HomeMy WebLinkAboutTHE DISTRICT @ CAMPUS WEST - PDP - PDP120003 - SUBMITTAL DOCUMENTS - ROUND 1 - RECOMMENDATION/REPORTGeotechnical Engineering Report THE DISTRICT AT CSU East of West Plum Street and City Park Avenue Fort Collins, Colorado November 2, 2011 Terracon Project No. 20115026 Prepared for: Ft. Collins Student Housing, LLC Houston, Texas Prepared by: Terracon Consultants, Inc. Fort Collins, Colorado TABLE OF CONTENTS Page EXECUTIVE SUMMARY .............................................................................................................. ii 1.0 INTRODUCTION ............................................................................................................... 1 2.0 PROJECT INFORMATION ............................................................................................... 1 2.1 Project Description ................................................................................................ 1 2.2 Site Location and Description ................................................................................ 2 3.0 SUBSURFACE CONDITIONS .......................................................................................... 3 3.1 Typical Profile ........................................................................................................ 3 3.2 Groundwater .......................................................................................................... 4 4.0 RECOMMENDATIONS FOR DESIGN AND CONSTRUCTION ....................................... 5 4.1 Geotechnical Considerations................................................................................. 5 4.1.1 Existing Fill................................................................................................. 5 4.1.2 Structural Recommendations .................................................................... 5 4.2 Earthwork .............................................................................................................. 6 4.2.1 Site Preparation ......................................................................................... 6 4.2.2 Import Material Specifications .................................................................... 7 4.2.3 Compaction Requirements ........................................................................ 7 4.2.4 Excavation and Trench Construction ......................................................... 8 4.2.5 Utility Trench Backfill ................................................................................. 8 4.2.6 Grading and Drainage ............................................................................... 9 4.2.7 Construction Considerations .................................................................... 10 4.2.8 Corrosion Protection ................................................................................ 10 4.3 Foundations ......................................................................................................... 10 4.3.1 Design Recommendations – Spread Footings ........................................ 11 4.3.2 Construction Considerations – Spread Footings ..................................... 11 4.3.3 Design Recommendations – Drilled Piers ............................................... 12 4.3.4 Construction Considerations – Drilled Piers ............................................ 12 4.4 Seismic Considerations ....................................................................................... 13 4.5 Interior Floor Systems ......................................................................................... 14 4.5.1 Design Recommendations – Slabs-on-grade ......................................... 14 4.5.2 Construction Considerations – Slabs-on-grade ...................................... 15 4.6 Below-grade Construction ................................................................................... 15 4.7 Lateral Earth Pressures ....................................................................................... 16 4.8 Pavement Design and Construction .................................................................... 17 4.8.1 Drainage Adjacent to Pavements ............................................................ 19 4.8.2 Compliance .............................................................................................. 19 4.8.3 Pavement Performance ........................................................................... 19 4.8.4 Construction Considerations .................................................................... 20 5.0 GENERAL COMMENTS ................................................................................................. 20 TABLE OF CONTENTS (Cont’d) APPENDIX A – FIELD EXPLORATION Exhibit A-1 Field Exploration Description Exhibit A-2 Boring Location Diagram Exhibits A-3 to A-9 Logs of Borings from Previous Study (Project No. 20085059) Exhibits A-10 to A-13 Logs of Borings for Current Study APPENDIX B – LABORATORY TESTING Exhibit B-1 Laboratory Testing Exhibits B-2 to B-23 Laboratory Test Results from Previous Study and Current Study APPENDIX C – SUPPORTING DOCUMENTS Exhibit C-1 General Notes Exhibit C-2 Unified Soil Classification Exhibit C-3 Rock Classification Exhibit C-4 Laboratory Test Significance and Purpose Exhibits C-5 and C-6 Report Terminology Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable ii EXECUTIVE SUMMARY A geotechnical engineering exploration has been performed for the proposed student housing development known as The District at CSU to be constructed east of the intersection of West Plum Street and City Park Avenue in Fort Collins, Colorado. Four (4) borings, presented as Exhibits A-3 through A-6 and designated as Boring Nos. 8 through 11, were performed to depths ranging from about 25 feet to 45 feet below the existing ground surface. These four new borings were used to supplement seven (7) borings drilled during a previous study on the project site. This report presents geotechnical recommendations for design and construction of the proposed student housing development and associated infrastructure. Based on the information obtained from our subsurface exploration and the laboratory testing completed, the site appears suitable for the proposed construction; however, the following geotechnical conditions will need to be considered:  Soils and bedrock encountered during our field exploration generally consisted of up to about ½ foot of topsoil or gravel paving over clay with varying amounts of sand and gravel and sand with varying amounts of silt, clay, and gravel underlain by weathered to unweathered claystone bedrock.  The proposed student housing and clubhouse buildings may be supported on spread footing foundations bearing upon undisturbed soils, suitable fill materials and/or newly placed engineered fill. Drilled pier foundations bottomed in bedrock may also be considered as an alternative foundation system for the student housing and/or clubhouse buildings if footing foundations are not feasible due to heavy building loads. The proposed parking garage should be supported on a drilled pier foundation system bottomed in bedrock.  It is our understanding that the existing structures on the site will be razed. Based on our limited site observations, we anticipate that some of the existing structures have basement construction. Care should be taken during site preparation to include complete removal of the foundation systems and basements as well as backfilling the resulting excavations within the proposed construction area.  Considering the low swelling soils encountered in our borings on this site, we believe a slab-on-grade floor system can be used for the proposed buildings provided some movement can be tolerated. If no or very little movement is desired, structurally- supported floor systems should be used for the proposed buildings.  Groundwater was measured at depths ranging from about 10 to 25 feet below the existing ground surface during our field studies conducted at this site. If the project team elects to extend the proposed parking garage below grade, it is possible the parking Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable iii garage will encroach upon groundwater. We recommend a 3-foot separation between the bottom of the lower floor for the parking garage and groundwater. If this separation is not maintained, a permanent dewatering system will be required.  The 2009 International Building Code (IBC), Table 1613.5.2 IBC seismic site classification for this site is C. This summary should be used in conjunction with the entire report for design purposes. It should be recognized that details were not included or fully developed in this section, and this report must be read in its entirety for a comprehensive understanding of the items contained herein. The section titled GENERAL COMMENTS should be read for an understanding of the report limitations. Responsive ■ Resourceful ■ Reliable 1 GEOTECHNICAL ENGINEERING REPORT The District at CSU East of West Plum Street and City Park Avenue Fort Collins, Colorado Terracon Project No. 20115026 November 2, 2011 1.0 INTRODUCTION A geotechnical engineering report has been completed for the proposed student housing development to be located east of the intersection of West Plum Street and City Park Avenue in Fort Collins, Colorado. As part of our subsurface exploration, a total of four (4) borings were drilled at the site. The Logs of Borings and Boring Location Diagram are included in Appendix A of this report. The four new borings drilled as part of this study were performed to supplement soil test borings drilled during a previous study conducted at this site. The results of our previous study are presented in our Geotechnical Engineering Report (Project No. 20085059; report dated August 21, 2008). Information presented in our previous study was considered during preparation of this report. The Logs of Borings and laboratory test results are compiled along with the data collected for this study in the appendices of this report. The purpose of these services is to provide information and geotechnical engineering recommendations relative to:  Subsurface soil and bedrock conditions  Floor system design and construction  Groundwater conditions  Foundation design and construction  Earthwork  Lateral earth pressures  Seismic considerations  Pavement construction  Grading and Drainage 2.0 PROJECT INFORMATION 2.1 Project Description Item Dsecription Site layout See Appendix A, Exhibit A-2, Boring Location Diagram Proposed construction Preliminary concepts indicate this project will consist of construction of several student housing buildings, a six-story parking garage possibly with ½ to 1 level below-grade, a clubhouse, a swimming pool, courtyards, and associated infrastructure including buried utilities, concrete flatwork, and access drives. Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 2 Item Dsecription Building construction The exact building layouts have not been finalized at this time. We understand the student housing buildings and clubhouse will be 4 to 5 stories with no basement or below-grade areas. We anticipate the student housing buildings will be steel-framed and/or wood- framed structures possibly with structural masonry supported by cast-in-place concrete foundations. The parking garage is anticipated to be up to about 60 feet tall and will consist of concrete foundation walls and/or precast concrete walls. Finished floor elevation Unknown at the time that this report was prepared Maximum loads Student Housing and Clubhouse Columns: 50 to 250 kips (assumed) Walls: 2 to 5 klf (assumed) Parking Garage Columns: up to 1,200 kips (assumed) Walls: 5 to 10 klf (assumed) Grading Preliminary Site Grading Plans were not available at the time this report was written. Based upon the existing topography in the area of proposed construction, we assume cuts and fills of less than about 6 feet will be necessary to achieve desired grades. Deeper cuts and fills on the order of 6 to 10 feet will be required to demolish and remove existing site buildings and associated elements. Infrastructure Installation of underground utilities within about 5 feet of finished site grades. Installation of pavements for drives and parking. Below-grade areas No below grade areas are planned for the student housing and clubhouse buildings. We understand the parking structure may extend up to about 12 feet below-grade. Traffic Loading Light-duty (parking lots): Assumed to not exceed 15,000 ESALs Heavy-duty (truck traffic): Assumed 75,000 ESALs 2.2 Site Location and Description Item Description Location The project site is located east of the intersection of West Plum Street and City Park Avenue in Fort Collins, Colorado. Existing improvements The site is currently occupied by 4-plex, 8-plex and single-family residential structures with some existing roadways also occupying portions of the site between the existing structures. There are several large clusters of mature trees at various locations on the property. We understand these structures will be demolished and removed prior to the new construction. Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 3 Item Description Current ground cover The lots are landscaped with sod, bushes, and mature deciduous trees surrounding existing residential buildings. The existing roadways are paved with asphalt or gravel-surfaced. Existing topography The site is relatively flat sloping gently away from the existing structures and generally down towards to the south and east. 3.0 SUBSURFACE CONDITIONS 3.1 Typical Profile Based on the results of the borings, subsurface conditions encountered underlying the existing ground surface on the project site can be generalized as follows: Material Description Approximate Depth to Bottom of Stratum (ft.) Consistency/Density/Hardness Topsoil or gravel paving About ½ foot --- Fill materials consisting of sandy lean clay with varying amounts of gravel About 3½ to 9 feet in Boring Nos. 3, 6 and 8 only Stiff to very stiff Sandy lean clay About 12 to 17½ feet except in Boring Nos. 6 and 7 Medium stiff to hard Silty to clayey sand with varying amounts of gravel About 13 to 18½ feet except in Boring Nos. 1, 4 and 10 Loose to dense Claystone bedrock To the maximum explored depths of about 20 to 45 feet Weathered to very hard Subsurface conditions encountered at each boring location are indicated on the individual Logs of Borings. Stratification boundaries on the Logs of Borings represent the approximate depths of changes in soil and bedrock type, the transition between materials may be gradual. The Logs of Borings are attached in Appendix A of this report. Laboratory testing was conducted on selected samples of the soils and bedrock collected during our field explorations and the test results for our previous study and this current study are presented in Appendix B and on the attached Logs of Borings. Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 4 3.2 Groundwater The borings were observed while drilling and after completion for the presence and level of groundwater. Groundwater levels measured in Boring Nos. 1 through 7 were measured in August 2008 and groundwater levels measured in Boring Nos. 8 through 11 were measured in September 2011. The groundwater levels are noted on the attached Logs of Borings, and are summarized below. Boring No. Depth to groundwater while drilling (ft.) Depth to groundwater one day after drilling (ft.) 1 15.5 Backfilled 2 Not encountered 16.7 3 Not encountered 25.0 4 12.5 12.5 5 13.5 14.6 6 Not encountered 15.0 7 Not encountered 18.2 8 10.0 Backfilled 9 Not encountered Backfilled 10 11.7 Backfilled 11 12.0 Backfilled These observations represent groundwater conditions at the time of the field exploration, and may not be indicative of other times or at other locations. Groundwater levels can be expected to fluctuate with varying seasonal and weather conditions, and other factors. Zones of perched and/or trapped groundwater may also occur at times in the subsurface soils overlying bedrock, on top of the bedrock surface or within permeable fractures in the bedrock materials. The location and amount of perched water is dependent upon several factors, including hydrologic conditions, type of site development, irrigation demands on or adjacent to the site, fluctuations in water features, seasonal and weather conditions. Groundwater level fluctuations occur due to seasonal variations in the amount of rainfall, runoff and other factors not evident at the time the borings were performed. Therefore, groundwater levels during construction or at other times in the life of the structures may be higher or lower than the levels indicated on the boring logs. The possibility of groundwater level fluctuations should be considered when developing the design and construction plans for the project. Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 5 4.0 RECOMMENDATIONS FOR DESIGN AND CONSTRUCTION 4.1 Geotechnical Considerations Based on the results of our study, it is our opinion that the site is suitable for the proposed construction from a geotechnical point of view provided certain precautions and design and construction recommendations outlined in this report are followed. We have identified geotechnical conditions that could impact design and construction of the proposed structures and other site improvements. 4.1.1 Existing Fill As previously noted, about 3½ to 9 feet of existing, undocumented fill was encountered in the borings drilled at the site. Deeper fills may be present around basements and within buried utility trenches for the existing buildings currently occupying the site. We do not possess any information regarding whether the fill was placed under the observation of a geotechnical engineer. Support of foundations, floor slabs, and pavements on or above existing fill soils is discussed in this report. However, even with the recommended construction testing services, there is an inherent risk for the owner that compressible fill or unsuitable material within or buried by the fill will not be discovered. This risk cannot be eliminated without completely removing the existing fill, but can be minimized by thorough exploration, testing and remedial earthwork. If additional exploration is not performed, the owner should make allowances for such conditions to exist in the preparation of the project budget and/or construction plans. Based upon the field penetration resistance values, in-situ dry densities, moisture contents, and the laboratory swell/expansion test data, it is our opinion the existing fill can be used for support of foundations, floor slabs-on-grade and pavements without the need for removal and/or recompaction. However, the consistency and relative density of the existing fill must be verified prior to foundation, slab-on-grade and pavement construction to assess that similar conditions exist across the site with those encountered in the borings. 4.1.2 Structural Recommendations Based on the geotechnical engineering analyses, subsurface exploration and laboratory test results, the proposed student housing and clubhouse buildings may be supported on spread footing foundations bearing upon undisturbed soils, suitable fill materials and/or newly placed engineered fill. Drilled pier foundations bottomed in bedrock may also be considered as an alternative foundation system for the student housing and/or clubhouse buildings if footing foundations are not feasible due to heavy building loads. The proposed parking garage should be supported on a drilled pier foundation system bottomed in bedrock. Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 6 Considering the low swelling soils encountered in our borings on this site, we believe a slab-on- grade floor system can be used for the proposed buildings provided some movement can be tolerated. If very little movement can be tolerated, structural floors, supported independent of the subgrade materials, are recommended. Design and construction recommendations for the foundation system and other earth connected phases of the project are outlined in subsequent sections. 4.2 Earthwork The following presents recommendations for site preparation, excavation, subgrade preparation and placement of engineered fills on the project. All earthwork on the project should be observed and evaluated by Terracon on a full-time basis. The evaluation of earthwork should include observation and testing of engineered fills, subgrade preparation, proof-rolling, and other geotechnical conditions exposed during the construction of the project. 4.2.1 Site Preparation Strip and remove existing concrete, asphalt, vegetation, unsuitable fills and other deleterious materials from below proposed buildings, pavements, and areas planned to receive fill prior to construction. All exposed surfaces should be free of mounds and depressions which could prevent uniform compaction. Stripped materials consisting of vegetation and organic materials should be wasted from the site or used to revegetate landscaped areas or exposed slopes after completion of grading operations. All exposed areas which will receive fill, once properly cleared and benched, should be scarified to a minimum depth of 10 inches, moisture conditioned to near optimum moisture content and compacted. Demolition of the existing buildings should include complete removal of the foundation systems within the proposed construction area. This should include removal of any loose backfill found adjacent to the existing foundations. All materials derived from the demolition of the existing structure should be removed from the site and should not be allowed for use in any on-site fills. Abandoned utilities associated with the structures should be completely removed or grouted in- place. The types of foundation systems supporting the existing residences are not known. If some or all of the buildings are supported by drilled piers, the existing piers should be truncated a minimum depth of 3 feet below areas of planned new construction. Although evidence of significant amounts of unsuitable fills or underground facilities such as septic tanks, cesspools, basements and utilities was not observed during the site reconnaissance, such features could be encountered during construction. If significant amounts Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 7 of unsuitable fills or underground facilities are encountered, such features should be removed and the excavation thoroughly cleaned prior to backfill placement and/or construction. The stability of the subgrade may be affected by precipitation, repetitive construction traffic or other factors. If unstable conditions are encountered or develop during construction, workability may be improved by scarifying and drying; however, allowing the clays to dry below the optimum moisture content is not recommended. If such conditions occur, the affected area should be overexcavated and replaced with granular materials and/or non- to low expansive materials. As an alternative, chemical treatment such as lime, fly ash, kiln dust, cement or geotextiles could also be considered as a stabilization technique. Laboratory evaluation is recommended to determine the effect of chemical stabilization on subgrade soils prior to construction. Lightweight excavation equipment may be required to reduce subgrade pumping. 4.2.2 Import Material Specifications Clean on-site soils or approved imported materials may be used as fill material. Imported soils (if required) should meet the following material property requirements: Gradation Percent finer by weight (ASTM C136) 4” 100 3” 70-100 No. 4 Sieve 50-100 No. 200 Sieve 15-50  Liquid Limit……………………………………………………30 (max)  Plastic Limit…………………………………………………..15 (max)  Maximum Expansive Potential (%)………………………..non-expansive* *Measured on a sample compacted to approximately 95 percent of the ASTM D698 maximum dry density at optimum water content. The sample is confined under a 100 psf surcharge and submerged. 4.2.3 Compaction Requirements Engineered fill should be placed and compacted in horizontal lifts, using equipment and procedures that will produce recommended moisture contents and densities throughout the lift. Item Description Fill lift thickness 8 to 10-inches or less in loose thickness Compaction requirements (clay) 95 percent of the maximum dry unit weight as determined by ASTM D 698 Moisture content cohesive soil (clay) -2 to +2 % of the optimum moisture content -1 to +2% of the optimum moisture content in pavement areas Moisture content cohesionless soil (sand) -3 to +3 % of the optimum moisture content Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 8 Item Description 1. We recommend engineered fill be tested for moisture content and compaction during placement. Should the results of the in-place density tests indicate the specified moisture or compaction limits have not been met, the area represented by the test should be reworked and retested as required until the specified moisture and compaction requirements are achieved. 2. Specifically, moisture levels should be maintained low enough to allow for satisfactory compaction to be achieved without the fill material pumping when proof-rolled. 