOR THE DISCLOSURE TO OTHERS
IS FORBIDDEN, EXCEPT BY SPECIFIC WRITTEN
PERMISSION FROM NYLOPLAST.
9-30-99
Sheet
Of 14 Sheets
GEICO OFFICE BUILDING
T���� �������� ���
����������� �� �������
�������� �� N�������
E���������� S�������, I��.
��� ��� ��� �� �� ���� ���
��� ���� �� ������������
������ ������ ��� ������ ��
� P����������� E������� ��
��� ������ �� N�������
E���������� S�������, I��.
NOT FOR CONSTRUCTION
REVIEW SET
200 S���� C������ A�����, S���� 010
F��� C������, C������� 80524
E N G I N E E R I N G
� � � � � � ��
PHONE: 970.221.4158 FAX: 970.221.4159
���.�������������������.���
CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.
Call before you dig.
R
C7.03
CONSTRUCTION DETAILS
A A
B
B
A A
������
������
6 6 6 6 6 6 6 6 6 6 6 6
6 6 6 6 6 6 6 6 6 6 6 6 6
6
COMPACTED GRANULAR MATERIAL
CONFORMING TO CDDH #67
LOWER LIMIT OF
TRENCH WALL
SLOPING
INITIAL LIFT *
12 IN. MIN.
PIPE O.D.
4 IN. MIN.
TRENCH WIDTH AS SPECIFIED
IN SECTION 02221
COMPACTED GRANULAR MATERIAL
CONFORMING TO CDDH #67
*
BEDDING REQUIRMENTS
WW-1
��
���� �������
U
S
A
A
S
U
I
E
J
W
�������
�������
LID PLAN VIEW
LID SECTION VIEW
VALVE BOX SECTION VIEW
W
J
E
I
CJA
NON TRAFFIC INSTALLATION
BACKFILL MATERIAL BELOW AND TO
SIDES OF STRUCTURE SHALL BE NATIVE SOIL
AND BE PLACED UNIFORMLY IN 12" LIFTS AND
COMPACTED TO A MIN OF 90%
REV. DESCRIPTION BY MM/DD/YY CHK'D
4640 TRUEMAN BLVD
HILLIARD, OHIO 43026
NOTE:ALL DIMENSIONS
ARE � 1/2 FOOT.
DRAWING NUMBER:
NTS
CKS
10/10/06
1 OF 1
1 UPDATED DRAWING TJR 02/20/07 CKS
NOTES:
1. MAXIMUM INSERTION ANGLE SHALL NOT EXCEED REQUIREMENTS AS SPECIFIED BY THE MANUFACTURER.
2. SEE STANDARD DETAILS STD-202 (A-B) THROUGH STD-204 (A-E) FOR STRUCTURE CONNECTIONS, PRODUCT INFORMATION AND
DIMENSIONAL PIPE DATA. INSTALLATION RECOMMENDATIONS ARE ALSO SPECIFIED IN TECHNICAL NOTE 5.04: HDPE CONNECTIONS
TO MANHOLES AND STRUCTURES.
3. PERFORMANCE HIGHLY DEPENDENT ON INSTALLATION. CONTRACTOR MUST INSURE MANHOLE GASKET IS UNIFORMLY SEATED
AROUND STRUCTURE ADAPTER. EXTRA PRECAUTIONS MUST BE TAKEN TO PREVENT DIFFERENTIAL SETTLEMENT BETWEEN THE
PIPE AND MANHOLE.
� 2007 ADS, INC.
VARIES
INSURE BACKFILL IS
PLACED UNDER PIPE
AND PROPERLY
COMPACTED
1 1/2 I.D.
MIN.
1 1/2 1.D.
MIN.
FINISH GRADE
MANHOLE/STRUCTURE WALL
FIRST COUPLER SHOULD BE
18" (045m) FROM WALL OR BE
ENCASED IN FLOWABLE FILL
BEDDING
NATIVE SOIL
SUITABLE FOUNDATION
FINISH GRADE
CLASS I OR II BACKFILL PER
ASTM D2321. COMPACTED IN
8" (0.2m) MAX. LIFTS TO A
MIN. OF 90% MAX. STANDARD
PROCTOR DENSITY
MANHOLE OPENING
OUTSIDE DIAMETER
OF HDPE PIPE
12" (0.3m)
MIN.
UNDISTURBED
EARTH
N
Y
L
O
P
L
A
S
T
DWG SIZE A SCALE 1:4 SHEET 1 OF 1 DWG NO. 7001-110-197 REV B
3130 VERONA AVE
BUFORD, GA 30518
PHN (770) 932-2443
FAX (770) 932-2490
���.���������-��.���
8 IN DOME GRATE ASSEMBLY
TITLE
PROJECT NO./NAME
MATERIAL
DATE
REVISED BY
DATE 3-3-06
THIS PRINT DISCLOSES SUBJECT MATTER IN WHICH DRAWN BY EBC
NYLOPLAST HAS PROPRIETARY RIGHTS. THE RECEIPT
OR POSSESSION OF THIS PRINT DOES NOT CONFER,
TRANSFER, OR LICENSE THE USE OF THE DESIGN OR
TECHNICAL INFORMATION SHOWN HEREIN
REPRODUCTION OF THIS PRINT OR ANY INFORMATION
CONTAINED HEREIN, OR MANUFACTURE OF ANY
ARTICLE HEREFROM, FOR THE DISCLOSURE TO OTHERS
IS FORBIDDEN, EXCEPT BY SPECIFIC WRITTEN
PERMISSION FROM NYLOPLAST.
3-13-10
EBC
0899CGD
DUCTILE IRON
8" DOME GRATE
DIMENSIONS ARE FOR REFERENCE ONLY
ACTUAL DIMENSIONS MAY VARY
DIMENSIONS ARE IN INCHES
QUALITY: MATERIALS SHALL CONFORM TO ASTM A536 GRADE 70-50-05
PAINT: CASTINGS ARE FURNISHED WITH A BLACK PAINT
LOCKING DEVICE AVAILABLE UPON REQUEST SEE DRAWING NO.
7001-110-228
APPROX. DRAIN AREA = 30.00 SQ IN
APPROX. WEIGHT = 4.54 LBS
8" INLINE DRAIN OR
8" DRAIN BASIN BODY TOP
� 8.00
4.00
®
�2010 NYLOPLAST
DWG SIZE A SCALE 1:6 SHEET 1 OF 1 DWG NO. 7001-110-228 REV B
3130 VERONA AVE
BUFORD, GA 30518
PHN (770) 932-2443
FAX (770) 932-2490
���.���������-��.���
8 IN DOME LOCKING GRATE ASSEMBLY
TITLE
PROJECT NO./NAME
MATERIAL
DATE
REVISED BY
DATE 2-20-06
THIS PRINT DISCLOSES SUBJECT MATTER IN WHICH DRAWN BY EBC
NYLOPLAST HAS PROPRIETARY RIGHTS. THE RECEIPT
OR POSSESSION OF THIS PRINT DOES NOT CONFER,
TRANSFER, OR LICENSE THE USE OF THE DESIGN OR
TECHNICAL INFORMATION SHOWN HEREIN
REPRODUCTION OF THIS PRINT OR ANY INFORMATION
CONTAINED HEREIN, OR MANUFACTURE OF ANY
ARTICLE HEREFROM, FOR THE DISCLOSURE TO OTHERS
IS FORBIDDEN, EXCEPT BY SPECIFIC WRITTEN
PERMISSION FROM NYLOPLAST.
3-14-10
EBC
1/4-20 X 4 1/2" LONG HEX BOLT
(7/16" SOCKET) ZINC-PLATED STEEL
8" DOME GRATE
8" DUCTILE IRON GRATE LOCK BAR
1/4-20 X 1/2" LONG SOCKET HEAD CAP SREWS
(ALLEN HEAD) BLACK STEEL
2 PLACES
DRILL � .281 HOLE THRU
DRILL � .281 HOLE
THRU 2 PLACES
0899CGDL
®
�2010 NYLOPLAST
B
A
D MIN
DWG SIZE A SCALE 1:25 SHEET 1 OF 1 DWG NO. 7001-110-104 REV D
3130 VERONA AVE
BUFORD, GA 30518
PHN (770) 932-2443
FAX (770) 932-2490
���.���������-��.���
DRAIN BASIN WITH REDUCER OPTIONS
TITLE
PROJECT NO./NAME
MATERIAL
DATE
REVISED BY
DATE 2-6-03
THIS PRINT DISCLOSES SUBJECT MATTER IN WHICH DRAWN BY CJA
NYLOPLAST HAS PROPRIETARY RIGHTS. THE RECEIPT
OR POSSESSION OF THIS PRINT DOES NOT CONFER,
TRANSFER, OR LICENSE THE USE OF THE DESIGN OR
TECHNICAL INFORMATION SHOWN HEREIN
REPRODUCTION OF THIS PRINT OR ANY INFORMATION
CONTAINED HEREIN, OR MANUFACTURE OF ANY
ARTICLE HEREFROM, FOR THE DISCLOSURE TO OTHERS
IS FORBIDDEN, EXCEPT BY SPECIFIC WRITTEN
PERMISSION FROM NYLOPLAST.
3-11-10
EBC
B
A
C MIN
CONE STYLE REDUCER
NOTE: DIMENSIONS ARE FOR REFERENCE ONLY
ACTUAL DIMENSIONS MAY VARY
®
�2010 NYLOPLAST
CAP STYLE REDUCER 6" MIN ON 8" - 24"
10" MIN ON 30"
6" MIN ON 8" - 24"
10" MIN ON 30"
10 100-YR ORIFICE PLATE DETAIL
NOTES:
1 - GRATES/SOLID COVERS SHALL BE DUCTILE IRON PER ASTM A536 GRADE 70-50-05
2 - FRAMES SHALL BE DUCTILE IRON PER ASTM A536 GRADE 70-50-05
3 - DRAIN BASIN TO BE CUSTOM MANUFACTURED ACCORDING TO PLAN DETAILS SEE DRAWING NO. 7001-110-065
4 - PERFORATIONS SHOULD NOT BE ON OR WITHIN 1" OF ADAPTERS.
