November 8, 2012
The City of Ft. Collins
Community Development Services
281 North College Avenue
P.O. Box 580
Ft. Collins, CO 80522
RE: Verizon Wireless 1052 W. Vine Dr, PDP120025, Round No. 1
Verizon Wireless FTC Fat Tire
The following are comments from City and reviewing agencies (italic); Verizon Wireless
response is in bold.
Comment Summary:
Department: Current Planning
Contact: Courtney Levingston, 970-416-2283, clevingston@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 10/15/20
10/15/2012: Please update the site and landscape plan to better clarify the
surrounding context, including clear labeling of Vine & Shields' edge of
pavement (both sides), R.O.W. and property line. Please see redlines.
RESPONSE: Updated per comments, see revised site plan & landscape
plan.
Comment Number: 2 Comment Originated: 10/15/20
10/15/2012: Please move the northeastern most Rocky Mountain Juniper
to/near either the southwestern corner or northwestern corner to help provide
better screening and transition. This also allows for potential future co-location
ground equipment to the east of the monopine tower.
RESPONSE: Rocky Mountain Juniper has been moved per comment,
see updated plans.
RE: Verizon Wireless 1052 W. Vine Dr, PDP120025, Round No. 1
(Continued) Page 2
Comment Number: 3 Comment Originated: 10/15/20
10/15/2012: Remove the last note under the Plant List on the landscape plan
Concerning replacement conformance.
RESPONSE: Note has been removed
Comment Number: 4 Comment Originated: 10/15/20
10/15/2012: The landscaping plan will need a water budget chart showing
total annual water useage. Please see LUC Section 3.2.1(E)(3)(b)(2).
RESPONSE: Water budget chart has been included
Comment Number: 5 Comment Originated: 10/15/20
10/15/2012: The enlarged site plan should be on a sheet separate from the
full site plan.
RESPONSE: The enlarged site plan has been moved to sheet A2.1 per
comment.
Department: Current Planning
Contact: Courtney Levingston, 970-416-2283, clevingston@fcgov.com
Topic: General
Comment Number: 6 Comment Originated: 10/15/20
10/15/2012: On all elevations, please call out that the utility boxes will be
painted to match the building per LUC 3.5.1(I)(3).
RESPONSE: All elevations have been updated ‘paint to match’ per
comment.
Comment Number: 7 Comment Originated: 10/15/20
10/15/2012: On all elevations, please call out the color and material of the
pole "trunk".
RESPONSE: Pole ‘trunk’ material has been called out, as well as color
per comment.
Comment Number: 8 Comment Originated: 10/15/20
10/15/2012: On the elevations, there is reference to a lighting cut sheet please
remove and provide light fixture detail on elevations. Per LUC 3.2.4, must be
fully shielded and down directional. Illustration on elevations should graphically
reflect the code requirement.
RESPONSE: Lighting cut sheet has been included on the elevation sheet
A3.0, the light is fully shielded per requirements noted.
Comment Number: 9 Comment Originated: 10/15/20
10/15/2012: On title sheet (T1.0) please change note regarding co-location as RE: Verizon Wireless
1052 W. Vine Dr, PDP120025, Round No. 1
(Continued) Page 3
follows - Note: "Per LUC 3.8.13(B), no wireless telecommunication facility of
equipment owner or lessee or employee there of shall act to exclude or
attempt to exclude any other wireless provider
from using the same building, structure or location."
RESPONSE: Co-location note has been updated per comments.
Comment Number: 10 Comment Originated: 10/15/20
10/15/2012: On title sheet (T1.0) please change stories from 1 to "3 - 75 feet"
RESPONSE: Clarification / note added,
Number of stories, Equipment Shelter = 1
Height of Monopine = 75’-0”
Comment Number: 11 Comment Originated: 10/15/20
10/15/2012: You will be required to resubmit plans with the changes formally
and have another round of review prior to going to hearing.
RESPONSE: Acknowledged
Comment Number: 12 Comment Originated: 10/16/20
10/16/2012: The zoning on the title sheet (T 1) is incorrect. It says
neighborhood commercial and it should be limited commercial. Please revise.
RESPONSE: Zoning has been updated per comment.
Comment Number: 13 Comment Originated: 10/19/20
10/19/2012: The GPS antenna depicted on the elevation is shown to protrude
above the building which does not meet Section 3.8.13(C)(3) of the Land Use
Code. Please lower the GPS antenna so it does not rise above the top of the
pre-fab equipment shelter.