4.2.4 Excavation and Trench Construction Excavations into the on-site soils may encounter caving soils and possibly groundwater, depending upon the final depth of excavation. We believe excavations into on-site soils can generally be performed using conventional excavation equipment. Excavations into the clays above groundwater levels below the site can be expected to stand on relatively steep temporary slopes during construction. However, excavations into clays and sands below the water table will likely require sloping or shoring of the excavation sides and temporary construction dewatering. The individual contractor(s) should be made responsible for designing and constructing stable, temporary excavations as required to maintain stability of both the excavation sides and bottom. All excavations should be sloped or shored in the interest of safety following local and federal regulations, including current OSHA excavation and trench safety standards. Soils penetrated by the proposed excavations may vary significantly across the site. The soil classifications are based solely on the materials encountered in the exploratory test borings. The contractor should verify that similar conditions exist throughout the proposed area of excavation. If different subsurface conditions are encountered at the time of construction, the actual conditions should be evaluated to determine any excavation modifications necessary to maintain safe conditions. As a safety measure, it is recommended that all vehicles and soil piles be kept to a minimum lateral distance from the crest of the slope equal to no less than the slope height. The exposed slope face should be protected against the elements. Depending upon depth of excavation and seasonal conditions, groundwater may be encountered in excavations on the site. Pumping from sumps and/or sloping of excavations to collection areas may be utilized to control water within excavations. 4.2.5 Utility Trench Backfill All trench excavations should be made with sufficient working space to permit construction including backfill placement and compaction. All underground piping within or near the proposed structures should be designed with flexible couplings, so minor deviations in alignment do not result in breakage or distress. Utility knockouts in foundation walls should be oversized to accommodate differential movements. It is Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 9 imperative that utility trenches be backfilled with relatively clean materials and is properly backfilled. If utility trenches are backfilled with relatively clean granular material, they should be capped with at least 18 inches of cohesive fill in non-pavement areas to reduce the infiltration and conveyance of surface water through the trench backfill. Utility trenches are a common source of water infiltration and migration. All utility trenches that penetrate beneath the buildings should be effectively sealed to restrict water intrusion and flow through the trenches that could migrate below the buildings. We recommend constructing an effective clay “trench plug” that extends at least 5 feet out from the face of the building exterior. The plug material should consist of clay compacted at a water content at or above the soils optimum water content. The clay fill should be placed to completely surround the utility line and be compacted in accordance with recommendations in this report. It is strongly recommended that a representative of the geotechnical engineer provide full-time observation and compaction testing of trench backfill within building and pavement areas. 4.2.6 Grading and Drainage All grades must be adjusted to provide positive drainage away from the buildings during construction and maintained throughout the life of the proposed project. Infiltration of water into utility or foundation excavations must be prevented during construction. Landscaped irrigation adjacent to foundations should be minimized or eliminated. Water permitted to pond near or adjacent to the perimeter of structures (either during or post-construction) can result in greater soil movements than those discussed in this report. As a result, any estimations of potential movement described in this report cannot be relied upon if positive drainage is not obtained and maintained, and water is allowed to infiltrate the fill and/or subgrade. Exposed ground should be sloped at a minimum of 10 percent grade for at least 10 feet beyond the perimeter of the buildings, where possible. The use of swales, chases and/or area drains may be required to facilitate drainage in unpaved areas around the perimeter of the buildings. Backfill against exterior walls and in utility and sprinkler line trenches should be well compacted and free of all construction debris to reduce the possibility of moisture infiltration. After building construction and prior to project completion, we recommend verification of final grading be performed to document positive drainage, as described above, has been achieved. Flatwork and pavements will be subject to post construction movement. Maximum grades practical should be used for paving and flatwork to prevent areas where water can pond. In addition, allowances in final grades should take into consideration post-construction movement of flatwork, particularly if such movement would be critical. Where paving or flatwork abuts the structures, care should be taken that joints are properly sealed and maintained to prevent the infiltration of surface water. Planters located adjacent to structures should preferably be self-contained. Sprinkler mains and spray heads should be located a minimum of 5 feet away from the building lines. Drip irrigation Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 10 may be considered in these areas. Roof drains should discharge on pavements or be extended away from the structures a minimum of 10 feet through the use of splash blocks or downspout extensions. A preferred alternative is to have the roof drains discharge to storm sewers by solid pipe or daylighted to a detention pond or other appropriate outfall. 4.2.7 Construction Considerations Upon completion of grading operations, care should be taken to maintain the moisture content of the subgrade prior to construction of pavements and exterior concrete flatwork. Construction traffic over prepared subgrade should be minimized and avoided to the extent practical. The site should also be graded to prevent ponding of surface water on the prepared subgrades or in excavations. In areas where water is allowed to pond over a period of time, the affected area should be removed and allowed to dry out; however, allowing the clays to dry out below the optimum moisture content is not recommended. If such conditions occur, the affected area should be over-excavated and replaced with granular materials and/or non- to low expansive materials. As an alternative, chemical treatment such as lime, fly ash, kiln dust, cement or geotextiles could also be considered as a stabilization technique. Terracon should be retained during the construction phase of the project to observe earthwork and to perform necessary tests and observations during site grading operations, excavations, subgrade preparation, proof-rolling, placement and compaction of controlled compacted fills, backfilling of excavations into the completed subgrade, and pavement construction. 4.2.8 Corrosion Protection Results of water-soluble sulfate testing performed on the existing soils indicated negligible values of 20 mg/l or less. Results of soluble sulfate testing indicate that ASTM Type I Portland cement is suitable for all project concrete on and below grade. However, if there is no (or minimal) cost differential, use of ASTM Type II Portland cement is recommended for additional sulfate resistance of construction concrete. Foundation concrete should be designed in accordance with the provisions of Section 318, Chapter 4, of the ACI Design Manual. 4.3 Foundations Several foundation alternatives were considered for the proposed buildings at this site. Based on the geotechnical engineering analyses, subsurface exploration and laboratory test results, the proposed student housing and clubhouse buildings may be supported on spread footing foundations bearing upon undisturbed soils, suitable fill materials and/or newly placed engineered fill. Drilled pier foundations bottomed in bedrock may also be considered as an alternative foundation system for the student housing and/or clubhouse buildings if footing foundations are not feasible due to heavy building loads. The proposed parking garage should be supported on a drilled pier foundation system bottomed in bedrock. Design Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 11 recommendations for spread footings and drilled piers bottomed in bedrock are presented in the following paragraphs. 4.3.1 Design Recommendations – Spread Footings Description Value Maximum allowable soil bearing pressure 1 2,500 psf Minimum dimensions Column Wall Footing 24 inches 16 inches Minimum embedment below finished grade for frost protection 2 30 inches 30 inches Estimated post-construction movement 3 about 1 inch about 1 inch 1. The net allowable soil bearing pressure applies to dead loads plus design live load conditions and is the maximum pressure that should be transmitted to the bearing soils in excess of the minimum surrounding overburden pressure at the footing base elevation. Assumes footing subgrade will be judged stable and if unstable conditions are encountered, subgrade will be stabilized prior to foundation construction. 2. For perimeter footings and footings beneath unheated areas. Interior column pads in heated areas should bear at least 12 inches below the adjacent grade (or the top of the floor slab) for confinement of the bearing materials and to develop the recommended bearing pressure. 3. Additional foundation movements could occur if surface water infiltrates the foundation soils; therefore, proper drainage away from the foundation system should be provided in the final design, during construction and maintained throughout the life of the structure. Footings should be proportioned to reduce differential foundation movement. Proportioning on the basis of relative constant dead-load pressure can provide a means to reduce differential movement between adjacent footings. Footings and foundation walls should be reinforced as necessary to reduce the potential for distress caused by differential foundation movement. 4.3.2 Construction Considerations – Spread Footings Subgrade soils beneath footings should be moisture conditioned and compacted. The moisture content and compaction of subgrade soils should be maintained until foundation construction. Where soils are loosened during excavation or in the forming process for the footings, or if soft/low strength or otherwise unsuitable soils are present at foundation bearing depth, they should be removed and replaced with engineered fill or re-compacted to at least 95 percent of the maximum dry unit weight as determined by ASTM D698 within 2 percent of optimum moisture content. Completed foundation excavations should be observed by a representative of Terracon well in advance of forming footings to confirm satisfactory bearing materials are present and Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 12 subsurface conditions are consistent with those encountered in our borings. If the soil conditions encountered differ significantly from those presented in this report, supplemental recommendations will be required. 4.3.3 Design Recommendations – Drilled Piers Drilled pier and grade beam foundation systems are considered a suitable deep foundation system for support of the proposed student housing and/or clubhouse buildings. We recommend constructing the proposed parking garage on a drilled pier foundation system bottomed in bedrock. Description Value Minimum pier length 25 feet Minimum pier diameter 18 inches Minimum bedrock embedment 1 8 feet Maximum end-bearing pressure 30,000 psf Skin friction (for portion of pier embedded in bedrock) 2,500 psf Void Thickness (beneath grade beams, between piers) 4 inches 1. Drilled piers should be embedded into firm or harder bedrock materials. Piers should be considered to work in group action if the horizontal spacing is less than three pier diameters. A minimum practical horizontal clear spacing between piers of at least three diameters should be maintained, and adjacent piers should bear at the same elevation. The capacity of individual piers must be reduced when considering the effects of group action. Capacity reduction is a function of pier spacing and the number of piers within a group. If group action analyses are necessary, capacity reduction factors can be provided for the analyses. To satisfy forces in the horizontal direction using L-pile, piers may be designed for the following lateral load criteria: Parameter Clay Sand Bedrock Unit weight (pci) 0.0694 0.0723 0.0752 Average undrained shear strength (psf) 2,500 N/A 8,000 Average angle of internal friction,  (degrees) N/A 30 N/A Coefficient of subgrade reaction, k (pci)* 100- static 40 - cyclic 90 (above water) 60 (submerged) 2,000- static 800 – cyclic Strain, 50 (%) 0.007 N/A 0.004 4.3.4 Construction Considerations – Drilled Piers Drilling to design depth should be possible with conventional single-flight power augers. However, very moist to wet clays and sands encountered in our borings on the site will require temporary steel casing to properly drill the piers prior to concrete placement. Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 13 Groundwater should be removed from each pier hole prior to concrete placement. Pier concrete should be placed immediately after completion of drilling and cleaning. If pier concrete cannot be placed in dry conditions, a tremie should be used for concrete placement. The use of a bottom-dump hopper, or an elephant's trunk discharging near the bottom of the hole where concrete segregation will be minimized, is recommended. Due to potential sloughing and raveling, foundation concrete quantities may exceed calculated geometric volumes. Casing should be withdrawn in a slow continuous manner maintaining a sufficient head of concrete to prevent infiltration of water or caving soils or the creation of voids in pier concrete. Pier concrete should have a relatively high fluidity when placed in cased pier holes or through a tremie. Pier concrete with slump in the range of 5 to 7 inches is recommended. We recommend the sides of each pier should be mechanically roughened in the claystone bearing strata. This should be accomplished by a roughening tooth placed on the auger. Shaft bearing surfaces must be cleaned prior to concrete placement. A representative of the geotechnical engineer should observe the bearing surface and shaft configuration of every drilled pier. Free-fall concrete placement in piers will only be acceptable if provisions are taken to avoid striking the concrete on the sides of the hole or reinforcing steel. The use of a bottom-dump hopper, or an elephant's trunk discharging near the bottom of the hole where concrete segregation will be minimized, is recommended. Pier-bearing surfaces must be cleaned prior to concrete placement. A representative of Terracon should observe the bearing surface and pier configuration. 4.4 Seismic Considerations Code Used Site Classification 2009 International Building Code (IBC) 1 C 2 1. In general accordance with the 2009 International Building Code, Table 1613.5.2. 2. The 2009 International Building Code (IBC) requires a site soil profile determination extending a depth of 100 feet for seismic site classification. The current scope requested does not include the required 100 foot soil profile determination. The borings performed at this site extended to a maximum depth of about 45 feet and this seismic site class definition considers that similar soil and bedrock conditions exist below the maximum depth of the subsurface exploration. Additional exploration to deeper depths could be performed to confirm the conditions below the current depth of exploration. Alternatively, a geophysical exploration could be utilized in order to attempt to justify a higher seismic site class; however, we believe this is unlikely. Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 14 4.5 Interior Floor Systems Considering the low swelling soils encountered in our borings on this site, we believe a slab-on- grade floor system can be used for the proposed buildings provided some movement can be tolerated. If very little movement can be tolerated, structural floors, supported independent of the subgrade materials, are recommended. Subgrade soils beneath interior and exterior slabs and beneath pavements should be scarified, moisture conditioned and compacted to a minimum depth of 8 inches. The moisture content and compaction of subgrade soils should be maintained until slab or pavement construction. 4.5.1 Design Recommendations – Slabs-on-Grade Even when bearing on properly prepared soils, movement of the slab-on-grade floor system is possible should the subgrade soils undergo an increase in moisture content. We estimate movement of about 1 inch or less is possible. If the owner cannot accept the risk of slab movement, a structural floor should be used. If conventional slab-on-grade is utilized, the subgrade soils should be prepared as outlined in the 4.2 Earthwork section of this report. For structural design of concrete slabs-on-grade, a modulus of subgrade reaction of 100 pounds per cubic inch (pci) may be used for floors supported on existing or compacted soils at the site. Additional floor slab design and construction recommendations are as follows:  Positive separations and/or isolation joints should be provided between slabs and all foundations, columns or utility lines to allow independent movement.  Control joints should be provided in slabs to control the location and extent of cracking.  A minimum 2-inch void space should be constructed above or below non-bearing partition walls (if any) placed on the floor slab. Special framing details should be provided at doorjambs and frames within partition walls to avoid potential distortion. Partition walls should be isolated from suspended ceilings.  Interior trench backfill placed beneath slabs should be compacted in accordance with recommended specifications outlined below.  The use of a vapor retarder should be considered beneath concrete slabs on grade that will be covered with wood, tile, carpet or other moisture sensitive or impervious coverings, or when the slab will support equipment sensitive to moisture. When conditions warrant the use of a vapor retarder, the slab designer and slab contractor should refer to ACI 302 for procedures and cautions regarding the use and placement of a vapor retarder. Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 15  Floor slabs should not be constructed on frozen subgrade.  Other design and construction considerations, as outlined in Section 302.1R of the ACI Design Manual, are recommended. 4.5.1 Construction Considerations – Slabs-on-Grade Movements of slab-on-grades using the above outlined alternatives will likely be reduced and tend to be more uniform. The estimates outlined above assume that the other recommendations in this report are followed. Additional movement could occur should the subsurface soils become wetted to significant depths, which could result in potential excessive movement causing uneven floor slabs and severe cracking. This could be due to over watering of landscaping, poor drainage, improperly functioning drain systems, and/or broken utility lines. Therefore, it is imperative that the recommendations outlined in the 4.2.6 Grading and Drainage section of this report be followed. 4.6 Below-grade Construction We understand the proposed student housing and clubhouse buildings will not have basements. The proposed parking garage may extend ½ to 1 level below grade which may results in about 10 feet of the parking garage constructed below grade. Groundwater was encountered at depths of about 10 to 25 feet below existing site grade in the test borings at the time of field exploration. Terracon recommends providing at least 3 feet of separation between the bottom of the parking garage lower level and measured groundwater levels. If the project team desires to extend the parking garage closer to groundwater below this site, a permanent dewatering system will be necessary. Terracon should be contacted if more detailed plans for the parking garage result in below-grade construction encroaching on groundwater below this site. To help control the water level behind below-grade walls for the proposed parking garage, installation of a perimeter drainage system is recommended. The drainage system should be constructed around the exterior perimeter of the parking garage foundation and sloped at a minimum 1/8 inch per foot to a suitable outlet(s), such as a sump(s) and pump system(s). Considering the large footprint anticipated for the proposed parking garage, lateral drains and multiple collection systems may be necessary. The drainage system should consist of a minimum 4-inch diameter perforated or slotted pipe, embedded in free-draining gravel, placed in a trench at least 12 inches in width. The edge of the trench should be sloped at a 1:1 slope beginning at the bottom outside edge of the grade beams between drilled piers. The trench should not be cut vertically at the edge of the foundation to avoid undermining the parking garage floor slab. Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 16 The drainage system should consist of a properly sized, perforated pipe that is embedded in free-draining gravel and placed in a trench at least 12 inches in width. Gravel should extend a minimum of 3 inches beneath the bottom of the pipe and at least 2 feet above the bottom of the foundation wall. The system should be underlain with a polyethylene moisture barrier that is sealed to the foundation walls and extended to at least the edge of the backfill zone. The gravel should be covered with drainage fabric prior to placement of foundation backfill. 4.7 Lateral Earth Pressures Reinforced concrete walls with unbalanced backfill levels on opposite sides should be designed for earth pressures at least equal to those indicated in the following table. Earth pressures will be influenced by structural design of the walls, conditions of wall restraint, methods of construction and/or compaction and the strength of the materials being restrained. Two wall restraint conditions are shown. The "at-rest" condition assumes no wall movement. The recommended design lateral earth pressures do not include a factor of safety and do not provide for possible hydrostatic pressure on the walls. EARTH PRESSURE COEFFICIENTS Earth Pressure Conditions Coefficient For Backfill Type Equivalent Fluid Density (pcf) Surcharge Pressure, p1 (psf) Earth Pressure, p2 (psf) At-Rest (Ko) Granular - 0.50 Lean Clay - 0.64 60 75 (0.50)S (0.64)S (60)H (75)H Passive (Kp) Granular - 3.0 Lean Clay - 2.1 360 250 --- --- --- --- Foundation Wall Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 17 Applicable conditions to the above include:  For passive earth pressure to develop, wall must move horizontally to mobilize resistance.  Uniform surcharge, where S is surcharge pressure  In-situ soil backfill weight a maximum of 120 pcf  Horizontal backfill, compacted to at least 95 percent of maximum dry unit weight as determined by ASTM D 698  Loading from heavy compaction equipment not included  No hydrostatic pressures acting on wall  No dynamic loading  No safety factor included in soil parameters  Ignore passive pressure in frost zone 4.8 Pavement Design and Construction Design of privately maintained pavements for the project has been based on the procedures outlined by the Asphalt Institute (AI) and the American Concrete Institute (ACI). If improvements to public roadways are anticipated, a pavement design report meeting the City of Fort Collins specifications (Larimer County Urban Area Street Standards) will need to be prepared for submittal, subsequent to final grading. We assumed the following design parameters for Asphalt Institute flexible pavement thickness design:  Automobile Parking Areas  Parking stalls and parking lots for cars and pick-up trucks, up to 200 stalls  Main Traffic Corridors  Parking lots with a maximum of 25 trucks per day  Subgrade Soil Characteristics  USCS Classification – CL (Poor Subgrade) We assumed the following design parameters for ACI rigid pavement thickness design based upon the average daily truck traffic (ADTT):  Automobile Parking Areas  ACI Category A-1: Automobile parking with an ADTT of 1 over 20 years  Main Traffic Corridors  ACI Category B: Commercial entrance and service lanes with an ADTT of 25 over 20 years  Subgrade Soil Characteristics  USCS Classification – CL  Concrete modulus of rupture value of 600 psi Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 18 Traffic patterns and anticipated loading conditions for the site pavements were not available at the time of this study. We should be contacted to confirm and/or modify the recommendations contained herein if actual traffic volumes differ from the assumed values shown above. In our opinion, a full depth asphalt concrete section over a prepared clay subgrade should not be used on this site. Recommended alternatives for flexible and rigid pavements are summarized for each traffic area as follows: Traffic Area Alternative Recommended Pavement Thickness (Inches) Asphalt Concrete Surface Aggregate Base Course Portland Cement Concrete Total Automobile Parking (AI Class I and ACI Category A) A 4 6 10 B 6 6 Main Traffic Corridors (AI Class III and ACI Category B) A 5 6 11 B 6 6 The placement of a partial pavement thickness for use during construction is not suggested without a detailed pavement analysis incorporating construction traffic. In addition, we should be contacted to confirm the traffic assumptions outlined above. If the actual traffic varies from the assumptions outlined above, modification of the pavement section thickness will be required. For areas subject to concentrated and repetitive loading conditions such as dumpster pads, truck delivery docks and ingress/egress aprons, we recommend using a Portland cement concrete pavement with a thickness of at least 7 inches underlain by at least 4 inches of crushed stone. Prior to placement of the crushed stone, the areas should be thoroughly proof- rolled. For dumpster pads, the concrete pavement area should be large enough to support the container and tipping axle of the refuse truck. For analysis of pavement costs, the following specifications should be considered for each pavement component: Colorado Department of Pavement Component Transportation Criteria Asphalt Concrete Surface ......................................................................... Grading S or SX Aggregate Base Course ................................................................................... Class 5 or 6 Portland Cement Concrete ...................................................................................... Class P Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 19 4.8.1 Drainage Adjacent to Pavements The clay soils will likely lose stability with increases in moisture content. Therefore, to reduce pavement distress due to wetting of the subgrade in areas of water intensive landscaping or other nearby water sources (or if aggregate base course is used) located adjacent to pavements, we recommend shoulder drains be considered. The drain system should consist of a properly sized pipe embedded in free-draining material directed to a suitable outfall such as an underdrain or storm sewer. 