5 - HOLES SHOULD BE STAGGERED EVERY OTHER ROW, AS SHOWN.
6 - MIN. 90� SEPARATION BETWEEN HOLES (MAX. 4 HOLES PER ROW)
2" MIN
� .375" MAX
SIDE VIEW
HOLE SIZE & LOCATION NTS
ENLARGED TO SHOW DETAIL
6" THE BACKFILL MATERIAL SHALL BE CRUSHED STONE OR OTHER
GRANULAR MATERIAL MEETING THE REQUIREMENTS OF CLASS II
MATERIAL AS DEFINED IN ASTM D2321. BEDDING & BACKFILL FOR
SURFACE DRAINAGE INLETS SHALL BE PLACED & COMPACTED
UNIFORMLY IN ACCORDANCE WITH ASTM D2321.
TOP 10" TO BE SOLID, WITHOUT PERFORATIONS
10" SOLID
TOP
NO PERFORATIONS
WITHIN 1" OF ADAPTORS
OPEN BOTTOM
(NO BOTTOM CAP)
NYLOPLAST SOLID H-20
HINGED GRATE
(ROTATE TO MATCH
PAVER PATTERN)
12" (W���� & S����)
I� ���� ������� �� ���� ����
4' �� �������� �������/��������,
�� ���� �� ������� ��� ��������.
E��� �� P������� ��
L�� �� E������� G�����
C��������
L���� �� S�������
M��������
P�������
T��������
V�����
V�����
1" (���.)
(S�� N��� 9 ����� ��� S����.)
4" (���.)
6" (���.)
T����� W����
V�����
2'
(���.)
B������ M�������
U���������� S���
U������ C������
N�� A������/C�������
C���� R��� B���
E������� R��� B���
6" F��� D���� A������ ��
X/Y C�������� S������
NOTES:
1. A�� �������� ����� �� ���������� �� ���������� ���� ��� ����� ������ ������ ��������� ��������� �� ���
L���� E����� E�������.
2. P���� �� ��������� �� �������/��������, �������� ���� ����� �� ��� ��� �� � �����, ��������, ��� ��������
����.
3. W���� ��� ����������� ����� ��� ���-���������, � ����/������ ������ (1 ���� ���) ��� �� ����������� ���
�������� ��������.
4. T����� ����� ����� ��� �� ���� ���� 16" ��� ���� ���� 12" ����� ���� ��� ������� �������� �� ��� ����.
5. U�� � #4 ����� �� ������� ����� ��� ��������� �� �������� ����������� ��������.
6. R���� �� C������ 22, M�������� & C����������� S������������� ��� ���������� ��� ������� ������������.
7. I� ���������� �����, ��� ��������� ����� ����� �� ��������, ������ & �������.
8. I� �������� ��������, � ������� �� ��� ������ �������� ����� ���� �� ��������.
9. B������ �������� ����� ���� ���������� ����� ����� ����� �� �� �� ������ ����, ������ �� ����� ��
���������� ��������; ����, ������� �������� ����� �� ������ �� � ����� 12" ����� ����.
9 TYPICAL CLEANOUT DETAIL
LANDSCAPED AREAS
TRAFFIC/PAVED AREAS
Dimensions & Availability
Will Vary by Region
Dimensions & Availability
Will Vary by Region
Dimensions May Vary
by Region
Top of Wall Steps
(2) - 4" Cap Units or
(1) - 8" Cap Unit
Note:
1. Secure all cap units with Keystone
Kapseal or equal.
8" Keystone
Unit
4" Cap Unit
Compac Unit
8"
Depth:
Height:
12"
Width: 18"
Weight: 90 lbs
Compac Unit/Base Pad Isometric Section View
Cap Unit
Weight:
Height:
Depth:
Width:
50 lbs
18"
10 1/2"
4"
Dimensions & Weight May Vary by Region
Base Leveling Pad Notes:
1. The leveling pad is to be
constructed of crushed stone
or 2,000 psi� unreinforced
concrete
2.The base foundation is to be
approved by the site geotechnical
engineer prior to placement of the
leveling pad.
Excavation
Limits
6" Crushed Rock or
Unreinforced Concrete
Leveling Pad
Unit Face
Sheet
Of 14 Sheets
GEICO OFFICE BUILDING
T���� �������� ���
����������� �� �������
�������� �� N�������
E���������� S�������, I��.
��� ��� ��� �� �� ���� ���
��� ���� �� ������������
������ ������ ��� ������ ��
� P����������� E������� ��
��� ������ �� N�������
E���������� S�������, I��.
NOT FOR CONSTRUCTION
REVIEW SET
200 S���� C������ A�����, S���� 010
F��� C������, C������� 80524
E N G I N E E R I N G
� � � � � � ��
PHONE: 970.221.4158 FAX: 970.221.4159
���.�������������������.���
CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.
Call before you dig.
R
C7.00
CONSTRUCTION DETAILS
3 CONCRETE DETAILS
6" 1"
1 1/2"R.
1'-6"
2" R.
4-1/2"
12"
6"
OUTFALL CURB & GUTTER
1-1/2"
6"
1-1/2" TO
4 PRIVATE CURB & GUTTER
6" 1"
1 1/2"R.
1'-6"
2" R.
4-1/2"
12"
6"
INFLOW CURB & GUTTER
1-1/2"
6"
1-1/2" TO
RIBBON CURB
ATTACHED SIDEWALK DETAIL
S���� �������� �� ���� 1/4" ��� ����.
NOTE: C�������� �������� ���� ������ �� 10' ���������
R 1/8"
WEAKENED PLANE JOINT EXPANSION JOINT
R1/4"
��� ������� ���� ������� �� ����.
INSTALL IN LOCATIONS SPECIFIED
IN CHAPTER 22
1/2"
1/4"
1/4 SLAB THICKNESS
1/4"
1/2" E��������
J���� ��������
DETACHED SIDEWALK DETAIL
V�������
L����������
S���� �������� �� ���� 1/4" ��� ����.
2' ���.
S����: M������
1
4"/��
M������ 3"/��
2 RAMP DETAIL
6"
2"R.
2"
6" 6"
12"
1 1/2"R.
2'-6"
6"
4 1/2"
30"
9"
R 0.5"
4.5"
18"
3.63"
21.75"
R 0.13"
7"
2"
3.75"
12"
ROLL-OVER
VERTICAL
(LOVELAND)
G����� ���� ��� ��
������� �� ��������.
(T������ ��� ��� C��� &
& G����� T����)
1 KEYSTONE COMPAC GRAVITY RETAINING WALL
5 6"-0" CURB TRANSITION
BASIN
Sheet
Of 14 Sheets
GEICO OFFICE BUILDING
T���� �������� ���
����������� �� �������
�������� �� N�������
E���������� S�������, I��.
��� ��� ��� �� �� ���� ���
��� ���� �� ������������
������ ������ ��� ������ ��
� P����������� E������� ��
��� ������ �� N�������
E���������� S�������, I��.
NOT FOR CONSTRUCTION
REVIEW SET
200 S���� C������ A�����, S���� 010
F��� C������, C������� 80524
E N G I N E E R I N G
� � � � � � ��
PHONE: 970.221.4158 FAX: 970.221.4159
���.�������������������.���
C6.00
DRAINAGE EXHIBIT
D���
D���
D���
D���
D���
D���
APPROVED:
CHECKED BY:
CHECKED BY:
CHECKED BY:
CHECKED BY:
CHECKED BY:
C��� E�������
W���� & W��������� U������
S��������� U������
P���� & R���������
T������ E�������
E������������ P������
C��� �� F��� C������, C�������
UTILITY PLAN APPROVAL
CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.
Call before you dig.
R
LEGEND:
NORTH
NOTES:
/ / / / / / / / / / / / / / / / / / / / / / / / / / / /
UD
B1
f2
LOD
FOR DRAINAGE REVIEW ONLY
NOT FOR CONSTRUCTION
ORIGINAL FIELD SURVEY BY:
PROJECT BENCHMARKS:
BENCHMARK #1:
City of Fort Collins Benchmark 6-13
Elevation= 4970.30 (NAVD 88) - For Reference Only
Elevation= 4967.10 (NGVD 29 - Unadjusted) - Project Datum
BENCHMARK #2:
City of Fort Collins Benchmark 1-96
Elevation= 4945.01 (NAVD 88) - For Reference Only
Elevation= 4941.81 (NGVD 29 - Unadjusted) - Project Datum
Basis of Bearings
Basis of Bearings is the South line of the Southeast quarter of Section 31-7-68 as bears
North 89�31'41" West (assumed bearing).
HARD OR ROCKY SLOPES, A PILOT BAR MAY BE NEEDED TO BEGIN THE
STAKE HOLE.
1"x 1" WOOD STAKES
18"-24"
BAILING WIRE OR
NYLON ROPE
WATTLE "A" WATTLE "B"
1' 2'
TYP.
1' 1'
W2 NOTES:
INSTALLATION:
STAKES SHOULD BE DRIVEN ACROSS FROM EACH OTHER
AND ON EACH SIDE OF THE WATTLE. LEAVING 4"-6" OF
STAKE PROTRUDING ABOVE THE WATTLE. BAILING WIRE OR
NYLON ROPE SHOULD BE TIED TO THE STAKES ACROSS
THE WATTLE. STAKES SHOULD THEN BE DRIVEN UNTIL THE
BAILING WIRE OR NYLON ROPE IS SUFFICIENTLY SNUG TO
THE WATTLE.