RESPONSE: GPS antenna has been moved to the monopole (note this
device need exposure to the Southern sky, mounting the device lower
on the equipment shelter will cause the device to not work properly).
Department: Current Planning
Contact: Courtney Levingston, 970-416-2283, clevingston@fcgov.com
Topic: General
Comment Number: 14 Comment Originated: 10/19/20
10/19/2012: The landscape plan notes need revision. Please address the
topics listed under LUC 3.2.1(I), with special care and notice regarding
maintenance and replacement as you propose no irrigation for the trees.
Please add the following notes: Organic soil amendments shall also be
incorporated in accordance with the requirements of Section 3.8.21 of the City
of Fort Collins Land Use Code
1052 W. Vine Dr, PDP120025, Round No. 1
(Continued) Page 4
All plants shall be A-Grade or No. 1 Grade, free of any defects, of normal
health, height, leaf density and spread appropriate to the species as defined by
American Association of Nurserymen standards.
All landscaping shall be installed according to sound horticultural practices in a
manner designed to encourage quick establishment and healthy growth. All
landscaping in each phase shall either be installed or the installation shall be
secured with a letter of credit, escrow or performance bond for one hundred
twenty-five (125) percent of the value of the landscaping
prior to the issuance of a building permit.
Trees and vegetation, irrigation systems, fences, walls and other landscape
elements shall be considered as elements of the project in the same manner
as parking, building materials and other site details. The applicant, landowner
or successors in interest shall be jointly and severally responsible for the
regular maintenance of all landscaping elements in good
condition. All landscaping shall be maintained free from disease, pests, weeds
and litter, and all landscape structures such as fences and walls shall be
repaired and replaced periodically to maintain a structurally sound condition.
Any landscape element that dies, or is otherwise removed, shall be promptly
replaced based on the requirements of this Section.
RESPONSE: Notes have been added to Landscape plan.
Department: Engineering Development Review
Contact: Marc Virata, 970-221-6567, mvirata@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 10/16/20
10/16/2012: The title of the project appears to be FTC Fat Tire based upon
the Title Sheet's "Site Name". If that's the intended title of the project, I don't
see this as a concern, though I'd suggest "Verizon Wireless FTC Fat Tire"
might be of benefit to have the name tied to the
wireless telecommunication use. (Note that this comment isn't intended to
imply any approval towards the use of "Fat Tire" in the title, which for all I know
may be subject to concerns of intellectual property of New Belgium Brewing
Company.)
RESPONSE: Project name has been updated to ‘Verizon Wireless FTC
Fat Tire’ per comment.
Department: Engineering Development Review
Contact: Marc Virata, 970-221-6567, mvirata@fcgov.com
Topic: General
1052 W. Vine Dr, PDP120025, Round No. 1
(Continued) Page 5
Comment Number: 2 Comment Originated: 10/16/20
10/16/2012: The "New 16'-10" Access & Utility Easement" should be revised
to 20' in width and be dedicated as an "Emergency Access & Utility Easement"
per discussion with PFA at the 10/17 Staff Review. The dedication of this
easement (and any easements) to the City requires deeds of dedication in an
approved City format (the template will be emailed separately) along
with a $250 fee for each easement, and county recordation costs in an amount
to be determined. The required deed(s) of dedication will need to be in place
prior to final plan approval of the project (after public hearing).
RESPONSE: Easement has been revised to a 20’-0- ‘Emergency Access
& Utility Easement’. Easement will be recorded as requested.
Comment Number: 3 Comment Originated: 10/16/20
10/16/2012: The "10' Utility Easement" should be indicated as "Existing 10'
Utility Easement".
RESPONSE: 10’ Utility Easement has been updated to existing 10’ Utility
Easement per comment.
Comment Number: 4 Comment Originated: 10/16/20
10/16/2012: The City typically uses a "Utility Plan" as a construction plan set
that is filed separately from the site plan and is approved by the City Engineer,
requiring to be prepared by a licensed engineer and indicates the public
infrastructure proposed for construction with the development. Does the "utility
plan" submitted here have any associated public infrastructure
associated with it, or are the utilities pertaining to the operations specific to
Verizon Wireless? We may wish to have this sheet either incorporated into the
site plan sheet and eliminate this sheet, or label the sheet different than "Utility
Plan" to not confuse our typical approach with utility plans.