4.8.2 Compliance Recommendations for pavement design and construction presented depend upon compliance with recommended material specifications. To assess compliance, observation and testing should be performed under the observation of the geotechnical engineer. 4.8.3 Pavement Performance The performance of all pavements can be enhanced by minimizing excess moisture which can reach the subgrade soils. Future performance of pavements at this site will be dependent upon several factors, including:  Maintaining stable moisture content of the subgrade soils both before and after pavement construction; and  Providing for a planned program of preventative maintenance. Since the clay soils on the site have shrink/swell characteristics, pavements could crack in the future primarily because of expansion of the soils and bedrock when subjected to an increase in moisture content to the subgrade. The cracking, while not desirable, does not necessarily constitute structural failure of the pavement, provided that timely maintenance, such as crack sealing is performed. Excessive movement and cracking could result if the subgrade soils are allowed to dry out before paving and subsequently become rewetted. The performance of all pavements can be enhanced by minimizing excess moisture, which can reach the subgrade soils. The following recommendations should be considered at minimum:  Site grading at a minimum 2 percent grade onto or away from the pavements;  Water should not be allowed to pond behind curbs;  Compaction of any utility trenches for landscaped areas to the same criteria as the pavement subgrade;  Sealing all landscaped areas in or adjacent to pavements to minimize or prevent moisture migration to subgrade soils;  Placing compacted backfill against the exterior side of curb and gutter; and  Placing shoulder or edge drains in pavement areas adjacent to water sources. Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 20 Preventative maintenance should be planned and provided for an ongoing pavement management program in order to enhance future pavement performance. Preventative maintenance activities are intended to slow the rate of pavement deterioration and to preserve the pavement investment. Preventative maintenance consists of both localized maintenance (e.g. crack sealing and patching) and global maintenance (e.g. surface sealing). Preventative maintenance is usually the first priority when implementing a planned pavement maintenance program and provides the highest return on investment for pavements. 4.8.4 Construction Considerations Site grading is generally accomplished early in the construction phase. However, as construction proceeds, the subgrade may be disturbed due to utility excavations, construction traffic, desiccation, or rainfall. As a result, the pavement subgrade may not be suitable for pavement construction and corrective action will be required. The subgrade should be carefully evaluated at the time of pavement construction for signs of disturbance or excessive rutting. If disturbance has occurred, pavement subgrade areas should be reworked, moisture conditioned, and properly compacted to the recommendations in this report immediately prior to paving. We recommend the pavement areas be rough graded and then thoroughly proof-rolled with a loaded tandem axle dump truck prior to final grading and paving. Particular attention should be paid to high traffic areas that were rutted and disturbed earlier and to areas where backfilled trenches are located. Areas where unsuitable conditions are located should be repaired by removing and replacing the materials with properly compacted fills. All pavement areas should be moisture conditioned and properly compacted to the recommendations in this report immediately prior to paving. The placement of a partial pavement thickness for use during construction is not recommended without a detailed pavement analysis incorporating construction traffic. In addition, if the actual traffic varies from the assumptions outlined above, we should be contacted to confirm and/or modify the pavement thickness recommendations outlined above. . 5.0 GENERAL COMMENTS Terracon should be retained to review the final design plans and specifications so comments can be made regarding interpretation and implementation of our geotechnical recommendations in the design and specifications. Terracon should also be retained to provide testing and observation during site grading, excavation, fill placement, as well as foundation and construction phases of the project. The analysis and recommendations presented in this report are based upon the data obtained from the borings performed at the indicated locations and from other information discussed in Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Responsive ■ Resourceful ■ Reliable 21 this report. This report does not reflect variations that may occur between borings, across the site, or due to the modifying effects of weather. The nature and extent of such variations may not become evident until during or after construction. If variations appear, we should be immediately notified so that further evaluation and supplemental recommendations can be provided. The scope of services for this project does not include, either specifically or by implication, any environmental or biological (e.g., mold, fungi, bacteria) assessment of the site or identification or prevention of pollutants, hazardous materials or conditions. If the owner is concerned about the potential for such contamination or pollution, other studies should be undertaken. This report has been prepared for the exclusive use of our client for specific application to the project discussed and has been prepared in accordance with generally accepted geotechnical engineering practices. No warranties, either express or implied, are intended or made. Site safety, excavation support, and dewatering requirements are the responsibility of others. In the event that changes are planned in the nature, design, or location of the project as outlined in this report, the conclusions and recommendations contained in this report shall not be considered valid unless Terracon reviews the changes, and either verifies or modifies the conclusions of this report in writing. APPENDIX A FIELD EXPLORATION Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Exhibit A-1 Field Exploration Description The location of borings was based upon the proposed development shown on the provided site plan. The borings were located in the field by Terracon personnel measuring from property lines and existing site features. Test boring surface elevations were within approximately 2 feet of adjacent street grades. Boring Nos. 1 through 7 were drilled on August 8, 2008 with a CME-55 truck-mounted drill rig with solid-stem augers. Boring Nos. 8 and 11 were drilled on September 22, 2011 with a limited access mini rig with solid-stem augers. Boring Nos. 9 and 10 were drilled on September 28, 2011 with a CME-55 truck-mounted drill rig with solid-stem augers. During the drilling operations, lithologic logs of the borings were recorded by the field engineer. Relatively undisturbed samples were obtained at selected intervals utilizing a 2-inch outside diameter split- spoon sampler (RS) and a 3-inch outside diameter ring-barrel sampler (RS). Penetration resistance values were recorded in a manner similar to the standard penetration test (SPT). This test consists of driving the sampler into the ground with a 140-pound hammer free-falling through a distance of 30 inches. The number of blows required to advance the ring-barrel sampler 12 inches (18-inches for standard split-spoon samplers, final 12-inches are recorded) or the interval indicated, is recorded and can be correlated to the standard penetration resistance value (N-value). The blow count values are indicated on the boring logs at the respective sample depths, ring-barrel sample blow counts are not considered N-values. A CME automatic SPT hammer was used to advance the samplers in the Boring Nos. 1 through 7, 9 and 10 performed on this site. A manual safety hammer was used to advance the samplers in Boring No. 8 and 11. A greater efficiency is typically achieved with the automatic hammer compared to the conventional safety hammer operated with a cathead and rope. Published correlations between the SPT values and soil properties are based on the lower efficiency cathead and rope method. This higher efficiency affects the standard penetration resistance blow count value by increasing the penetration per hammer blow over what would be obtained using the cathead and rope method. The effect of the automatic hammer's efficiency has been considered in the interpretation and analysis of the subsurface information for this report. The standard penetration test provides a reasonable indication of the in-place density of sandy type materials, but only provides an indication of the relative stiffness of cohesive materials since the blow count in these soils may be affected by the soils moisture content. In addition, considerable care should be exercised in interpreting the N-values in gravelly soils, particularly where the size of the gravel particle exceeds the inside diameter of the sampler. Groundwater measurements were obtained in the borings at the time of site exploration and several days after drilling. After subsequent groundwater measurements were obtained, the borings were backfilled with auger cuttings. Some settlement of the backfill may occur and should be repaired as soon as possible. 0’ 50’ 100’ LEGEND APPROXIMATE SCALE Scale: 301 North Howes Street Fort Collins, Colorado 80521 PH. (970) 484-0359 FAX. (970) 484-0454 EDB EDB EDB DJJ Project Manager: Drawn by: Checked by: Approved by: BORING LOCATION DIAGRAM THE DISTRICT AT CSU West Plum Street and City Park Avenue Fort Collins, Colorado A-2 20115026 Exhibit 10/28/2011 1=100’ Project No. File Name: Date: DIAGRAM IS FOR GENERAL LOCATION ONLY, AND IS NOT INTENDED FOR CONSTRUCTION PURPOSES 1 Approximate Boring Location for Previous Study (Terracon Project No. 20085059; report dated 8/21/08) 8 Approximate Boring Location for Current Study (Terracon Project No. 20115026) 8 9 10 11 7 6 5 4 2 3 1 RS 111 SS 116 RS RS RS SS RS 50/0.5 11 12 12 12 12 12 12 115 50/0.3 112 50 45 14 15 14 CL CL CL 12 2.3% 500psf 30 15 0.5 BOTTOM OF BORING 7 6 5 4 3 2 1 CLAYSTONE Firm to hard, brown, gray SANDY LEAN CLAY Stiff to very stiff, reddish brown TOPSOIL 12 The stratification lines represent the approximate boundary lines Proposed Student Housing Project CME55 8-8-08 18 BOREHOLE_99 20085059.GPJ BORING.GDT 8/22/08 15.5 % SWELL SURCHARGE JOB # CLIENT 9 PROJECT CL 127 124 118 102 25 RS RS RS RS 9 RIG FOREMAN PG BORING STARTED 11 CL 12 18 4 12 12 12 50/0.4 3 30 13 20 0.2% 500psf 17 13 0.5 SANDY LEAN CLAY Stiff to very stiff, reddish brown WATER LEVEL OBSERVATIONS, ft 2 1 BOTTOM OF BORING CLAYEY SAND Medium dense, brown 4 TOPSOIL CLAYSTONE Hard, brown, gray JOB # UNCONFINED STRENGTH, psf The stratification lines represent the approximate boundary lines Proposed Student Housing Project CME55 8-8-08 PROJECT 16.7 5 10 15 20 BLOWS / ft. WATER CONTENT, % USCS SYMBOL SAMPLES BOREHOLE_99 20085059.GPJ BORING.GDT 8/22/08 % SWELL SURCHARGE SS SS RS SS RS RS 11 6 5 4 3 2 16 12 12 12 12 50/0.9 50 24 21 SM CL CL 130 118 111 50/0.5 30 1 1.9% 500psf 16.5 13 5 0.5 12 BOTTOM OF BORING CLAYSTONE Firm to hard, brown, gray SILTY SAND WITH GRAVEL Medium dense, brown SANDY LEAN CLAY Stiff, reddish brown FILL, SANDY LEAN CLAY Very stiff, brown TOPSOIL The stratification lines represent the approximate boundary lines Proposed Student Housing Project CME55 8-8-08 UNCONFINED STRENGTH, psf Dry % SWELL SURCHARGE JOB # CLIENT 12 13 