WHEN INSTALLING RUNNING LENGTHS OF WATTLES, TO
PREVENT SHIFTING, BUTT THE SECOND WATTLE TIGHTLY
AGAINST THE FIRST. DO NOT OVERLAP THE ENDS. STAKES
SHOULD BE DRIVEN 1 FT. FROM END, ACROSS FROM AND
ON EACH SIDE OF WATTLE LEAVING 4"-6" OF STAKE
PROTRUDING ABOVE THE WATTLE. BAILING WIRE OR
NYLON ROPE SHOULD BE TIED TO STAKES IN AN HOUR
GLASS FORMATION (FRONT TO BACK OF WATTLE "A",
ACROSS TO FRONT OF WATTLE "B", ACROSS TO BACK AND
BACK TO FRONT OF WATTLE "A"). STAKES SHOULD THEN BE
DRIVEN IN UNTIL BAILING WIRE OR NYLON ROPE IS
SUFFICIENTLY SNUG TO THE WATTLE.
SEDIMENT
DEPOSITION
ZONE
STORM WATER LINE
ROCK WATTLE
LIP OF GUTTER
SIDEWALK EXISTING OR
PROPOSED INLET
TOP BACK CURB
FLOW LINE
SEDIMENT
DEPOSITION
ZONE
STORM WATER LINE
LIP OF GUTTER
ROCK WATTLE
AT 45 DEG. TO CURB
SIDEWALK
TOP BACK CURB
FLOW LINE
SIDEWALK
TOP BACK CURB
FLOW LINE
W4 NOTES:
1. NUMBER OF WATTLES AND SPACING SHOULD BE DETERMINED BY THE SLOPE AND SITE CONDITIONS.
2. TUBULAR MARKERS SHALL MEET THE REQUIREMENTS OF MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES (MUTCD)
3. CITY RECOMMENDS INSTALLING AT LEAST 3 CHECKDAMS WHEN USING THIS SETUP.
LIP OF GUTTER
ROCK WATTLE
W1 & W2 INSTALLATION NOTES:
1. THE LOCATION AND LENGTH OF WATTLE IS DEPENDENT ON THE CONDITIONS OF EACH SITE.
2. WATTLES SHALL BE INSTALLED PRIOR TO ANY LAND-DISTURBING ACTIVITIES.
3. WATTLES SHALL CONSIST OF STRAW, COMPOST, EXCELSIOR, OR COCONUT FIBER.
4. NOT FOR USE IN CONCENTRATED FLOW AREAS.
5. THE WATTLES SHALL BE TRENCHED INTO THE GROUND A MINIMUM OF TWO (2) INCHES.
6. WATTLES SHALL BE INSTALLED PER MANUFACTURERS SPECIFICATIONS.
7. ON SLOPES, WATTLES SHOULD BE INSTALLED ON CONTOUR WITH A SLIGHT DOWNWARD ANGLE AT THE END OF THE ROW IN ORDER TO PREVENT
PONDING AT THE MID SECTION.
8. RUNNING LENGTHS OF WATTLES SHOULD BE ABUTTED FIRMLY TO ENSURE NO LEAKAGE AT THE ABUTMENTS.
9. SPACING - DOWNSLOPE:
10. VERTICAL SPACING FOR SLOPE INSTALLATIONS SHOULD BE DETERMINED BY SITE CONDITIONS. SLOPE GRADIENT AND SOIL TYPE ARE THE MAIN
FACTORS. A GOOD RULE OF THUMB IS:
1:1 SLOPES = 10 FEET APART
2:1 SLOPES = 20 FEET APART
3:1 SLOPES = 30 FEET APART
4:1 SLOPES = 40 FEET APART, ETC.
11. HOWEVER, ADJUSTMENTS MAY HAVE TO BE MADE FOR THE SOIL TYPE: FOR SOFT, LOAMY SOILS - ADJUST THE ROWS CLOSER TOGETHER; FOR HARD,
ROCKY SOILS - ADJUST THE ROWS FURTHER APART. A SECONDARY WATTLE PLACED BEHIND THE ABUTMENT OF TWO WATTLES IS ENCOURAGED ON
STEEP SLOPES OR WHERE JOINTS HAVE FAILED IN THE PAST.
12. STAKING: THE CITY RECOMMENDS USING WOOD STAKES TO SECURE THE WATTLES. 1/2" TO 5/8" REBAR IS ALSO ACCEPTABLE. BE SURE TO USE A
STAKE THAT IS LONG ENOUGH TO PROTRUDE SEVERAL INCHES ABOVE THE WATTLE: 18" IS A GOOD LENGTH FOR HARD, ROCKY SOIL. FOR SOFT LOAMY
SOIL USE A 24" STAKE.
SNUG WITH WATTLE.
W3 NOTE:
IF THE AREA BEHIND THE INLET IS NOT STABILIZED, A
BMP SHOULD BE USED TO PREVENT SEDIMENT FROM
ENTERING THE INLET
1"x 1" WOOD STAKES
18"-24"
THE CONTRACTOR SHALL INSPECT WATTLES EVERY TWO WEEKS AND AFTER ANY SIGNIFICANT STORM EVENT AND MAKE REPAIRS OR REMOVE SEDIMENT
ACCUMULATED BEHIND WATTLE AS NECESSARY.
SEDIMENT ACCUMULATED BEHIND WATTLE SHALL BE REMOVED WHEN THE SEDIMENT HAS ACCUMULATED TO ONE HALF THE DIAMETER OF THE WATTLE.
WATTLES SHALL REMAIN IN PLACE UNTIL THE UPSTREAM DISTURBED AREA IS STABILIZED AND IS ACCEPTED BY THE CITY.
WATTLE MAINTENANCE NOTES:
1.
2.
3.
ENDS SHALL ABUT TIGHTLY
TO BACK OF CURB
END SHALL ABUT TIGHTLY
TO BACK OF CURB
ENDS OF ADJACENT WATTLES
SHALL BE TIGHTLY ABUTTED
TO PREVENT SEDIMENT BYPASS
4' MAX.
SEDIMENT
DEPOSITION ZONE
W2 NOTE:
ONLY WATTLES MADE WITH COCONUT
FIBERS SHALL BE USED WHEN
INSTALLATION COMES IN CONTACT WITH A
WATER BODY.
SIDEWALK CULVERT/CHASE/PAN
W3, W4 & W5 NOTES:
1. WHEN USING STRAW WATTLE, THE STRAW WATTLE MUST HAVE A WEIGHTED
CORE.
2. ALL PRODUCTS SHALL BE INSTALLED PER THE MANUFACTURER'S
SPECIFICATIONS.
3. OTHER PRODUCTS MAY BE USED IN PLACE OF WEIGHTED WATTLES UPON
WRITTEN APPROVAL FROM THE CITY. NOTE: A COPY OF DETAILS AND
SPECIFICATIONS WILL NEED TO BE INCORPORATED INTO THE SWMP.
END SHALL
TIGHTLY ABUT TO
BACK OF CURB
SEDIMENT
DEPOSITION ZONE
TUBULAR
MARKER
EXISTING OR
PROPOSED INLET
END SHALL
TIGHTLY ABUT TO
BACK OF CURB
VTC
CONCRETE WASHOUT AREA
CWA
6
1
4
2
WP
SILT FENCE
SF SF
3
ROCK SOCK SECTION ROCK SOCK PLAN
ROCK SOCK JOINTING
GRADATION TABLE
SIEVE SIZE
MASS PERCENT
PASSING SQUARE
MESH SIEVES
NO. 4
2" 100
1-1/2" 90-100
1" 20-55
3/4" 0-15
3/8" 0-5
MATCHES SPECIFICATIONS FOR NO. 4 COARSE AGGREGATE FOR
CONCRETE PER AASHTO M43. ALL ROCK SHALL BE FRACTURED FACE,
ALL SIDES
5 ROCK SOCK DETAIL
RS
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.
Call before you dig.
R
C5.00
STATIC PLAN
EROSION CONTROL
G������
Overlot
P������� I�����������
Stormwater
C������� I�����������
Building Structure
M������������
Hardscape Amenities & Landscaping
BEST MANAGEMENT PRACTICES
T��������
Inlet Protection (IP)
Vehicle Tracking Control (VTC)
Flow Barriers (Wattles, Etc) (WP)
Concrete Washout Area (CWA)
Preventative Maintenance Activities/Meetings/ etc.
P��������
Mulching/Sealant
Permanent Seed Planting
Curb and Gutter
Concrete Parking and Drive Aisle
Permeable Pavers
TABLE OF CONSTRUCTION
SEQUENCE AND BMP APPLICATION
Project: Geico Office Building
CONSTRUCTION PHASE PHASE I PHASE II PHASE III PHASE IV
Silt Fence (SF)
Demolition LEGEND:
NOTES:
CWA
SF
LOD
Rock Sock
(SEE NOTE 8)
Sheet
Of 14 Sheets
GEICO OFFICE BUILDING
T���� �������� ���
����������� �� �������
�������� �� N�������
E���������� S�������, I��.
��� ��� ��� �� �� ���� ���
��� ���� �� ������������
������ ������ ��� ������ ��
� P����������� E������� ��
��� ������ �� N�������
E���������� S�������, I��.
NOT FOR CONSTRUCTION
REVIEW SET
200 S���� C������ A�����, S���� 010
F��� C������, C������� 80524
E N G I N E E R I N G
� � � � � � ��
PHONE: 970.221.4158 FAX: 970.221.4159
���.�������������������.���
NORTH
CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.
Call before you dig.
