The content of this Letter needs to be issued as part the PDP plan response comments on the above mentioned
project.
Department: Current Planning
Contact: Seth Lorson, 970-224-6189, slorson@fcgov.com
Topic: Lighting Plan
Comment Number: 1 Comment Originated: 09/24/2013
09/24/2013: Please submit an alternative compliance request per Sec. 3.2.4(E) for the uplighting on the decorative
light fixtures and the light spill beyond 20' along the ROW that exceeds 0.1 footcandles.
Per the above request we are requesting exterior lighting alternative compliance on the 111 Meldrum Office Building
project in accordance with Fort Collins land use code section 3.2.4(E) for the following (2) items.
Item 1
Section 3.2.4(D)(3) of the land use code requires that light sources be concealed and fully shielded and shall feature
sharp cut-off capability so as to minimize up-light, spill-light, glare and unnecessary diffusion on adjacent property.
We would like to use a hand full of architectural lighting fixtures that produce a pattern of light on the building in
question at (4) select locations. (See sheets 9 & 10 of the PDP submittal). The light fixtures in question are fully
shielded, feature sharp cut-off capability and minimize spill-light, glare and unnecessary diffusion on adjacent
property. They do however, produce a small beam of light patterned on the wall in an upward direction. (The fixture
cut sheets for the “HH” and “KK” fixtures can be found on sheet 12 of the PDP submittal.) We are requesting the
fixtures be allowed as they follow the intent of section 3.2.4(D)(3) by enhancing the cityscape without producing any
unnecessary nuisances on the adjacent properties. Below is an example of the “KK” fixture used at another project in
town.
Adonai Professional Services, Inc. (APS, Inc.)
Electrical Engineers
Page 2
Item 2
Section 3.2.4(D)(8) of the land use code requires light levels measured twenty feet beyond the property line of the
development site (adjacent to residential uses or public rights-of-way)shall not exceed one-tenth (0.1) foot-candle as
a direct result of the on-site lighting. The building to be located at 111 Meldrum will be located within 5’ of the
property line and will have a canopy that extends into the public right-of-way. As a result the one-tenth(0.1) foot-
candle lighting level extends to a distance of 33’ beyond the property line in lieu of the 20’ distance mandated above.
The street curb is approximately 42’ from the property line and the public right-of-way in this area is to be
substantially improved up on as this area will serve as the main entrance into the new building. Due to the proximity
of the building and the public right-of-way we are requesting a variance that would allow the one-tenth foot-candle
level to extend to a distance of 33 feet beyond the property line. It would appear that the lighting levels in this regard
follows the intent of the Land Use Code and does not impose any excessive nuisances that would otherwise
compromise the Land Use Code with regard to light trespass in the public right-of-way as the lighting levels at the
curb line are less than the desired one-tenth level mandated by the code.