PROJECT 5 14 CL CL 117 25 113 108 RS 50/0.5 RS RS RS 114 15 12.5 RIG FOREMAN 23 BORING STARTED 17 17 14 6 12 12 12 PG 0.5% 500psf 0.7% 500psf 20 13 0.5 CLAYSTONE Weathered to hard, brown, gray TESTS 4 3 2 1 BOTTOM OF BORING SANDY LEAN CLAY Stiff to very stiff, brown GRAVEL PAVING CME55 BOREHOLE_99 20085059.GPJ BORING.GDT 8/22/08 UNCONFINED STRENGTH, psf The stratification lines represent the approximate boundary lines 8-8-08 TYPE 8-8-08 PROJECT WATER LEVEL OBSERVATIONS, ft Proposed Student Housing Project 5 10 15 20 BLOWS / ft. WATER CONTENT, % SS CL CL 120 119 21 SS RS RS 11 RIG FOREMAN PG BORING STARTED 13 SM 13 33 6 12 12 12 50/0.5 28 2 13 20 4 0.4% 500psf 18 13 0.5 TOPSOIL WATER LEVEL OBSERVATIONS, ft 1 BOTTOM OF BORING CLAYSTONE Hard, brown, gray SANDY LEAN CLAY Very stiff, reddish brown, calcareous 3 SILTY SAND WITH GRAVEL Medium dense, brown, fine to medium grained JOB # UNCONFINED STRENGTH, psf The stratification lines represent the approximate boundary lines Proposed Student Housing Project CME55 8-8-08 PROJECT 14.6 5 10 15 20 BLOWS / ft. WATER CONTENT, % USCS SYMBOL SAMPLES BOREHOLE_99 20085059.GPJ BORING.GDT 8/22/08 % SWELL CL 123 127 113 103 SC 18 RS RS RS RS WATER LEVEL OBSERVATIONS, ft 9 FOREMAN PG BORING STARTED 13 SC 7 4 6 12 12 12 50/0.5 42 54 9 20 0.2% 500psf 17 9 0.5 FILL, SANDY LEAN CLAY WITH GRAVEL Stiff, reddish brown 3 2 1 BOTTOM OF BORING CLAYEY SAND WITH GRAVEL Medium dense, brown, fine to medium grained GRAVEL PAVING CLAYSTONE Hard, brown, gray JOB # UNCONFINED STRENGTH, psf The stratification lines represent the approximate boundary lines Proposed Student Housing Project CME55 8-8-08 PROJECT RIG 15.0 5 10 15 20 BLOWS / ft. WATER CONTENT, % SC SC 122 124 110 33 25 RS RS SS RS RS 9 FOREMAN PG BORING STARTED 11 12 11 11 6 12 12 12 12 50/0.5 41 16 30 14 0.5 0.1% 500psf BOTTOM OF BORING 5 4 3 2 1 CLAYSTONE Firm to hard, brown, gray CLAYEY SAND Loose to medium dense, brown, fine to medium grained, trace gravel GRAVEL PAVING WATER LEVEL OBSERVATIONS, ft UNCONFINED STRENGTH, psf The stratification lines represent the approximate boundary lines Proposed Student Housing Project CME55 8-8-08 PROJECT Dry RIG % SWELL SURCHARGE 5 10 15 20 25 0.5 3.5 17.5 18.5 29.5 TOPSOIL - 6 inches FILL lean clay with sand, stiff, moist, reddish brown SANDY LEAN CLAY medium stiff to very stiff, slightly moist, reddish brown very moist at 8.5 feet SILTY SAND with GRAVEL dense, wet, brown, reddish brown CLAYSTONE BEDROCK hard to very hard, slightly moist, olive, brown, gray BOTTOM OF BORING -200 = 73 LL = 50 PI = 21 -200 = 55 1 2 3 4 5 6 RS RS RS RS RS SS CL CL 17 26 8 17 50/6 50/6 15 9 19 21 15 18 92 114 108 107 BORING STARTED 9-22-11 10 WD AD SITE CLIENT WL WL APPROVED 0.5 13 14.5 29.4 TOPSOIL - 6 inches SANDY LEAN CLAY medium stiff to stiff, moist, brown, dark brown varying amounts of gravel SILTY SAND with GRAVEL dense, wet, brown, reddish brown CLAYSTONE BEDROCK weathered to very hard, slightly moist, light brown, brown BOTTOM OF BORING -200 = 61 LL = 36 PI = 18 1 2 3 4 5 6 7 RS RS RS RS RS RS SS CL 15 8 25 30 45 50/3 50/5 11 9 15 18 13 9 10 105 107 119 112 122 BORING STARTED 9-28-11 None WD AD SITE CLIENT WL WL APPROVED The stratification lines represent the approximate boundary lines Page 1 of 1 0.5 14 44.1 TOPSOIL - 6 inches SANDY LEAN CLAY stiff to very stiff, moist, brown, dark brown CLAYSTONE BEDROCK medium hard to very hard, moist, black, gray Auger refusal at 45 feet. BOTTOM OF BORING -200 = 59 -200 = 99 LL = 54 PI = 34 1 2 3 4 5 6 7 8 9 10 RS RS RS RS RS RS SS SS SS SS CL CH 34 30 12 11 48 88 87 50/6 50/5 50/1 11 8 14 17 17 14 15 13 14 13 105 108 116 0.2 12 13 24.8 TOPSOIL - 3 inches SANDY LEAN CLAY very stiff to hard, slightly moist, dark brown, reddish brown Gravel interlayered with clayey sand SILTY SAND with GRAVEL dense, wet, brown, reddish brown CLAYSTONE BEDROCK hard to very hard, brown, olive, rust BOTTOM OF BORING 1 2 3 4 5 6 RS RS RS RS SS SS 26 50 43 19 85/15 50/9 13 14 13 21 19 20 97 111 116 106 BORING STARTED 9-22-11 12 WD AD SITE CLIENT WL WL APPROVED The stratification lines represent the approximate boundary lines Page 1 of 1 UNCONFINED STRENGTH, psf TESTS 9-22-11 DESCRIPTION Exhibit A-13 WATER LEVEL OBSERVATIONS, ft Ft. Collins Student Housing, LLC 20115026 APPENDIX B LABORATORY TESTING Geotechnical Engineering Report The District at CSU ■ Fort Collins, Colorado November 2, 2011 ■ Terracon Project No. 20115026 Exhibit B-1 Laboratory Testing Samples retrieved during the field exploration were returned to the laboratory for observation by the project geotechnical engineer, and were classified in general accordance with the Unified Soil Classification System described in Appendix C. Samples of bedrock were classified in accordance with the general notes for Rock Classification. At this time, an applicable laboratory-testing program was formulated to determine engineering properties of the subsurface materials. Following the completion of the laboratory testing, the field descriptions were confirmed or modified as necessary, and Logs of Borings were prepared. These logs are presented in Appendix A. Laboratory test results for our previous study conducted at this site as well as for the current study are presented in Appendix B. These results were used for the geotechnical engineering analyses and the development of foundation and earthwork recommendations. All laboratory tests were performed in general accordance with the applicable local or other accepted standards. Selected soil and bedrock samples were tested for the following engineering properties:  Water content  Dry density  Expansion/Consolidation  Grain-size distribution  Atterberg limits  Water-soluble sulfate content 2 4 5 7 SANDY LEAN CLAY(CL) LEAN CLAY with SAND(CL) SANDY LEAN CLAY(CL) 68 70 68 46 CLAYEY SAND(SC) 100 50 40 30 20 10 0 20 40 80 60 0 60 9.0ft 17 15 15 16 22 18 15 11 LL PL Job #: 20085059 Site: West of Int. of Plum St. and S. Shields Fort Collins, Colorado Project: Proposed Student Housing Project %Fines Classification ATTERBERG LIMITS RESULTS 4.0ft 4.0ft 4.0ft 33 27 Specimen Identification CL PI MH TC_ATTERBERG_LIMITS 20085059.GPJ BORING.GDT 8/22/08 39 LIQUID LIMIT CL-ML ML 30 CH P L A S T I C I T Y I 0 10 20 30 40 50 60 0 20 40 60 80 100 Specimen Identification ML CL MH CH CL-ML P L A S T I C I T Y I N D E X 2.0ft 2.0ft 19.0ft LIQUID LIMIT 8 9 10 50 36 54 29 18 20 21 18 34 LL PL %Fines ATTERBERG LIMITS RESULTS SANDY CLAY FILL WITH GRAVEL (CL) SANDY LEAN CLAY(CL) CLAYSTONE BEDROCK 73 61 99 PI Classification Project: The District at CSU Proj. No. 20115026 Site: West Plum Street and City Park Avenue, Fort Collins, Colorado TC_ATTERBERG_LIMITS 20115026.GPJ DENVER 031610.GDT 11/1/11 -2 100 1,000 Notes: 1 5.0ft SANDY LEAN CLAY 111 11 4 0 -4 -6 -8 -10 2 TC_CONSOL_STRAIN 20085059.GPJ BORING.GDT 8/22/08 SWELL CONSOLIDATION TEST PRESSURE, psf AXIAL STRAIN, % Project: Proposed Student Housing Project Site: West of Int. of Plum St. and S. Shields Fort Collins, Colorado 10,000 Specimen Identification Classification , pcf WC,% Job #: 20085059 -2 100 1,000 Notes: 2 4.0ft SANDY LEAN CLAY 102 9 4 0 -4 -6 -8 -10 2 TC_CONSOL_STRAIN 20085059.GPJ BORING.GDT 8/22/08 SWELL CONSOLIDATION TEST PRESSURE, psf AXIAL STRAIN, % Project: Proposed Student Housing Project Site: West of Int. of Plum St. and S. Shields Fort Collins, Colorado 10,000 Specimen Identification Classification , pcf WC,% Job #: 20085059 -2 100 1,000 Notes: 3 9.0ft SANDY LEAN CLAY 118 13 4 0 -4 -6 -8 -10 2 TC_CONSOL_STRAIN 20085059.GPJ BORING.GDT 8/22/08 SWELL CONSOLIDATION TEST PRESSURE, psf AXIAL STRAIN, % Project: Proposed Student Housing Project Site: West of Int. of Plum St. and S. Shields Fort Collins, Colorado 10,000 Specimen Identification Classification , pcf WC,% Job #: 20085059 -2 100 1,000 Notes: 4 4.0ft LEAN CLAY with SAND(CL) 108 14 4 0 -4 -6 -8 -10 2 TC_CONSOL_STRAIN 20085059.GPJ BORING.GDT 8/22/08 SWELL CONSOLIDATION TEST PRESSURE, psf AXIAL STRAIN, % Project: Proposed Student Housing Project Site: West of Int. of Plum St. and S. Shields Fort Collins, Colorado 10,000 Specimen Identification Classification , pcf WC,% Job #: 20085059 -2 100 1,000 Notes: 4 9.0ft SANDY LEAN CLAY 114 17 4 0 -4 -6 -8 -10 2 TC_CONSOL_STRAIN 20085059.GPJ BORING.GDT 8/22/08 SWELL CONSOLIDATION TEST PRESSURE, psf AXIAL STRAIN, % Project: Proposed Student Housing Project Site: West of Int. of Plum St. and S. Shields Fort Collins, Colorado 10,000 Specimen Identification Classification , pcf WC,% Job #: 20085059 -2 100 1,000 Notes: 5 4.0ft SANDY LEAN CLAY(CL) 119 11 4 0 -4 -6 -8 -10 2 TC_CONSOL_STRAIN 20085059.GPJ BORING.GDT 8/22/08 SWELL CONSOLIDATION TEST PRESSURE, psf AXIAL STRAIN, % Project: Proposed Student Housing Project Site: West of Int. of Plum St. and S. Shields Fort Collins, Colorado 10,000 Specimen Identification Classification , pcf WC,% Job #: 20085059 -2 100 1,000 Notes: 6 4.0ft SANDY LEAN CLAY WITH GRAVEL 103 9 4 0 -4 -6 -8 -10 2 TC_CONSOL_STRAIN 20085059.GPJ BORING.GDT 8/22/08 SWELL CONSOLIDATION TEST PRESSURE, psf AXIAL STRAIN, % Project: Proposed Student Housing Project Site: West of Int. of Plum St. and S. Shields Fort Collins, Colorado 10,000 Specimen Identification Classification , pcf WC,% Job #: 20085059 -2 100 1,000 Notes: 7 4.0ft CLAYEY SAND(SC) 110 9 4 0 -4 -6 -8 -10 2 TC_CONSOL_STRAIN 20085059.GPJ BORING.GDT 8/22/08 SWELL CONSOLIDATION TEST PRESSURE, psf AXIAL STRAIN, % Project: Proposed Student Housing Project Site: West of Int. of Plum St. and S. Shields Fort Collins, Colorado 10,000 Specimen Identification Classification , pcf WC,% Job #: 20085059 -10 -8 -6 -4 -2 0 2 4 100 1,000 10,000 AXIAL STRAIN, % PRESSURE, psf SWELL CONSOLIDATION TEST Exhibit B-12 Project: The District at CSU Proj. No. 20115026 Site: West Plum Street and City Park Avenue, Fort Collins, Colorado , pcf WC,% 107 9 SpecimenClassification Identification 9 4.0 ft SANDY LEAN CLAY (CL) Notes: Water added at 1,000 psf. TC_CONSOL_STRAIN 20115026.GPJ DENVER 031610.GDT 11/1/11 -10 -8 -6 -4 -2 0 2 4 100 1,000 10,000 AXIAL STRAIN, % PRESSURE, psf SWELL CONSOLIDATION TEST Exhibit B-13 Project: The District at CSU Proj. No. 20115026 Site: West Plum Street and City Park Avenue, Fort Collins, Colorado , pcf WC,% 115 17 SpecimenClassification Identification 10 19.0 ft CLAYSTONE BEDROCK Notes: Water added at 1,000 psf. TC_CONSOL_STRAIN 20115026.GPJ DENVER 031610.GDT 11/1/11 -10 -8 -6 -4 -2 0 2 4 100 1,000 10,000 AXIAL STRAIN, % PRESSURE, psf SWELL CONSOLIDATION TEST Exhibit B-14 Project: The District at CSU Proj. No. 20115026 Site: West Plum Street and City Park Avenue, Fort Collins, Colorado , pcf WC,% 120 14 SpecimenClassification Identification 10 24.0 ft CLAYSTONE BEDROCK Notes: Water added at 1,000 psf. TC_CONSOL_STRAIN 20115026.GPJ DENVER 031610.GDT 11/1/11 -10 -8 -6 -4 -2 0 2 4 100 1,000 10,000 AXIAL STRAIN, % PRESSURE, psf SWELL CONSOLIDATION TEST Exhibit B-15 Project: The District at CSU Proj. No. 20115026 Site: West Plum Street and City Park Avenue, Fort Collins, Colorado , pcf WC,% 97 13 SpecimenClassification Identification 11 2.0 ft SANDY LEAN CLAY (CL) Notes: Water added at 200 psf. TC_CONSOL_STRAIN 20115026.GPJ DENVER 031610.GDT 11/1/11 -10 -8 -6 -4 -2 0 2 4 100 1,000 10,000 AXIAL STRAIN, % PRESSURE, psf SWELL CONSOLIDATION TEST Exhibit B-16 Project: The District at CSU Proj. No. 20115026 Site: West Plum Street and City Park Avenue, Fort Collins, Colorado , pcf WC,% 111 14 SpecimenClassification Identification 11 4.0 ft SANDY LEAN CLAY (CL) Notes: Water added at 500 psf. TC_CONSOL_STRAIN 20115026.GPJ DENVER 031610.GDT 11/1/11 -10 -8 -6 -4 -2 0 2 4 100 1,000 10,000 AXIAL STRAIN, % PRESSURE, psf SWELL CONSOLIDATION TEST Exhibit B-17 Project: The District at CSU Proj. No. 20115026 Site: West Plum Street and City Park Avenue, Fort Collins, Colorado , pcf WC,% 116 13 SpecimenClassification Identification 11 9.0 ft SANDY LEAN CLAY (CL) Notes: Water added at 1,000 psf. TC_CONSOL_STRAIN 20115026.GPJ DENVER 031610.GDT 11/1/11 -10 -8 -6 -4 -2 0 2 4 100 1,000 10,000 AXIAL STRAIN, % PRESSURE, psf SWELL CONSOLIDATION TEST Exhibit B-18 Project: The District at CSU Proj. No. 20115026 Site: West Plum Street and City Park Avenue, Fort Collins, Colorado , pcf WC,% 106 21 SpecimenClassification Identification 11 14.0 ft CLAYSTONE BEDROCK Notes: Water added at 1,750 psf. TC_CONSOL_STRAIN 20115026.GPJ DENVER 031610.GDT 11/1/11 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 100 10 1 0.1 0.01 0.001 GRAIN SIZE DISTRIBUTION 26.2 73.0 8 9.5 50 60 100 coarse 1.5 GRAIN SIZE IN MILLIMETERS PERCENT FINER BY WEIGHT Classification coarse SAND SILT OR CLAY 200 LL PL D10 fine 6 1 6 3/4 1/2 3/8 PI Cc Cu 0.8 4 3 14 2 8 COBBLES GRAVEL 29 Specimen Identification D100 4 21 10 D30 16 20 30 40 U.S. SIEVE OPENING IN INCHES U.S. SIEVE NUMBERS SANDY CLAY FILL WITH GRAVEL (CL) fine Exhibit B-19 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 100 10 1 0.1 0.01 0.001 GRAIN SIZE DISTRIBUTION 32.5 61.3 9 19 50 60 100 coarse 1.5 GRAIN SIZE IN MILLIMETERS PERCENT FINER BY WEIGHT Classification