R
C4.00
GRADING PLAN
LEGEND:
ST
NOTES:
LOD
FIELD SURVEY BY:
PROJECT BENCHMARKS:
UD UD UD UD
W F S
G
E
E
VAULT
ELEC
E
E
E
E
E
E E
E
G
6" PERFORATED
UNDER DRAIN
EXISTING3
4"
METER & CURB
STOP
UPSIZE SERVICE 5'
PAST METER TO A 1"
SERVICE
1" WATER
SERVICE
6" FIRE
SERVICE
6" SANITARY
SEWER SERVICE
INV. = 4959.90 INSTALL CLEANOUT
INV. = 4958.09
N:107927.85
E:205318.01
EXISTING SANITARY
SEWER MANHOLE
RIM = 4963.38
INV. IN = 4955.55 (W)
INV. OUT = 4955.46 (E)
INV. IN = 4955.66 (S)
ELECTRIC
METER
GAS
METER
ELECTRIC
SERVICE
ELECTRIC
TRANSFORMER
GAS
SERVICE
EXISTING 16"
WATER MAIN
EXISTING 3
4"
WATER SERVICE
EXISTING 8"
SANITARY SEWER
MAIN
INSTALL 8"x6" TAPPING
SADDLE W/ 6" G.V. & T.B.
SANITARY SEWER SERVICE
TO BE BORED UNDER TIMBERLINE RD.
10" DRAIN BASIN w/
8" DOME INLET
INV. OUT=4963.26 (W)
FG=4964.83
INSTALL 12"x6" TEE w/
1 - 12"x6" REDUCER
INV: 4963.12
FG=4965.90
INSTALL 12", 90� BEND
w/ CLEANOUT
INV: 4962.96
FG=4966.05
INSTALL COMBONATION INLET
w/ ORIFICE PLATE
INV: 4962.14
FG=4964.42
INSTALL FLAP GATE STRUCTURE
FG=4962.07
10" DRAIN BASIN w/
8" DOME INLET
INV. OUT=4963.17 (S)
FG=4964.90
13.41 LF
6" HDPE
@ 0.52%
33.68 LF
12" HDPE
@ 0.50%
27.14 LF
6" HDPE
@ 0.50%
10.08 LF
6" HDPE
@ 0.50%
INSTALL MONITORING BASIN
INV. IN=4962.90 (S)
FG=4965.53
INSTALL SCOURSTOP
TRANSITION MAT ABOVE
SC-250 NORTH AMERICAN
GREEN EROSION MAT
EXISTING FORT COLLINS
TRANSFORT BUS STOP
/ /
/
/
/
/
/
/ / / / / /
/
/
/
/
/
/ / / / / / / / / /
/
/
/
/
FIRE SERVICE
TO BE BORED UNDER TIMBERLINE RD.
109� LF
6" FIRE LINE
34� LF
1" WATER SERVICE
181� LF @ 1%
6" SS SERVICE
243� LF @ 1%
6" SS SERVICE
INSTALL MONITORING BASIN
INV. IN=4961.04 (E)
FG=4964.02
27.34 LF
6" HDPE
@ 0.50%
10" DRAIN BASIN w/
8" DOME INLET
INV. OUT=4961.17 (W)
FG=4963.74
APPROXIMATE LIMITS OF
SIDEWALK TO BE REMOVED
(SEE NOTE 10)
APPROXIMATE LIMITS OF
ASPHALT, CURB & GUTTER &
CONCRETE MEDIAN TO BE
REMOVED FOR BORING PIT
(SEE NOTE 7, 10 & 11)
INSTALL MONITORING BASIN
INV: 4962.40
FG=4965.41
51.86 LF
6" PERFORATED PVC
@ 0.50%
50.37 LF
6" PERFORATED PVC
@ 0.50%
INSTALL MONITORING BASIN
INV: 4962.39
FG=4963.73
10.83 LF
12" RCP
@ 0.50%
Sheet
Of 14 Sheets
GEICO OFFICE BUILDING
T���� �������� ���
����������� �� �������
�������� �� N�������
E���������� S�������, I��.
��� ��� ��� �� �� ���� ���
��� ���� �� ������������
������ ������ ��� ������ ��
� P����������� E������� ��
��� ������ �� N�������
E���������� S�������, I��.
NOT FOR CONSTRUCTION
REVIEW SET
200 S���� C������ A�����, S���� 010
F��� C������, C������� 80524
E N G I N E E R I N G
� � � � � � ��
PHONE: 970.221.4158 FAX: 970.221.4159
���.�������������������.���
C3.00
UTILITY PLAN
NORTH
CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.
Call before you dig.
R
LEGEND:
NOTES:
E
G
T
SS
W
X
VAULT
ELEC
�2�
�
F.O.
�
�
�
�
�
M
�
FO
T
T S
TRAFFIC
VAULT
�
G
E
UD UD
F
W
S
90�00'00"
128�09'23"
51�50'37"
RADIUS
25.00'
2.00'
2.00'
2.00'
2.00'
25.00'
LENGTH
22.62'
4.47'
3.14'
3.14'
4.47'
22.62'
BEARING
N25�28'46"W
S64�31'20"W
S44�31'52"E
S45�28'19"W
N63�38'15"W
S26�21'45"W
CHORD
21.86'
3.60'
2.83'
2.83'
3.60'
21.86'
HARMONY ROAD
(PUBLIC ROW-WIDTH VARIES)
TIMBERLINE ROAD
(PUBLIC ROW-WIDTH VARIES)
DIXON CANYON LATERAL
PROPOSED
BUILDING
Sheet
Of 14 Sheets
GEICO OFFICE BUILDING
T���� �������� ���
����������� �� �������
�������� �� N�������
E���������� S�������, I��.
��� ��� ��� �� �� ���� ���
��� ���� �� ������������
������ ������ ��� ������ ��
� P����������� E������� ��
��� ������ �� N�������
E���������� S�������, I��.
NOT FOR CONSTRUCTION
REVIEW SET
200 S���� C������ A�����, S���� 010
F��� C������, C������� 80524
E N G I N E E R I N G
� � � � � � ��
PHONE: 970.221.4158 FAX: 970.221.4159
���.�������������������.���
C2.00
HORIZONTAL CONTROL
NORTH
CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.
Call before you dig.
R
NOTES:
LEGEND:
ORIGINAL FIELD SURVEY BY:
PROJECT BENCHMARKS:
TIMBERLINE ROAD
(PUBLIC ROW-WIDTH VARIES)
FOUND SE CORNER
SECTION 31-7-68
3" ALUM CAP LS 17497
(PER MONUMENT RECORD)
30' R.O.W.
30' R.O.W.
2.3'
AVERY, BROWN AND PRESTON
DITCH EASEMENT (BK L PG 21)
15' ACCESS &
UTILITY EASEMENT
CITY OF FORT COLLINS
RECEPTION NO.
2001059218 & 2003009675
ACCESS
(TO REMAIN)
1 STORY
FRAME
STRUCTURE
(TO BE
REMOVED)
ASPHALT
PARKING AREA
COVERED
PORCH
RAMP
1 STORY BRICK
& WOOD
1 STORY
BRICK
LOT 1 (2024 EAST HARMONY)
HARMONY LAWSER SUBDIVISION
(RECEPTION NO. 2001113965)
(2024 EAST HARMONY)
W W
W
W W
W W W W W W W W W W W W W W W W
SS
W W W
/ / / / / / / / / /
/ / / / / / / / / / / / / / / / / / /
/ / / / / / / / / / / / / /
/ / / /
/ / / / / /
/
/ / / / / / / / / / / / / /
/
/ / /
/ / /
/
/ / / / / / /
/
/ / / / /
/
/
/ / / / / / / / / / / / / /
/
/ / / / / / / / / / / / / / / / / / / / / / / / / / / /
/ / / / / /
/
/
/
/
/
/ / / / / /
/
/
/
/
/
/ / / / / / / / / /
DIXON CANYON LATERAL
EXISTING FORT COLLINS
TRANSFORT BUS STOP
ACCESS
(TO BE REMOVED)
ACCESS DRIVE TO BE REMOVED & REPLACED
WITH 30" VERTICAL CURB & GUTTER
APPROXIMATE LIMITS OF
ASPHALT TO BE REMOVED
(SEE NOTE 8)
ACCESS
(TO BE REMOVED)
NORTH
C1.00
& DEMOLITION PLAN
EXISTING CONDITIONS
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
K��� ����'� �����.
C��� ������ ��� ���.
R
E
LEGEND:
G
T
ST
FIELD SURVEY BY:
NOTES:
SS
W
X
VAULT
ELEC
�2�
�
Sheet
Of 14 Sheets
GEICO OFFICE BUILDING
T���� �������� ���
����������� �� �������
�������� �� N�������
E���������� S�������, I��.
��� ��� ��� �� �� ���� ���
��� ���� �� ������������
������ ������ ��� ������ ��
� P����������� E������� ��
��� ������ �� N�������
E���������� S�������, I��.
NOT FOR CONSTRUCTION
REVIEW SET
200 S���� C������ A�����, S���� 010
F��� C������, C������� 80524
E N G I N E E R I N G
� � � � � � ��
PHONE: 970.221.4158 FAX: 970.221.4159
���.�������������������.���
SUBSURFACE EXPLORATION BY:
/ / / / / / / / / / / / / / / / / / / / / / / / / / / /
F.O.
�
�
�
�
�
M
�
FO
T
T S
TRAFFIC
VAULT
�
Fort Collins - Loveland Water District
South Fort Collins Sanitation District
WEST 137.40' (R)
N01�56'50"W 100.06' (R)
N71�18'40"E 43.61'
LOT 1
HARMONY
WELLNESS
CENTER
S89�24'31"E 59.98'
S00�22'43"W 83.73'
S44�56'29"W 42.53'
S89�21'30"E 140.90'
N89�31'41"W 208.96'
N01�30'04"W 100.37'
LOT 1
23,881 sq. ft.