RESPONSE: Sheet has been removed, all data is listed on A2.0 Site Plan
and LS1 Land Survey.
Comment Number: 5 Comment Originated: 10/16/20
10/16/2012: Why is the "Utility Plan" sheet using all the same notation of "W"
to label telephone, gas, and chain link fence? The information is unclear as a
result. Please rectify.
RESPONSE: Sheet has been deleted
Comment Number: 6 Comment Originated: 10/16/20
10/16/2012: The right-of-way existing for both Vine Drive and Shields Street
appears to be sufficient abutting the property for the roadway classifications of
these streets. Additional dedication for utility easement as well as obligation for
1052 W. Vine Dr, PDP120025, Round No. 1
(Continued) Page 6
roadway improvements to these streets
may be required with future development/redevelopment of the parcel.
RESPONSE: Acknowledged
Department: Forestry
Contact: Tim Buchanan, 970-221-6361, tbuchanan@fcgov.com
Topic: General
Comment Number: 3 Comment Originated: 10/19/20
10/19/2012: Watering:
Thoroughly soak the soil ball and surrounding soil at planting.
Following transplanting, and through the first three growing seasons, trees
shall receive supplemental watering at a rate of minimum of 50 gallons of
water each week during the growing season (from April through September);
and 50 gallons every four weeks during the winter (October through March).
Water shall be applied over the top of the soils ball. If trees
appear stressed apply additional water at each irrigation cycle. Length of water
cycles may be modified slightly as determined appropriate by a qualified
landscape contractor.
RESPONSE: Note has been added to L1.0 per the above comment, and
calculated square foot water estimate added to water budget chart.
Comment Number: 4 Comment Originated: 10/19/20
10/19/2012: Landscape contractor to contact the City Forester at the end of
three seasons of tank irrigation to determine if trees can survive without
additional irrigation or if addition irrigation will be required.
RESPONSE: Acknowledged, note has been added to the L1.0 sheet.
Topic: Landscape Plans
Comment Number: 1 Comment Originated: 10/16/20
10/16/2012: Adding a few additional trees is possible with the spacing shown
on the landscape plan. This could provide better initial screening of the base
per LUC 3.2.1(E).
RESPONSE: Acknowledged, no additional landscaping has been shown
Comment Number: 2 Comment Originated: 10/19/20
10/19/2012: Planting detail:
Include 8 inch water basin at edge of planting hole
Mulch 4 inches deep within planting basin
1052 W. Vine Dr, PDP120025, Round No. 1
(Continued) Page 6
No need to wrap tree trunks on conifers
Don't over excavate the depth of the tree planting pit
Remove top half of wire basket and pull burlap back off the top of the ball
Remove all twine and labels
Surface of tree ball to be 1 inch higher that existing grade
RESPONSE: Acknowledged, planting detail on L1 has been revised per
comments.
Department: Light And Power
Contact: Alan Rutz, 970-224-6153, arutz@fcgov.com
Topic: General
Comment Number: 2 Comment Originated: 10/16/20
10/16/2012: A new transformer will need to be installed for this project.
RESPONSE: Acknowledged
Department: Light And Power
Contact: Doug Martine, 970-224-6152, dmartine@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 10/01/20
10/01/2012: Light & Power Engineering will need a Commercial Service
Information (C-1) form completed. Electric development and system
modifications will apply. Please coordinate
power requirements with Light & Power Engineering at (970)221-6700.
RESPONSE: Acknowledged
Department: PFA
Contact: Jim Lynxwiler, 970-416-2869, jlynxwiler@poudre-fire.org
Topic: General
Comment Number: 1 Comment Originated: 10/17/20
10/17/2012: FIRE LANE
Shall be designated on the plat as an Emergency Access Easement.
Maintain the required 20 foot minimum unobstructed width & 14 foot minimum
overhead clearance. Be designed as a flat, hard, all-weather driving surface
capable of supporting 40 tons.
Be visible by signage and maintained unobstructed at all times.
2006 International Fire Code 503.2.3, 503.3, 503.4 and Appendix D
RESPONSE: Emergency access has been updated to a 20’W and has a
note for road base (4” class 5 road base) for emergency vehicles.
1052 W. Vine Dr, PDP120025, Round No. 1
(Continued) Page 7
Comment Number: 2 Comment Originated: 10/17/20
10/17/2012: TURNING RADII
The required turning radii of a fire apparatus access road shall be a minimum
of 25 feet inside and 50 feet outside.