coarse SAND SILT OR CLAY 200 LL PL D10 fine 6 1 6 3/4 1/2 3/8 PI Cc Cu 6.2 4 3 14 2 8 COBBLES GRAVEL 18 Specimen Identification D100 4 18 10 D30 16 20 30 40 U.S. SIEVE OPENING IN INCHES U.S. SIEVE NUMBERS SANDY LEAN CLAY(CL) fine Exhibit B-20 3 4 4.0 3 29.0 10.3 3 24.0 10.5 129.8 10.6 19.0 70 3 14.0 3.5 3 9.0 13.0 117.8 1.9/500 1 8.0 114.1 5 4.0 4 19.0 15.4 116.7 14.0 17.4 112.5 33 0.5/500 18 4 9.0 17.3 100 A-6 CL 14.3 108.2 0.7/500 4.0 4 11.9 1 29.0 14.5 1 24.0 14.9 14.0 17.5 112.3 111.0 115.0 4.0 1 9.0 1 5.0 10.8 111.2 2.3/500 0.5 8.8 1 CL 3 2 19.0 10.6 127.4 2 14.0 13.4 123.9 116.0 12.0 2 2 9.0 39 22 68 A-6 9.5 102.1 0.2/500 68 117.8 11.1 Water Soluble Sulfates (ppm) Plasticity Index USCS Class- ification Dry Unit Weight (pcf) Depth ft 8 2 CL A-7-6 (14) 92 15 100 99 97 91 73 50 21 4 8 4 CL 114 9 55 4,5 8 9 108 19 4 8 14 107 21 4 8 19 15 4 8 29 18 4 9 2 CL A-6 (8) 105 11 100 94 89 76 61 36 18 4 9 4 107 9 1.0 -0.4 3,4 9 9 119 15 4 9 14 112 18 4 9 19 122 13 4 9 24 9 4 9 29 10 4 10 2 105 11 4 10 4 108 8 <1 4 10 9 CL 116 14 59 4,5 10 14 116 17 4 10 19 CH A-7-6 (19) 115 17 1.0 +3.9 99 54 34 3,4,5 10 24 120 14 1.0 +3.2 3,4 10 29 15 4 10 34 13 4 Exhibit B-22 Initial Dry Density, Initial Water Content and Swell values obtained from undisturbed samples unless otherwise noted * = partially disturbed sample - = compression/settlement Notes: REMARKS: 1. Remolded compacted density (approximately between 95 to 100% of ASTM D698 maximum dry density near optimum) 2. Remolded compacted density (approximately between 95 to 100% of ASTM D1557 maximum dry density near optimum) 3. Submerged to approximate saturation 4. Density/water content determined from one-ring of a multi-ring sample 5. Minus #200 only 6. Moisture-Density Relations Test Method ASTM D698/AASHTO T99 7. Moisture-Density Relations Test Method ASTM D1557/AASHTO T180 8. Indicates composite sample Initial Dry Density (pcf) Initial Water Content (%) SUMMARY OF LABORATORY TEST RESULTS Terracon Project No. 20115026 The District at CSU, Fort Collins, Colorado A - STANDARD SUMMARY 20115026.GPJ DENVER 031610.GDT 11/1/11 AASHTO Class- ification USCS Soil DepthClassification Boring No. Swell #4 (%) Swell/Consolidation Surcharge (ksf) 3/4" #10 #40 Particle Size Distribution 10 39 14 4 10 44 13 4 11 2 97 13 0.2 +3.6 3,4 11 4 111 14 0.5 +1.1 3,4 11 9 116 13 1.0 +0.4 20 3,4 11 14 106 21 1.8 +0.3 3,4 11 19 19 4 11 24 20 4 Exhibit B-23 Initial Dry Density, Initial Water Content and Swell values obtained from undisturbed samples unless otherwise noted * = partially disturbed sample - = compression/settlement Notes: REMARKS: 1. Remolded compacted density (approximately between 95 to 100% of ASTM D698 maximum dry density near optimum) 2. Remolded compacted density (approximately between 95 to 100% of ASTM D1557 maximum dry density near optimum) 3. Submerged to approximate saturation 4. Density/water content determined from one-ring of a multi-ring sample 5. Minus #200 only 6. Moisture-Density Relations Test Method ASTM D698/AASHTO T99 7. Moisture-Density Relations Test Method ASTM D1557/AASHTO T180 8. Indicates composite sample Initial Dry Density (pcf) Initial Water Content (%) SUMMARY OF LABORATORY TEST RESULTS Terracon Project No. 20115026 The District at CSU, Fort Collins, Colorado A - STANDARD SUMMARY 20115026.GPJ DENVER 031610.GDT 11/1/11 AASHTO Class- ification USCS Soil DepthClassification Boring No. Swell #4 (%) Swell/Consolidation Surcharge (ksf) 3/4" #10 #40 Particle Size Distribution Percent Passing by Weight #200 Liquid Limit Plasticity Index Water Soluble Sulfates (mg/L) Remarks NV = no value NP = non-plastic APPENDIX C SUPPORTING DOCUMENTS GENERAL NOTES DRILLING & SAMPLING SYMBOLS: SS: Split Spoon - 1-3/8" I.D., 2" O.D., unless otherwise noted HS: Hollow Stem Auger ST: Thin-Walled Tube - 2" O.D., unless otherwise noted PA: Power Auger RS: Ring Sampler - 2.42" I.D., 3" O.D., unless otherwise noted HA: Hand Auger DB: Diamond Bit Coring - 4", N, B RB: Rock Bit BS: Bulk Sample or Auger Sample WB: Wash Boring or Mud Rotary The number of blows required to advance a standard 2-inch O.D. split-spoon sampler (SS) the last 12 inches of the total 18-inch penetration with a 140-pound hammer falling 30 inches is considered the “Standard Penetration” or “N-value”. For 3” O.D. ring samplers (RS) the penetration value is reported as the number of blows required to advance the sampler 12 inches using a 140- pound hammer falling 30 inches, reported as “blows per foot,” and is not considered equivalent to the “Standard Penetration” or “N-value”. WATER LEVEL MEASUREMENT SYMBOLS: WL: Water Level WS: While Sampling WCI: Wet Cave in WD: While Drilling DCI: Dry Cave in BCR: Before Casing Removal AB: After Boring ACR: After Casing Removal Water levels indicated on the boring logs are the levels measured in the borings at the times indicated. Groundwater levels at other times and other locations across the site could vary. In pervious soils, the indicated levels may reflect the location of groundwater. In low permeability soils, the accurate determination of groundwater levels may not be possible with only short- term observations. DESCRIPTIVE SOIL CLASSIFICATION: Soil classification is based on the Unified Classification System. Coarse Grained Soils have more than 50% of their dry weight retained on a #200 sieve; their principal descriptors are: boulders, cobbles, gravel or sand. Fine Grained Soils have less than 50% of their dry weight retained on a #200 sieve; they are principally described as clays if they are plastic and silts if they are slightly plastic or non-plastic. Major constituents may be added as modifiers and minor constituents may be added according to the relative proportions based on grain size. In addition to gradation, coarse- grained soils are defined on the basis of their in-place relative density and fine-grained soils on the basis of their consistency. FINE-GRAINED SOILS COARSE-GRAINED SOILS BEDROCK (RS) Blows/Ft. (SS) Blows/Ft. Consistency (RS) Blows/Ft. (SS) Blows/Ft. Relative Density (RS) Blows/Ft. (SS) Blows/Ft. Consistency < 3 0-2 Very Soft 0-6 < 3 Very Loose < 30 < 20 Weathered 3-4 3-4 Soft 7-18 4-9 Loose 30-49 20-29 Firm 5-9 5-8 Medium Stiff 19-58 10-29 Medium Dense 50-89 30-49 Medium Hard 10-18 9-15 Stiff 59-98 30-50 Dense 90-119 50-79 Hard 19-42 16-30 Very Stiff > 98 > 50 Very Dense > 119 > 79 Very Hard > 42 > 30 Hard RELATIVE PROPORTIONS OF SAND AND GRAVEL GRAIN SIZE TERMINOLOGY Descriptive Terms of Other Constituents Percent of Dry Weight Major Component of Sample Particle Size Trace < 15 Boulders Over 12 in. (300mm) With 15 – 29 Cobbles 12 in. to 3 in. (300mm to 75 mm) UNIFIED SOIL CLASSIFICATION SYSTEM Criteria for Assigning Group Symbols and Group Names Using Laboratory Tests Soil Classification Group Symbol Group NameB Coarse Grained Soils More than 50% retained on No. 200 sieve Gravels More than 50% of coarse fraction retained on No. 4 sieve Clean Gravels Less than 5% finesC Cu  4 and 1  Cc  3E GW Well graded gravelF Cu  4 and/or 1  Cc  3E GP Poorly graded gravelF Gravels with Fines More than 12% finesC Fines classify as ML or MH GM Silty gravelF,G, H Fines classify as CL or CH GC Clayey gravelF,G,H Sands 50% or more of coarse fraction passes No. 4 sieve Clean Sands Less than 5% finesD Cu  6 and 1  Cc  3E SW Well graded sandI Cu  6 and/or 1  Cc  3E SP Poorly graded sandI Sands with Fines More than 12% finesD Fines classify as ML or MH SM Silty sandG,H,I Fines classify as CL or CH SC Clayey sandG,H,I Fine-Grained Soils 50% or more passes the No. 200 sieve Silts and Clays Liquid limit less than 50 Inorganic PI  7 and plots on or above “A” lineJ CL Lean clayK,L,M PI  4 or plots below “A” lineJ ML SiltK,L,M Organic Liquid limit - oven dried  0.75 OL Organic clayK,L,M,N Liquid limit - not dried Organic siltK,L,M,O Silts and Clays Liquid limit 50 or more Inorganic PI plots on or above “A” line CH Fat clayK,L,M PI plots below “A” line MH Elastic siltK,L,M Organic Liquid limit - oven dried  0.75 OH Organic clayK,L,M,P Liquid limit - not dried Organic siltK,L,M,Q Highly organic soils Primarily organic matter, dark in color, and organic odor PT Peat A Based on the material passing the 3-in. (75-mm) sieve B If field sample contained cobbles or boulders, or both, add “with cobbles or boulders, or both” to group name. C Gravels with 5 to 12% fines require dual symbols: GW-GM well graded ROCK CLASSIFICATION (Based on ASTM C-294) Sedimentary Rocks Sedimentary rocks are stratified materials laid down by water or wind. The sediments may be composed of particles or pre-existing rocks derived by mechanical weathering, evaporation or by chemical or organic origin. The sediments are usually indurated by cementation or compaction. Chert Very fine-grained siliceous rock composed of micro-crystalline or cyrptocrystalline quartz, chalcedony or opal. Chert is various colored, porous to dense, hard and has a conchoidal to splintery fracture. Claystone Fine-grained rock composed of or derived by erosion of silts and clays or any rock containing clay. Soft massive and may contain carbonate minerals. Conglomerate Rock consisting of a considerable amount of rounded gravel, sand and cobbles with or without interstitial or cementing material. The cementing or interstitial material may be quartz, opal, calcite, dolomite, clay, iron oxides or other materials. Dolomite A fine-grained carbonate rock consisting of the mineral dolomite [CaMg(CO3)2]. May contain noncarbonate impurities such as quartz, chert, clay minerals, organic matter, gypsum and sulfides. Reacts with hydrochloric acid (HCL). Limestone A fine-grained carbonate rock consisting of the mineral calcite (CaCO3). May contain noncarbonate impurities such as quartz, chert, clay minerals, organic matter, gypsum and sulfides. Reacts with hydrochloric acid (HCL). Sandstone Rock consisting of particles of sand with or without interstitial and cementing materials. The cementing or interstitial material may be quartz, opal, calcite, dolomite, clay, iron oxides or other material. Shale Fine-grained rock composed of or derived by erosion of silts and clays or any rock containing clay. Shale is hard, platy, of fissile may be gray, black, reddish or green and may contain some carbonate minerals (calcareous shale). Siltstone Fine grained rock composed of or derived by erosion of silts or rock containing silt. Siltstones consist predominantly of silt sized particles (0.0625 to 0.002 mm in diameter) and are intermediate rocks between claystones and sandstones and may contain carbonate minerals. Exhibit C-3 LABORATORY TEST SIGNIFICANCE AND PURPOSE TEST SIGNIFICANCE PURPOSE California Bearing Ratio Used to evaluate the potential strength of subgrade soil, subbase, and base course material, including recycled materials for use in road and airfield pavements. Pavement Thickness Design Consolidation Used to develop an estimate of both the rate and amount of both differential and total settlement of a structure. Foundation Design Direct Shear Used to determine the consolidated drained shear strength of soil or rock. Bearing Capacity, Foundation Design, and Slope Stability Dry Density Used to determine the in-place density of natural, inorganic, fine-grained soils. Index Property Soil Behavior Expansion Used to measure the expansive potential of fine-grained soil and to provide a basis for swell potential classification. Foundation and Slab Design Gradation Used for the quantitative determination of the distribution of particle sizes in soil. Soil Classification Liquid & Plastic Limit, Plasticity Index Used as an integral part of engineering classification systems to characterize the fine-grained fraction of soils, and to specify the fine-grained fraction of construction materials. Soil Classification Permeability Used to determine the capacity of soil or rock to conduct a liquid or gas. Groundwater Flow Analysis pH Used to determine the degree of acidity or alkalinity of a soil. Corrosion Potential Resistivity Used to indicate the relative ability of a soil medium to carry electrical currents. Corrosion Potential R-Value Used to evaluate the potential strength of subgrade soil, subbase, and base course material, including recycled materials for use in road and airfield pavements. Pavement Thickness Design Soluble Sulphate Used to determine the quantitative amount of soluble sulfates within a soil mass. Corrosion Potential Unconfined Compression To obtain the approximate compressive strength of soils that possess sufficient cohesion to permit testing in the unconfined state. Bearing Capacity REPORT TERMINOLOGY (Based on ASTM D653) Allowable Soil Bearing Capacity The recommended maximum contact stress developed at the interface of the foundation element and the supporting material. Alluvium Soil, the constituents of which have been transported in suspension by flowing water and subsequently deposited by sedimentation. Aggregate Base Course A layer of specified material placed on a subgrade or subbase usually beneath