0.548 ac.
N77�26'23"W
62.28'
S89�52'27"W 79.99'
N00�32'23"E
11.79'
L1
L2
L3
L4
UNPLATTED
S00�32'23"W
15.00'
LOT 2A
HARMONY VILLAGE
P.U.D., REPLAT NO. 3
LOT 1A
HARMONY VILLAGE
P.U.D., REPLAT NO. 3
LOT 2
HARMONY
SCHOOL SHOPS,
1ST FILING
109.91'
N00�28'19"E
30.00'
137.32'
71.64'
N79�28'11"E
61.12'
DITCH EASEMENT TO BE
DEDICATED BY THIS PLAT
L5
C
1
L6
L7
L8
L9
L10
C
2
L11
38.90' 22.00' 65.99'
EXISTING LOT LINE TO BE
VACATED BY THIS PLAT
N89�31'41"W 137.86'
EMERGENCY ACCESS
EASEMENT
HARMONY RD.
TIMBERLINE RD.
STONEY CREEK DR
CORBETT DR.
COUNCIL TREE DR.
TIMBERLINE RD.
COUNCIL TREE DR.
TIMBERWOOD DR.
ZIEGLER RD.
ZIEGLER RD.
ZIEGLER RD.
HORSETOOTH RD.
STONEHAVEN DR.
ANTELOPE RD.
ROCK CREEK DR.
SOUTH 1/4 CORNER
SECTION 31-7-68
2 1/2" ALUM CAP LS 17497
(PER MONUMENT RECORD)
WEST 1/4 CORNER
SECTION 31-7-68
2 1/2" ALUM CAP LS 17497
(PER MONUMENT RECORD)
LINE TABLE
LINE
L1
L2
L3
L4
L5
LENGTH
5.43'
4.60'
5.00'
4.62'
11.51'
BEARING
S89� 31' 41"E
N00� 16' 16"E
S89� 43' 44"E
S00� 16' 16"W
N00� 28' 19"E
Sheet
Of 1 Sheet
GEICO OFFICE BUILDING NOTICE
:
According to Colorado law you must commence any legal action based
upon any defect in this survey within three years after you discover such
defect. In no event may any action based upon any defect in this survey
be commenced more than ten years after the date of the certificate shown
200 S���� C������ A�����, S���� 10 hereon.
F��� C������, C������� 80524
E N G I N E E R I N G
� � � � � � ��
PHONE: 970.221.4158 FAX: 970.221.4159
���.�������������������.���
1
CITY OF FORT COLLINS
STATE OF COLORADO
MAINTENANCE GUARANTEE:
The Owner hereby warrants and guarantees to the City, for a period of two (2) years from the date of completion and first acceptance by the City of the improvements warranted hereunder,
the full and complete maintenance and repair of the improvements
to be constructed in connection with the Development which is the subject of this Plat. This warranty and guarantee is made in accordance with the City Land Use Code and/or the Transitional
Land Use Regulations, as applicable. This guarantee applies
to the streets and all other appurtenant structures and amenities lying within the rights-of-way, Easements and other public properties, including, without limitation, all curbing, sidewalks,
bike paths, drainage pipes, culverts, catch basins, drainage ditches
and landscaping. Any maintenance and/or repair required on utilities shall be coordinated with the owning utility company or department.
The Owner shall maintain said improvements in a manner that will assure compliance on a consistent basis with all construction standards, safety requirements and environmental protection
requirements of the City. The Owner shall also correct and
repair, or cause to be corrected and repaired, all damages to said improvements resulting from development-related or building-related activities. In the event the Owner fails to correct
any damages within thirty (30) days after written notice thereof, then
said damages may be corrected by the City and all costs and charges billed to and paid by the Owner. The City shall also have any other remedies available to it as authorized by law.
Any damages which occurred prior to the end of said two (2) year
period and which are unrepaired at the termination of said period shall remain the responsibility of the Owner.
REPAIR GUARANTEE:
In consideration of the approval of this final Plat and other valuable consideration, the Owner does hereby agree to hold the City harmless for a five (5) year period, commencing upon
the date of completion and first acceptance by the City of the
improvements to be constructed in connection with the development which is the subject of this Plat, from any and all claims, damages, or demands arising on account of the design and
construction of public improvements of the property shown herein;
and the Owner furthermore commits to make necessary repairs to said public improvements, to include, without limitation, the roads, streets, fills, embankments, ditches, cross pans,
sub-drains, culverts, walls and bridges within the right-of-way,
Easements and other public properties, resulting from failures caused by design and/or construction defects. This agreement to hold the City harmless includes defects in materials and
workmanship, as well as defects caused by or consisting of settling
trenches, fills or excavations.
Further, the Owner warrants that he/she owns fee simple title to the property shown hereon and agrees that the City shall not be liable to the Owner or his/her successors in interest
during the warranty period, for any claim of damages resulting from
negligence in exercising engineering techniques and due caution in the construction of cross drains, drives, structures or buildings, the changing of courses of streams and rivers, flooding
from natural creeks and rivers, and any other matter whatsoever on
private property. Any and all monetary liability occurring under this paragraph shall be the liability of the Owner. I further warrant that I have the right to convey said land according
to this Plat.
NOTICE OF OTHER DOCUMENTS:
All persons take notice that the Owner has executed certain documents pertaining to this Development which create certain rights and
obligations of the Development, the Owner and/or subsequent Owners of all or portions of the Development site, many of which
obligations constitute promises and covenants that, along with the obligations under this Plat, run with the land. The said documents
may also be amended from time to time and may include, without limitation, the Development Agreement, Site And Landscape
Covenants, Final Site Plan, Final Landscape Plan, and Architectural Elevations, which documents are on file in the office of the clerk of
the City and should be closely examined by all persons interested in purchasing any portion of the Development site.
SURVEYOR'S STATEMENT
I, Gerald D. Gilliland, a Colorado Registered Professional Land Surveyor do hereby state that this Subdivision Plat
was prepared from an actual survey under my personal supervision, that the monumentation as indicated hereon were
found or set as shown, and that the foregoing plat is an accurate representation thereof, all this to the best of my
knowledge, information and belief.
__________________________________
Gerald D. Gilliland
Colorado Registered Professional
Land Surveyor No. 14823
CERTIFICATE OF DEDICATION:
The Owner does hereby dedicate and convey to the City of Fort Collins, Colorado (hereafter “City”), for public use, forever, a permanent right-of-way for street purposes and the “Easements”
as laid out and
designated on this Plat; provided, however, that (1) acceptance by the City of this dedication of Easements does not impose upon the City a duty to maintain the Easements so dedicated,
and (2) acceptance by
the City of this dedication of streets does not impose upon the City a duty to maintain streets so dedicated until such time as the provisions of the Maintenance Guarantee have been
fully satisfied. The streets
dedicated on this Plat are the fee property of the City as provided in Section 31-23-107 C.R.S. The City's rights under the Easements include the right to install, operate, access, maintain,
repair, reconstruct,
remove and replace within the Easements public improvements consistent with the intended purpose of the Easements; the right to install, maintain and use gates in any fences that cross
the Easements; the
right to mark the location of the Easements with suitable markers; and the right to permit other public utilities to exercise these same rights. Owner reserves the right to use the Easements
for purposes that do
not interfere with the full enjoyment of the rights hereby granted. The City is responsible for maintenance of its own improvements and for repairing any damage caused by its activities
in the Easements, but by
acceptance of this dedication, the City does not accept the duty of maintenance of the Easements, or of improvements in the Easements that are not owned by the City. Owner will maintain
the surface of the
Easements in a sanitary condition in compliance with any applicable weed, nuisance or other legal requirements.
Except as expressly permitted in an approved plan of development or other written agreement with the City, Owner will not install on the Easements, or permit the installation on the
Easements, of any
building, structure, improvement, fence, retaining wall, sidewalk, tree or other landscaping (other than usual and customary grasses and other ground cover). In the event such obstacles
are installed in the
Easements, the City has the right to require the Owner to remove such obstacles from the Easements. If Owner does not remove such obstacles, the City may remove such obstacles without
any liability or
obligation for repair and replacement thereof, and charge the Owner the City's costs for such removal. If the City chooses not to remove the obstacles, the City will not be liable for
any damage to the obstacles
or any other property to which they are attached.
The rights granted to the City by this Plat inure to the benefit of the City's agents, licensees, permittees and assigns.
ATTORNEY'S CERTIFICATION
I hereby certify that this Subdivision Plat has been duly executed as required pursuant to Section 2.2.3(C)(3)(a) through (e) inclusive of
the Land Use Code of the City of Fort Collins and that all persons signing this Subdivision Plat on behalf of a corporation or other entity
are duly authorized signatories under the laws of the State of Colorado. This Certification is based upon the records of the Clerk and
Recorder of Larimer County, Colorado as of the date of execution of the Plat and other information discovered by me through
reasonable inquiry and is limited as authorized by Section 2.2.3(C)(3)(f) of the Land Use Code.
Attorney:________________________________________
Address: ________________________________________
________________________________________
Registration No.:__________________________________
NOTICE
ALL RESPONSIBILITIES AND COSTS OF OPERATION, MAINTENANCE AND
RECONSTRUCTION OF THE PRIVATE STREETS AND/OR DRIVES LOCATED ON THE
PRIVATE PROPERTY THAT IS THE SUBJECT OF THIS PLAT SHALL BE BORNE BY THE
OWNERS OF SAID PROPERTY, EITHER INDIVIDUALLY, OR COLLECTIVELY, THROUGH A
PROPERTY OWNERS' ASSOCIATION, IF APPLICABLE. THE CITY OF FORT COLLINS SHALL
HAVE NO OBLIGATION OF OPERATION, MAINTENANCE OR RECONSTRUCTION OF SUCH
PRIVATE STREETS AND/OR DRIVES NOR SHALL THE CITY HAVE ANY OBLIGATION TO
ACCEPT SUCH STREETS AND/OR DRIVES AS PUBLIC STREETS OR DRIVES.