International Fire Code 503.2.4 and Local Amendments
RESPONSE: Turning radius is min. 25’-0” as noted on plans.
Comment Number: 3 Comment Originated: 10/17/20
10/17/2012: PREMISE IDENTIFICATION
New and existing buildings shall be plainly identified. Address numbers shall
be visible from the street fronting the property, plainly visible, and posted with a
minimum of six-inch numerals on a contrasting background.
2006 International Fire Code 505.1
RESPONSE: A note has been added to the enlarged site plan A2.1 to
add required signage per requirements.
Comment Number: 4 Comment Originated: 10/17/20
10/17/2012: BATTERY STORAGE SYSTEMS
Stationary storage battery systems used for standby power and having an
electrolyte capacity in excess of 50 gallons of stationary lead acid or 1,000 lbs
lithium ion shall comply with Section
608 and Table 608.1 of the International Fire Code.
RESPONSE: Acknowledged
Comment Number: 5 Comment Originated: 10/17/20
10/17/2012: DIESEL GENERATOR
Storage systems for diesel fuel shall provide for spill control and secondary
containment when the storage vessel exceeds 55 gallons. Other conditions
apply to combustible liquid storage.
Refer to Sections 2704 and 3404 of the 2006 International Fire Code for more
details.
RESPONSE: Acknowledged
Department: Stormwater Engineering
Contact: Mark Taylor, , mtaylor@fcgov.com
Topic: Floodplain
Comment Number: 1 Comment Originated: 10/16/20
Any and all construction activities in the flood fringe must be preceded by an
approved Floodplain Use Permit, $25 fee, and approved plans (at time of
building permit). This can be found online at:
http://www.fcgov.com/utilities/what-we-do/stormwater/flooding/forms-document
Please contact Mark Taylor, 970.416.2494, mtaylor@fcgov.com with
questions.
1052 W. Vine Dr, PDP120025, Round No. 1
(Continued) Page 8
RESPONSE: Acknowledged
Comment Number: 3 Comment Originated: 10/18/20
10/18/2012: On enlarged site plan sep. sheet, please show (call out) the
separation between flood fringe and monopine base.
RESPONSE: Dimension has been added (1’-3”) building separation from
flood fringe.
Comment Number: 4 Comment Originated: 10/18/20
10/18/2012: Is the tower (monopine trunk) and the contents of waterproof? If
so, please add the following note on the site plan: "The contents of the tower
and the tower itself is waterproof. In the event of flooding, the City of Fort
Collins is not responsible for any damage." If not, please call Mark Taylor.
RESPONSE: Monopine trunk is water proof, note has been added to the
drawings per comments.
Contact: Wes Lamarque, 970-416-2418, wlamarque@fcgov.com
Topic: General
Comment Number: 2 Comment Originated: 10/16/20
10/16/2012: Please document on the site plan how much the new facility
within the lease area will increase the impervious area. (rooftop, concrete,
asphalt, etc.)
RESPONSE: Table added to sheet A2.0 with all information.
Department: Technical Services
Contact: Jeff County, 970-221-6588, jcounty@fcgov.com
Topic: Building Elevations
Comment Number: 4 Comment Originated: 10/16/20
10/16/2012: There are line over text issues on all(including color 11"x17")
sheets A3.0 & A3.1.
RESPONSE: Acknowledged, due to limited space on sheet layout, all
text has been removed for clarity. A note has been added to reference
elevations sheets for specific information, heights, notes, color, etc.
Comment Number: 5 Comment Originated: 10/16/20
10/16/2012: Please trim everything shown outside of the border on the color
11"x17" sheets A3.0 & A3.1.
RESPONSE: Acknowledged
Topic: Construction Drawings
Comment Number: 3 Comment Originated: 10/16/20
10/16/2012: Please change the elevation & datum of the benchmark
1052 W. Vine Dr, PDP120025, Round No. 1
(Continued) Page 9
on sheet A2.1. The City of
Fort Collins requires the 1929 unadjusted datum.
RESPONSE: The drawings have been updated to reflect the elevation &
datum as requested.
Topic: General
Comment Number: 1 Comment Originated: 10/16/20
10/16/2012: Please add a legal description to sheet T1.0.
RESPONSE: Legal description has been added
Comment Number: 2 Comment Originated: 10/16/20
10/16/2012: Please add a sheet index to sheet T1.0.
RESPONSE: Index has been added