slabs or pavements. Backfill A specified material placed and compacted in a confined area. Bedrock A natural aggregate of mineral grains connected by strong and permanent cohesive forces. Usually requires drilling, wedging, blasting or other methods of extraordinary force for excavation. Bench A horizontal surface in a sloped deposit. Caisson (Drilled Pier or Shaft) A concrete foundation element cast in a circular excavation which may have an enlarged base. Sometimes referred to as a cast-in-place pier or drilled shaft. Coefficient of Friction A constant proportionality factor relating normal stress and the corresponding shear stress at which sliding starts between the two surfaces. Colluvium Soil, the constituents of which have been deposited chiefly by gravity such as at the foot of a slope or cliff. Compaction The densification of a soil by means of mechanical manipulation Concrete Slab-on- Grade A concrete surface layer cast directly upon a base, subbase or subgrade, and typically used as a floor system. Differential Movement Unequal settlement or heave between, or within foundation elements of structure. Earth Pressure The pressure exerted by soil on any boundary such as a foundation wall. ESAL Equivalent Single Axle Load, a criteria used to convert traffic to a uniform standard, (18,000 pound axle loads). Engineered Fill Specified material placed and compacted to specified density and/or moisture conditions under observations of a representative of a geotechnical engineer. Equivalent Fluid A hypothetical fluid having a unit weight such that it will produce a pressure against a lateral support presumed to be equivalent to that produced by the actual soil. This simplified approach is valid only when deformation conditions are such that the pressure increases linearly with depth and the wall friction is neglected. Existing Fill (or Man-Made Fill) Materials deposited throughout the action of man prior to exploration of the site. Existing Grade The ground surface at the time of field exploration. Exhibit C-5 REPORT TERMINOLOGY (Based on ASTM D653) Expansive Potential The potential of a soil to expand (increase in volume) due to absorption of moisture. Finished Grade The final grade created as a part of the project. Footing A portion of the foundation of a structure that transmits loads directly to the soil. Foundation The lower part of a structure that transmits the loads to the soil or bedrock. Frost Depth The depth at which the ground becomes frozen during the winter season. Grade Beam A foundation element or wall, typically constructed of reinforced concrete, used to span between other foundation elements such as drilled piers. Groundwater Subsurface water found in the zone of saturation of soils or within fractures in bedrock. Heave Upward movement. Lithologic The characteristics which describe the composition and texture of soil and rock by observation. Native Grade The naturally occurring ground surface. Native Soil Naturally occurring on-site soil, sometimes referred to as natural soil. Optimum Moisture Content The water content at which a soil can be compacted to a maximum dry unit weight by a given compactive effort. Perched Water Groundwater, usually of limited area maintained above a normal water elevation by the presence of an intervening relatively impervious continuous stratum. Scarify To mechanically loosen soil or break down existing soil structure. Settlement Downward movement. Skin Friction (Side Shear) The frictional resistance developed between soil and an element of the structure such as a drilled pier. Soil (Earth) Sediments or other unconsolidated accumulations of solid particles produced by the physical and chemical disintegration of rocks, and which may or may not contain organic matter. Strain The change in length per unit of length in a given direction. Stress The force per unit area acting within a soil mass. Strip To remove from present location. Subbase A layer of specified material in a pavement system between the subgrade and base course. Subgrade The soil prepared and compacted to support a structure, slab or pavement system. Exhibit C-6 Analysis for Foundations Water Content Used to determine the quantitative amount of water in a soil mass. Index Property Soil Behavior Exhibit C-4 gravel with silt, GW-GC well graded gravel with clay, GP-GM poorly graded gravel with silt, GP-GC poorly graded gravel with clay. D Sands with 5 to 12% fines require dual symbols: SW-SM well graded sand with silt, SW-SC well graded sand with clay, SP-SM poorly graded sand with silt, SP-SC poorly graded sand with clay E Cu = D60/D10 Cc = 10 60 2 30 D x D (D ) F If soil contains  15% sand, add “with sand” to group name. G If fines classify as CL-ML, use dual symbol GC-GM, or SC-SM. HIf fines are organic, add “with organic fines” to group name. I If soil contains  15% gravel, add “with gravel” to group name. J If Atterberg limits plot in shaded area, soil is a CL-ML, silty clay. K If soil contains 15 to 29% plus No. 200, add “with sand” or “with gravel,” whichever is predominant. L If soil contains  30% plus No. 200 predominantly sand, add “sandy” to group name. MIf soil contains  30% plus No. 200, predominantly gravel, add “gravelly” to group name. N PI  4 and plots on or above “A” line. O PI  4 or plots below “A” line. P PI plots on or above “A” line. Q PI plots below “A” line. Exhibit C-2 Modifier > 30 Gravel 3 in. to #4 sieve (75mm to 4.75 mm) Sand Silt or Clay #4 to #200 sieve (4.75mm to 0.075mm) Passing #200 Sieve (0.075mm) RELATIVE PROPORTIONS OF FINES PLASTICITY DESCRIPTION Descriptive Terms of Other Constituents Percent of Dry Weight Term Plasticity Index Trace With Modifiers < 5 5 – 12 > 12 Non-plastic Low Medium High 0 1-10 11-30 30+ Exhibit C-1 Atterberg Limits Percent Passing by Weight #200 Liquid Limit Plasticity Index Water Soluble Sulfates (mg/L) Remarks NV = no value NP = non-plastic Atterberg Limits SUMMARY OF LABORATORY RESULTS 30 7 29.0 7 19.0 11.8 122.3 7 14.0 16.2 Sheet 1 of 1 Job #: 20085059 Site: West of Int. of Plum St. and S. Shields Fort Collins, Colorado Project: Proposed Student Housing Project Unconfined Comp. Strength (psf) Borehole Water Content (%) AASHTO Class- ification % <#200 Sieve Liquid Limit 9.0 Swell (%)/ Surcharge (psf) 5 123.6 6 4.0 8.9 103.0 0.2/500 5 19.0 13.4 9.0 14.0 6.6 5 9.0 12.8 120.5 A-6 CL 10.9 119.2 0.4/500 TC_LAB_SUMMARY 20085059.GPJ BORING.GDT 8/22/08 12.8 4.0 15 7 46 200 A-6 SC 9.0 110.4 0.1/500 6 27 10.7 7 6 19.0 12.9 123.0 6 14.0 9.3 127.0 112.5 11 3 %Gravel %Sand %Silt Specimen Identification 140 %Clay HYDROMETER 9 D60 medium 2.0ft 2.0 ft 36 Project: The District at CSU Proj. No. 20115026 Site: West Plum Street and City Park Avenue, Fort Collins, Colorado TC_GRAIN_SIZE 20115026.GPJ DENVER 031610.GDT 11/1/11 3 %Gravel %Sand %Silt Specimen Identification 140 %Clay HYDROMETER 8 D60 medium 2.0ft 2.0 ft 50 Project: The District at CSU Proj. No. 20115026 Site: West Plum Street and City Park Avenue, Fort Collins, Colorado TC_GRAIN_SIZE 20115026.GPJ DENVER 031610.GDT 11/1/11 N D E X Mini Rig EDB PROJ. NO. LOGGED PROJECT BORING COMPLETED * 140lb. SPT manual hammer 3" diameter solid stem auger Backfilled RIG EDB between soil and rock types: in-situ, the transition may be gradual. The District at CSU West Plum Street and City Park Avenue Fort Collins, Colorado GRAPHIC LOG BORING LOG NO. 11 PERCENT FINES ATTERBERG LIMITS, % BOREHOLE WITH ATTERBERG LIMITS 20115026.GPJ DENVER TEMPLATE 8-5-11.GDT 11/1/11 TYPE NUMBER DEPTH, ft. SAMPLES USCS SYMBOL 5 10 15 20 BLOWS / ft.* RECOVERY, in. WATER CONTENT, % DRY UNIT WT, pcf 116 115 120 BORING STARTED 9-28-11 11.7 WD AD SITE CLIENT WL WL APPROVED The stratification lines represent the approximate boundary lines Page 1 of 1 UNCONFINED STRENGTH, psf TESTS 9-28-11 DESCRIPTION Exhibit A-12 WATER LEVEL OBSERVATIONS, ft Ft. Collins Student Housing, LLC 20115026 CME 55 EDB PROJ. NO. LOGGED PROJECT BORING COMPLETED * 140lb. SPT automatic hammer 4" diameter solid stem auger Backfilled RIG BCJ between soil and rock types: in-situ, the transition may be gradual. The District at CSU West Plum Street and City Park Avenue Fort Collins, Colorado GRAPHIC LOG BORING LOG NO. 10 PERCENT FINES ATTERBERG LIMITS, % BOREHOLE WITH ATTERBERG LIMITS 20115026.GPJ DENVER TEMPLATE 8-5-11.GDT 11/1/11 TYPE NUMBER DEPTH, ft. SAMPLES USCS SYMBOL 5 10 15 20 25 30 35 40 45 BLOWS / ft.* RECOVERY, in. WATER CONTENT, % DRY UNIT WT, pcf UNCONFINED STRENGTH, psf TESTS 9-28-11 DESCRIPTION Exhibit A-11 WATER LEVEL OBSERVATIONS, ft Ft. Collins Student Housing, LLC 20115026 CME 55 EDB PROJ. NO. LOGGED PROJECT BORING COMPLETED * 140lb. SPT automatic hammer 4" diameter solid stem auger Backfilled RIG BCJ between soil and rock types: in-situ, the transition may be gradual. The District at CSU West Plum Street and City Park Avenue Fort Collins, Colorado GRAPHIC LOG BORING LOG NO. 9 PERCENT FINES ATTERBERG LIMITS, % BOREHOLE WITH ATTERBERG LIMITS 20115026.GPJ DENVER TEMPLATE 8-5-11.GDT 11/1/11 TYPE NUMBER DEPTH, ft. SAMPLES USCS SYMBOL 5 10 15 20 25 BLOWS / ft.* RECOVERY, in. WATER CONTENT, % DRY UNIT WT, pcf The stratification lines represent the approximate boundary lines Page 1 of 1 UNCONFINED STRENGTH, psf TESTS 9-22-11 DESCRIPTION Exhibit A-10 WATER LEVEL OBSERVATIONS, ft Ft. Collins Student Housing, LLC 20115026 Mini Rig EDB PROJ. NO. LOGGED PROJECT BORING COMPLETED * 140lb. SPT manual hammer 3" diameter solid stem auger Backfilled RIG EDB between soil and rock types: in-situ, the transition may be gradual. The District at CSU West Plum Street and City Park Avenue Fort Collins, Colorado GRAPHIC LOG BORING LOG NO. 8 PERCENT FINES ATTERBERG LIMITS, % BOREHOLE WITH ATTERBERG LIMITS 20115026.GPJ DENVER TEMPLATE 8-5-11.GDT 11/1/11 TYPE NUMBER DEPTH, ft. SAMPLES USCS SYMBOL 5 10 15 20 25 BLOWS / ft.* RECOVERY, in. WATER CONTENT, % DRY UNIT WT, pcf 30 BLOWS / ft. WATER CONTENT, % USCS SYMBOL SAMPLES BOREHOLE_99 20085059.GPJ BORING.GDT 8/22/08 JOB # DRY UNIT WT pcf RECOVERY, in. DEPTH, ft. NUMBER TYPE 20085059 Page 1 of 1 between soil and rock types: in-situ, the transition may be gradual. West of Int. of Plum St. and S. Shields Fort Collins, Colorado LOG OF BORING NO. 7 WD AB 8-8-08 TESTS 18.2 CLIENT DESCRIPTION Water Level Reading 8/9/08 Glenwood Intermountain Properties SITE WL WL WL BORING COMPLETED GRAPHIC LOG USCS SYMBOL SAMPLES BOREHOLE_99 20085059.GPJ BORING.GDT 8/22/08 % SWELL SURCHARGE DRY UNIT WT pcf RECOVERY, in. DEPTH, ft. NUMBER TYPE West of Int. of Plum St. and S. Shields Fort Collins, Colorado Dry Page 1 of 1 between soil and rock types: in-situ, the transition may be gradual. Glenwood Intermountain Properties LOG OF BORING NO. 6 20085059 WD AB 8-8-08 TESTS CLIENT Water Level Reading 8/9/08 GRAPHIC LOG SITE WL WL WL BORING COMPLETED DESCRIPTION SURCHARGE DRY UNIT WT pcf RECOVERY, in. DEPTH, ft. NUMBER TYPE West of Int. of Plum St. and S. Shields Fort Collins, Colorado 13.5 Page 1 of 1 between soil and rock types: in-situ, the transition may be gradual. Glenwood Intermountain Properties LOG OF BORING NO. 5 20085059 WD AB 8-8-08 TESTS CLIENT Water Level Reading 8/9/08 GRAPHIC LOG SITE WL WL WL BORING COMPLETED DESCRIPTION USCS SYMBOL SAMPLES DRY UNIT WT pcf RECOVERY, in. DEPTH, ft. NUMBER % SWELL SURCHARGE Glenwood Intermountain Properties 12.5 Water Level Reading 8/9/08 JOB # between soil and rock types: in-situ, the transition may be gradual. West of Int. of Plum St. and S. Shields Fort Collins, Colorado 20085059 WD AB Page 1 of 1 GRAPHIC LOG CLIENT LOG OF BORING NO. 4 DESCRIPTION SITE WL WL WL BORING COMPLETED 10 15 20 25 30 BLOWS / ft. WATER CONTENT, % USCS SYMBOL SAMPLES DRY UNIT WT pcf RECOVERY, in. DEPTH, ft. NUMBER TYPE BOREHOLE_99 20085059.GPJ BORING.GDT 8/22/08 DESCRIPTION 20085059 WD AB 8-8-08 TESTS WATER LEVEL OBSERVATIONS, ft West of Int. of Plum St. and S. Shields Fort Collins, Colorado RIG FOREMAN PG BORING STARTED 10 11 8 4 25 GRAPHIC LOG SITE WL WL WL BORING COMPLETED Glenwood Intermountain Properties LOG OF BORING NO. 3 between soil and rock types: in-situ, the transition may be gradual. Water Level Reading 8/9/08 Page 1 of 1 DRY UNIT WT pcf RECOVERY, in. DEPTH, ft. NUMBER TYPE West of Int. of Plum St. and S. Shields Fort Collins, Colorado Dry Page 1 of 1 between soil and rock types: in-situ, the transition may be gradual. Glenwood Intermountain Properties LOG OF BORING NO. 2 20085059 WD AB 8-8-08 TESTS CLIENT Water Level Reading 8/9/08 GRAPHIC LOG SITE WL WL WL BORING COMPLETED DESCRIPTION 5 10 15 20 25 30 BLOWS / ft. WATER CONTENT, % USCS SYMBOL SAMPLES UNCONFINED STRENGTH, psf DRY UNIT WT pcf RECOVERY, in. DEPTH, ft. NUMBER TYPE WATER LEVEL OBSERVATIONS, ft 20085059 WD FILLED IN AB 8-8-08 RIG FOREMAN PG BORING STARTED 14 15 TESTS DESCRIPTION GRAPHIC LOG SITE WL WL WL West of Int. of Plum St. and S. Shields Fort Collins, Colorado BORING COMPLETED between soil and rock types: in-situ, the transition may be gradual. Glenwood Intermountain Properties LOG OF BORING NO. 1 Water Level Reading 8/9/08 Page 1 of 1