APPROVED AS TO FORM, CITY ENGINEER
By the City Engineer of the City of Fort Collins, Colorado this ______day of _____________ A.D., 20_____.
____________________________________________________
City Engineer
PLANNING APPROVAL
By the Director of Community Development and Neighborhood Services of the City of Fort Collins, Colorado this _____ day of
___________ A.D., 20_____.
____________________________________________________
Director
NOTES:
1) The Basis of Bearings is the South line of the Southeast Quarter of Section 31-7-68 as bearing North 89° 31' 41"
West as monumented on drawing (assumed bearing).
2) The lineal unit of measurement for this plat is U.S. Survey Feet.
3) All information regarding easements, right-of-way or title of record, Northern Engineering relied upon
Commitment Number 01330-24482, dated April 29, 2013 prepared by Stewart Title Guaranty Corporation.
4) There shall be no private conditions, covenants or restrictions that prohibit or limit the installation of resource
conserving equipment or landscaping that are allowed by Sections 12-120 - 12-122 of the City Code.
OWNER:
BY:_________________________________
Name:_______________________________
Title:________________________________
STATE OF COLORADO )
)SS
COUNTY OF LARIMER )
The foregoing instrument was acknowledged before me this _____ day of ___________________, 20____, by ________________________________, as ___________________________
of ________________________________________.
Witness my hand and official seal
My commission expires: ________________
_______________________________
Notary Public
STATEMENT OF OWNERSHIP AND SUBDIVISION:
Know all persons by these presents, that the undersigned owner(s) of the following described land:
Lot 1, Harmony Lawser Subdivision, and a tract of land located in the Southeast Quarter of Section 31, Township 7 North, Range 68 West of the 6th P.M., City of Fort Collins, County of
Larimer, State of
Colorado, being more particularly described as follows:
Considering the South line of the Southeast Quarter of Section 31 as bearing North 89° 31' 41" West and with all bearings contained herein relative thereto:
Commencing at the Southeast Quarter of Section 31; thence along the South line of the Southeast Quarter of Section 31, North 89° 31' 41" West, 109.91 feet; thence, North 00° 28' 19"
East, 30.00 feet to a
point on the North right-of-way line of East Harmony Road, said point being the POINT OF BEGINNING; thence along said North line, North 89° 31' 41" West, 208.96 feet to the Southwest
corner of Lot 1,
Harmony Lawser Subdivision; thence along the West line of said Lot 1, North 01° 30' 04" West, 100.37 feet to the Northwest corner of said Lot 1; thence along the North line of said Lot
1, South 89° 21' 30"
East, 140.90 feet; thence, South 89° 24' 31" East, 59.98 feet; thence, North 71° 18' 40" East, 43.61 feet to a point on the West right-of-way line of Timberline Road; thence along said
West line, South 00° 22'
43" West, 83.73 feet; thence, South 44° 56' 29" West, 42.53 feet to the Point of Beginning.
Contains 23,881 square feet or 0.548 acres, more or less.
For themselves and their successors in interest (collectively "Owner") have caused the above described landto be surveyed and subdivided into lots, tracts and streets as shown on this
Plat to be known as
GEICO OFFICE BUILDING (the "Development"), subject to all easements and rights-of-way now of record or existing or indicated on this Plat. The rights and obligations of this Plat shall
run with the land.
GEICO OFFICE BUILDING
A REPLAT OF LOT 1, HARMONY LAWSER SUBDIVISION, AND A TRACT OF LAND LOCATED IN THE SOUTHEAST QUARTER OF SECTION 31,
TOWNSHIP 7 NORTH, RANGE 68 WEST OF THE 6TH P.M., CITY OF FORT COLLINS, COUNTY OF LARIMER, STATE OF COLORADO
NORTH
(US SURVEY FEET)
LEGEND
BOUNDARY LINE
CENTERLINE
EASEMENT LINE
LOT LINE
FOUND CORNER AS DESCRIBED
RIGHT-OF-WAY
LIENHOLDER:
BY:_________________________________
Name:_______________________________
Title:________________________________
STATE OF COLORADO )
)SS
COUNTY OF LARIMER )
The foregoing instrument was acknowledged before me this _____ day of ___________________, 20____, by __________________________,
as ______________________ of ______________________________.
Witness my hand and official seal
My commission expires: ________________
_______________________________
Notary Public
SITE
VICINITY MAP
NORTH
Water Utility.
14. A State Construction Dewatering Wastewater Discharge Permit is required if dewatering is required in order to install utilities or if water is
discharged into a storm sewer, channel, irrigation ditch or any waters of the United States.
15. The Developer shall comply with all terms and conditions of the Colorado Permit for Storm Water Discharge (Contact Colorado Department
of Health, Water Quality Control Division, (303) 692-3590), the Storm Water Management Plan, and the Erosion Control Plan.
16. The City of Fort Collins shall not be responsible for the maintenance of storm drainage facilities located on private property. Maintenance of
onsite drainage facilities shall be the responsibility of the property owner(s).
17. Prior to final inspection and acceptance by the City of Fort Collins, certification of the drainage facilities, by a registered engineer, must be
submitted to and approved by the Stormwater Utility Department. Certification shall be submitted to the Stormwater Utility Department at
least two weeks prior to the release of a certificate of occupancy for single family units. For commercial properties, certification shall be
submitted to the Stormwater Utility Department at least two weeks prior to the release of any building permits in excess of those allowed
prior to certification per the Development Agreement.
18. The City of Fort Collins shall not be responsible for any damages or injuries sustained in this Development as a result of groundwater
seepage, whether resulting from groundwater flooding, structural damage or other damage unless such damage or injuries are sustained as
a result of the City of Fort Collins failure to properly maintain its water, wastewater, and/or storm drainage facilities in the development.
19. All recommendations of the Preliminary Drainage and Erosion Control Report for Geico Office Building dated March 5, 2014by Northern
Engineering Services, Inc., shall be followed and implemented.
20. Temporary erosion control during construction shall be provided as shown on the Erosion Control Plan. All erosion control measures shall
be maintained in good repair by the Developer, until such time as the entire disturbed areas is stabilized with hard surface or landscaping.
21. The Developer shall be responsible for insuring that no mud or debris shall be tracked onto the existing public street system. Mud and
debris must be removed within 24 hours by an appropriate mechanical method (i.e. machine broom sweep, light duty front-end loader, etc.)
or as approved by the the City of Fort Collins street inspector.
22. No work may commence within any improved or unimproved public Right-of-Way until a Right-of-Way Permit or Development Construction
Permit is obtained, if applicable.
23. The Developer shall be responsible for obtaining all necessary permits for all applicable agencies prior to commencement of construction.
The Developer shall notify the the City of Fort Collins Inspector (Fort Collins - 221-6605) and the City of Fort Collins Erosion Control
Inspector (Fort Collins - 221-6700) at least 2 working days prior to the start of any earth disturbing activity, or construction on any and all
public improvements. If the City of Fort Collins Engineer is not available after proper notice of construction activity has been provided, the
Developer may commence work in the Engineer's absence. However, the City of Fort Collins reserves the right not to accept the
improvement if subsequent testing reveals an improper installation.
24. The Developer shall be responsible for obtaining soils tests within the Public Right-of-Way after right of way grading and all utility trench
work is complete and prior to the placement of curb, gutter, sidewalk and pavement. If the final soils/pavement design report does not
correspond with the results of the original geotechnical report, the Developer shall be responsible for a re-design of the subject pavement
section or, the Developer may use the City of Fort Collins' default pavement thickness section(s). Regardless of the option used, all final
soils/pavement design reports shall be prepared by a licensed Professional Engineer. The final report shall be submitted to the Inspector a
minimum of 10 working days prior to placement of base and asphalt. Placement of curb, gutter, sidewalk, base and asphalt shall not occur
until the City of Fort Collins Engineer approves the final report.
25. The contractor shall hire a licensed engineer or land surveyor to survey the constructed elevations of the street subgrade and the gutter
flowline at all intersections, inlets, and other locations requested by the the City of Fort Collins inspector. The engineer or surveyor must
certify in a letter to the City of Fort Collins that these elevations conform to the approved plans and specifications. Any deviations shall be
noted in the letter and then resolved with the City of Fort Collins before installation of base course or asphalt will be allowed on the streets.
26. All utility installations within or across the roadbed of new residential roads must be completed prior to the final stages of road construction.
For the purposes of these standards, any work except c/g above the subgrade is considered final stage work. All service lines must be
stubbed to the property lines and marked so as to reduce the excavation necessary for building connections.
27. Portions of Larimer County are within overlay districts. The Larimer County Flood Plain Resolution should be referred to for additional
criteria for roads within these districts.
28. All road construction in areas designated as Wild Fire Hazard Areas shall be done in accordance with the construction criteria as
established in the Wild Fire Hazard Area Mitigation Regulations in force at the time of final plat approval.
29. Prior to the commencement of any construction, the contractor shall contact the Local Entity Forester to schedule a site inspection for any
tree removal requiring a permit.
30. The Developer shall be responsible for all aspects of safety including, but not limited to, excavation, trenching, shoring, traffic control, and
security. Refer to OSHA Publication 2226, Excavating and Trenching.
31. The Developer shall submit a Construction Traffic Control Plan, in accordance with MUTCD, to the appropriate Right-of-Way authority. (The
the City of Fort Collins, Larimer County, Colorado), for approval, prior to any construction activities within, or affecting, the Right-of-Way.
The Developer shall be responsible for providing any and all traffic control devices as may be required by the construction activities.
32. Prior to the commencement of any construction that will affect traffic signs of any type, the contractor shall contact the City of Fort Collins
Traffic Operations Department, who will temporarily remove or relocate the sign at no cost to the contractor, however, if the contractor
moves the traffic sign then the contractor will be charged for the labor, materials and equipment to reinstall the sign as needed.
33. The Developer is responsible for all costs for the initial installation of traffic signing and striping for the Development related to the
Development's local street operations. In addition, the Developer is responsible for all costs for traffic signing and striping related to directing
traffic access to and from the Development.
34. There shall be no site construction activities on Saturdays, unless specifically approved by the City of Fort Collins Engineer, and no site
construction activities on Sundays or holidays, unless there is prior written approval by Larimer County.
35. The Developer is responsible for providing all labor and materials necessary for the completion of the intended improvements, shown on
these drawings, or designated to be provided, installed, or constructed, unless specifically noted otherwise.
36. Dimensions for layout and construction are not to be scaled from any drawing. If pertinent dimensions are not shown, contact the Designer
for clarification, and annotate the dimension on the as-built record drawings.
37. The Developer shall have, onsite at all times, one (1) signed copy of the approved plans, one (1) copy of the appropriate standards and
specifications, and a copy of any permits and extension agreements needed for the job.
38. If, during the construction process, conditions are encountered which could indicate a situation that is not identified in the plans or
specifications, the Developer shall contact the Designer and the City of Fort Collins Engineer immediately.
39. The Developer shall be responsible for recording as-built information on a set of record drawings kept on the construction site, and available
to the Larimer County's Inspector at all times. Upon completion of the work, the contractor(s) shall submit record drawings to the City of Fort
Collins Engineer.
40. The Designer shall provide, in this location on the plan, the location and description of the nearest survey benchmarks (2) for the project as
well as the basis of bearings. The information shall be as follows:
BENCHMARK #1:
City of Fort Collins Benchmark 6-13
Elevation= 4970.30 (NAVD 88) - For Reference Only
Elevation= 4967.10 (NGVD 29 - Unadjusted) - Project Datum
BENCHMARK #2:
City of Fort Collins Benchmark 1-96
Elevation= 4945.01 (NAVD 88) - For Reference Only
Elevation= 4941.81 (NGVD 29 - Unadjusted) - Project Datum
Basis of Bearings
Basis of Bearings is the South line of the Southeast quarter of Section 31-7-68 as bears North 89�31'41" West (assumed bearing).
41. All stationing is based on centerline of roadways unless otherwise noted.
42. Damaged curb, gutter and sidewalk existing prior to construction, as well as existing fences, trees, streets, sidewalks, curbs and gutters,
landscaping, structures, and improvements destroyed, damaged or removed due to construction of this project, shall be replaced or restored
in like kind at the Developer's expense, unless otherwise indicated on these plans, prior to the acceptance of completed improvements
and/or prior to the issuance of the first Certificate of Occupancy.
43. When an existing asphalt street must be cut, the street must be restored to a condition equal to or better than its original condition. The
existing street condition shall be documented by the City of Fort Collins Construction Inspector before any cuts are made. Patching shall be
done in accordance with the City of Fort Collins Street Repair Standards. The finished patch shall blend in smoothly into the existing
surface. All large patches shall be paved with an asphalt lay-down machine. In streets where more than one cut is made, an overlay of the
entire street width, including the patched area, may be required. The determination of need for a complete overlay shall be made by the
Larimer County Engineer and/or the City of Fort Collins Inspector at the time the cuts are made.
44. Upon completion of construction, the site shall be cleaned and restored to a condition equal to, or better than, that which existed before
construction, or to the grades and condition as required by these plans.
45. Standard Handicap ramps are to be constructed at all curb returns and at all "T" intersections.
46. After acceptance by the City of Fort Collins, public improvements depicted in these plans shall be guaranteed to be free from material and
workmanship defects for a minimum period of two years from the date of acceptance.
47. The City of Fort Collins shall not be responsible for the maintenance of roadway and appurtenant improvements, including storm drainage
structures and pipes, for the following private streets: N.A.
48. Approved Variances are listed as follows: N.A.
CONSTRUCTION NOTES
A. Grading and Erosion Control Notes
1. The erosion control inspector must be notified at least twenty-four (24) hours prior to any construction on this site.
2. There shall be no earth-disturbing activity outside the limits designated on the accepted plans.
3. All required perimeter silt and construction fencing shall be installed priorto any land disturbing activity (stockpiling, stripping, grading, etc).
All other required erosion control measures shall be installed at the appropriate time in the construction sequence as indicated in the
approved project schedule, construction plans, and erosion control report.
4. At all times during construction, the Developer shall be responsible for preventing and controlling on-site erosion including keeping the
property sufficiently watered so as to minimize wind blown sediment. The Developer shall also be responsible for installing and maintaining
all erosion control facilities shown herein.
5. Pre-disturbance vegetation shall be protected and retained wherever possible. Removal or disturbance of existing vegetation shall be
limited to the area(s) required for immediate construction operations, and for the shortest practical period of time.
6. All soils exposed during land disturbing activity (stripping, grading, utility installations, stockpiling, filling, etc.) shall be kept in a roughened
condition by ripping or disking along land contours until mulch, vegetation, or other permanent erosion control BMPs are installed. No soils
in areas outside project street rights-of-way shall remain exposed by land disturbing activity for more than thirty (30) days before required
temporary or permanent erosion control (e.g. seed/mulch, landscaping, etc.) is installed, unless otherwise approved by the City/County.
7. In order to minimize erosion potential, all temporary (structural) erosion control measures shall:
a. Be inspected at a minimum of once every two (2) weeks and after each significant storm event and repaired or reconstructed as
necessary in order to ensure the continued performance of their intended function.
b. Remain in place until such time as all the surrounding disturbed areas are sufficiently stabilized as determined by the erosion control
inspector.
c. Be removed after the site has been sufficiently stabilized as determined by the erosion control inspector.
8. When temporary erosion control measures are removed, the Developer shall be responsible for the clean up and removal of all sediment
and debris from all drainage infrastructure and other public facilities.
9. The contractor shall immediately clean up any construction materials inadvertently deposited on existing streets, sidewalks, or other public
rights of way, and make sure streets and walkways are cleaned at the end of each working day.
10. All retained sediments, particularly those on paved roadway surfaces, shall be removed and disposed of in a manner and location so as not
to cause their release into any waters of the United States.
11. No soil stockpile shall exceed ten (10) feet in height. All soil stockpiles shall be protected from sediment transport by surface roughening,
watering, and perimeter silt fencing. Any soil stockpile remaining after thirty (30) days shall be seeded and mulched.
12. The stormwater volume capacity of detention ponds will be restored and storm sewer lines will be cleaned upon completion of the project
and before turning the maintenance over to the City/County or Homeowners Association (HOA).
13. City Ordinance and Colorado Discharge Permit System (CDPS) requirements make it unlawful to discharge or allow the discharge of any
pollutant or contaminated water from construction sites. Pollutants include, but are not limited to discarded building materials, concrete
truck washout, chemicals, oil and gas products, litter, and sanitary waste. The developer shall at all times take whatever measures are
necessary to assure the proper containment and disposal of pollutants on the site in accordance with any and all applicable local, state, and
federal regulations.
14. A designated area shall be provided on site for concrete truck chute washout. The area shall be constructed so as to contain washout
material and located at least fifty (50) feet away from any waterway during construction. Upon completion of construction activities the
concrete washout material will be removed and properly disposed of prior to the area being restored.
15. Conditions in the field may warrant erosion control measures in addition to what is shown on these plans. The Developer shall implement
whatever measures are determined necessary, as directed by the City.
B. Street Improvement Notes
1. All street construction is subject to the General Notes on the cover sheet of these plans as well as the Street Improvements Notes listed
here.
2. A paving section design, signed and stamped by a Colorado licensed Engineer, must be submitted to the City of Fort Collins Engineer for
approval, prior to any street construction activity, (full depth asphalt sections are not permitted at a depth greater than 8 inches of asphalt).
The job mix shall be submitted for approval prior to placement of any asphalt.
3. Where proposed paving adjoins existing asphalt, the existing asphalt shall be saw cut, a minimum distance of 12 inches from the existing
edge, to create a clean construction joint. The Developer shall be required to remove existing pavement to a distance where a clean
construction joint can be made. Wheel cuts shall not be allowed unless approved by the City of Fort Collins Engineer in Fort Collins.
4. Street subgrades shall be scarified the top 12 inches and re-compacted prior to subbase installation. No base material shall be laid until the
subgrade has been inspected and approved by the City of Fort Collins Engineer.
5. Ft. Collins only. Valve boxes and manholes are to be brought up to grade at the time of pavement placement or overlay. Valve box adjusting
rings are not allowed.
6. When an existing asphalt street must be cut, the street must be restored to a condition equal to or better than its original condition. The
existing street condition shall be documented by the Inspector before any cuts are made. Cutting and patching shall be done in
conformance with Chapter 25, Reconstruction and Repair. The finished patch shall blend smoothly into the existing surface. The
determination of need for a complete overlay shall be made by the City of Fort Collins Engineer. All overlay work shall be coordinated with
adjacent landowners such that future projects do not cut the new asphalt overlay work.
7. All traffic control devices shall be in conformance with these plans or as otherwise specified in M.U.T.C.D. (including Colorado supplement)
and as per the Right-of-Way Work Permit traffic control plan.
8. The Developer is required to perform a gutter water flow test in the presence of the City of Fort Collins Inspector and prior to installation of
asphalt. Gutters that hold more than 1/4 inch deep or 5 feet longitudinally, of water, shall be completely removed and reconstructed to drain
properly.
9. Prior to placement of H.B.P. or concrete within the street and after moisture/density tests have been taken on the subgrade material (when a
full depth section is proposed) or on the subgrade and base material (when a composite section is proposed), a mechanical "proof roll" will
be required. The entire subgrade and/or base material shall be rolled with a heavily loaded vehicle having a total GVW of not less than
50,000 lbs. and a single axle weight of at least 18,000 lbs. with pneumatic tires inflated to not less that 90 p.s.i.g. "Proof roll" vehicles shall
not travel at speeds greater than 3 m.p.h. Any portion of the subgrade or base material which exhibits excessive pumping or deformation, as
determined by the City of Fort Collins Engineer, shall be reworked, replaced or otherwise modified to form a smooth, non-yielding surface.
The City of Fort Collins Engineer shall be notified at least 24 hours prior to the "proof roll." All "proof rolls" shall be preformed in the presence
of an Inspector.
C. Traffic Signing and Pavement Marking Construction Notes
1. All signage and marking is subject to the General Notes on the cover sheet of these plans, as well as the Traffic Signing and Marking
Construction Notes listed here.
2. All symbols, including arrows, ONLYS, crosswalks, stop bars, etc. shall be pre-formed thermo-plastic.
3. All signage shall be per the City of Fort Collins Standards and these plans or as otherwise specified in MUTCD.
4. All lane lines for asphalt pavement shall receive two coats of latex paint with glass beads.
5. All lane lines for concrete pavement should be epoxy paint.
6. Prior to permanent installation of traffic striping and symbols, the Developer shall place temporary tabs or tape depicting alignment and
placement of the same. Their placement shall be approved by the City of Fort Collins Traffic Engineer prior to permanent installation of
striping and symbols.
7. Pre-formed thermo-plastic applications shall be as specified in these Plans and/or these Standards.
8. Epoxy applications shall be applied as specified in CDOT Standard Specifications for Road and Bridge Construction.
9. All surfaces shall be thoroughly cleaned prior to installation of striping or markings.
10. All sign posts shall utilize break-away assemblies and fasteners per the Standards.
11. A field inspection of location and installation of all signs shall be performed by the City of Fort Collins Traffic Engineer. All discrepancies
identified during the field inspection must be corrected before the 2-year warranty period will begin.
12. The Developer installing signs shall be responsible for locating and protecting all underground utilities.
13. Special care shall be taken in sign location to ensure an unobstructed view of each sign.
14. Signage and striping has been determined by information available at the time of review. Prior to initiation of the warranty period,the City of
Fort Collins Traffic Engineer reserves the right to require additional signage and/or striping if the City of Fort Collins Traffic Engineer
determines that an unforeseen condition warrants such signage according to the MUTCD or the CDOT M and S Standards. All signage and
striping shall fall under the requirements of the 2-year warranty period for new construction (except fair wear on traffic markings).
15. Sleeves for sign posts shall be required for use in islands/medians. Refer to Chapter 14, Traffic Control Devices, for additional detail.
D. Storm Drainage Notes
1. The City of Fort Collins shall not be responsible for the maintenance of storm drainage facilities located on private property. Maintenance of
onsite drainage facilities shall be the responsibility of the property owner(s).
2. All recommendations of the Preliminary Drainage and Erosion Control Report for Geico Office Building dated March 5, 2014by Northern
Engineering Services, Inc., shall be followed and implemented.
3. Prior to final inspection and acceptance by the City of Fort Collins, certification of the drainage facilities, by a registered engineer, must by
submitted to and approved by the Stormwater Utility Department. Certification shall be submitted to the Stormwater Utility Department at
least two weeks prior to the release of a certificate of occupancy for single family units. For commercial properties, certification shall by
submitted to the Stormwater Utility Department at least two weeks prior to the release of any building permits in excess of those allowed
prior to certification per the Development Agreement.
E. Utility Notes
1. All waterline and sanitary sewer construction shall conform to the Fort Utility standards and specifications current to date of construction.
2. The minimum cover over water lines is 4.5 feet and the maximum cover is 5.5 feet unless otherwise noted in the plans and approved by the
water utility.
3. Water mains shall be poly-wrapped D.I.P, or PVC with tracer wire.
4. HDPE pipe may be used for 1-1/2 and 2 inch water services. The pipe shall meet the standards of AWWA 901, NSF Standard 61 and
ASTM. The HDPE pipe shall be SDR 9 having a pressure rating of 200 psi. Stiffeners shall be used at all fittings and connections. Tracer
wire shall be installed with the HDPE service, and shall extend up the curb stop. The curb stop shall be covered with a metal box and tracer
wire test lid per City Water Detail 25.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
K��� ����'� �����.
C��� ������ ��� ���.
R
BENCHMARK #1:
City of Fort Collins Benchmark 6-13
Elevation= 4970.30 (NAVD 88) - For Reference Only
Elevation= 4967.10 (NGVD 29 - Unadjusted) - Project Datum
BENCHMARK #2:
City of Fort Collins Benchmark 1-96
Elevation= 4945.01 (NAVD 88) - For Reference Only
Elevation= 4941.81 (NGVD 29 - Unadjusted) - Project Datum
Basis of Bearings
Basis of Bearings is the South line of the Southeast quarter of Section 31-7-68 as bears
North 89�31'41" West (assumed bearing).
Northern Engineering Services, Inc
NE Project No. 959-001
Date: September 18, 2013
ADDITIONAL FIELD SURVEYS:
Northern Engineering Services, Inc
Date(s): October 17, 2013
ORIGINAL FIELD SURVEY BY:
Earth Engineering, Inc.
"SUBSURFACE EXPLORATION REPORT GEICO INSURANCE OFFICE BUILDING
2024 EAST HARMONY ROAD"
EEC Project No. 1132073
Date: October 14, 2013
SUBSURFACE EXPLORATION BY:
PROJECT BENCHMARKS:
SHEET INDEX
COVER SHEET
GRADING PLAN
UTILITY PLAN
1
C4.00
C3.00
C6.00
GENERAL & CONSTRUCTION
NOTES
C0.00
C0.01
EXISTING CONDITIONS &
DEMOLITION PLAN
C1.00
DRAINAGE EXHIBIT
SUBDIVISION PLAT
(FOR REFERENCE ONLY)
Sheet
Of 14 Sheets
GEICO OFFICE BUILDING
T���� �������� ���
����������� �� �������
�������� �� N�������
E���������� S�������, I��.
��� ��� ��� �� �� ���� ���
��� ���� �� ������������
������ ������ ��� ������ ��
� P����������� E������� ��
��� ������ �� N�������
E���������� S�������, I��.
NOT FOR CONSTRUCTION
REVIEW SET
200 S���� C������ A�����, S���� 010
F��� C������, C������� 80524
E N G I N E E R I N G
� � � � � � ��
PHONE: 970.221.4158 FAX: 970.221.4159
���.�������������������.���
UTILITY PLANS FOR
A TRACT OF LAND LOCATED IN SOUTHEAST QUARTER OF SECTION 31, TOWNSHIP 7 NORTH, RANGE 68 WEST OF THE 6th P.M.,
CITY OF FORT COLLINS, COUNTY OF LARIMER, STATE OF COLORADO
GEICO OFFICE BUILDING
The Birdsall Group
Cathy Mathis, APA
444 Mountain Ave.
Berthoud, Colorado 80513
(970) 532-5891
Local Geico Office
Steve Allen
115 E. Harmony Rd, Suite 110
Fort Collins, Colorado 80525
(970) 221-5230
email: SAllen@geico.com
Aller .Lingle .Massey
Ian Shuff, AIA
712 Whalers Way
Fort Collins, Colorado 80525
(970) 223-1820
ARCHITECT
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
K��� ����'� �����.
C��� ������ ��� ���.
R
Earth Engineering Company, Inc.
Lester Litton, PE
4396 Greenfield Drive
Windsor, Colorado 80550
(970) 545-3908
GEOTECHNICAL ENGINEER
Integrated Mechanical
Thomas Segelhorst, PE
223 Linden St., Suite 204
Fort Collins, Colorado 80524
(970) 556-0570
MECHANICAL ENGINEER
UTILITY CONTACT LIST: *
UTILITY COMPANY
* This list is provided as a courtesy reference only. Northern Engineering Services assumes no responsibility for
the accuracy or completeness of this list. In no way shall this list relinquish the Contractor's responsibility for
locating all utilities prior to commencing any construction activity. Please contact the Utility Notification Center of
Colorado (UNCC) at 811 for additional information.
PHONE NUMBER
GAS----------------- Xcel Energy----------------------------- Stephanie Rich (970) 225-7857
ELECTRIC-------- City of Fort Collins Light & Power-- Doug Martine (970) 224-6152
CABLE------------- Comcast---------------------------------- Don Kapperman (970) 567-0425
TELECOM.--------CenturyLink------------------------------- William Johnson (970) 377-6401
WATER------------ City of Fort Collins Utilities----------- Roger Buffington (970) 221-6700
WASTEWATER--City of Fort Collins Utilities----------- Roger Buffington (970) 221-6700
STORMWATER- City of Fort Collins Utilities----------- Glen Schlueter (970) 221-6700
223 Linden St., Suite 204
Fort Collins, CO 80524
Phone: 970-556-0570
Front-Desk@Int-Mech.com
Fort Collins - Loveland Water District
South Fort Collins Sanitation District
DIXON CANYON LATERAL
C2.00 HORIZONTAL CONTROL
C5.00 EROSION CONTROL STATIC PLAN
C5.10 EROSION CONTROL CONSTRUCTION DETAILS
C7.00-C7.03 CONSTRUCTION DETAILS