HomeMy WebLinkAboutTIMBERLINE CHURCH EXPANSION MAJOR AMENDMENT - 01-97B - CORRESPONDENCE -Project: TIMBERLINE CHURCH EXPANSION MAJOR AMENDMENT
Major Amendment
Request for the Phase 3 addition - 86,400 sq ft addition to northside of building for auditorium to seat approximately 3500 people. There will be
additional parking lot modifications. The project is located at 2908 S. Timberline Rd., on the east side of S. Timberline Road, south of East Drake
Road and north of the Fort Collins High School and Pinecone Apartments. The zoning is LMN - Low Density Mixed Use Neighborhood.
Project Type:
Project Desc:
File ID: 01-97B Planner: Ted Shepard DMS Project Num: CP071965
ID Topic Issue Status Round Comment By Initial Date
1 Zoning [2/26/07] Need to clarify if this major amendment supercedes the current
minor amendment that is in for review. The minor amendment includes
phase 2 and some parking changes on the south, including trash dumpster
locations. However, the major amendment also shows parking and trash
changes on the south, but they are different from those shown on the minor
amendment. Which plan is correct? If it's the major amendment, then
should the minor amendment be withdrawn?
Resolved 1 Peter Barnes 02/26/2007
2 Zoning [2/26/07] Per Section 3.2.2(K)(5)(d) of the Land Use Code, 28 handicap
parking spaces are required. However, the land use data indicates only 26
spaces provided.
Resolved 1 Peter Barnes 02/26/2007
3 Zoning [2/26/07] In order to determine if enough parking is being provided per
Section 3.2.2(K)(1)(h) of the Land Use Code, the plan needs to indicate the
seating capacity of the room or rooms that will be used during worship
services.
Resolved 1 Peter Barnes 02/26/2007
4 Zoning [2/26/07] Show distance from Phase 3 addition to north property line. Resolved 1 Peter Barnes 02/26/2007
5 Zoning [2/26/07] This is in the residential neighborhood sign district. Need to show
possible wall sign location of any wall signs.
Resolved 1 Peter Barnes 02/26/2007
6 General [2/28/07] No comments. Active 1 Doug Martine 02/28/2007
3/7/2011 Page 1
Project: TIMBERLINE CHURCH EXPANSION MAJOR AMENDMENT
ID Topic Issue Status Round Comment By Initial Date
7 Fire [5/23/07] The fire lane needs to be recorded by separate document, if the
property is not going to be replatted. (I worked on the fire lane location and
specifications with folks from Northern Engineering.)
[3/6/07] REQUIRED ACCESS: A fire lane is required. The fire lane shall be
located so that it provides unobstructed access to the Fire Department
(automatic sprinkler) Connection. This fire lane shall be visible by painting
and signage, and maintained unobstructed at all times. A fire lane plan shall
be submitted for approval PRIOR to installation. In addition to the design
criteria already contained in relevant standards and policies, any new fire lane
must meet the following general requirements:
Be designed as a flat, hard, all-weather driving surface (asphalt or
concrete) capable of supporting fire apparatus weights. Compacted road
base shall be used only for temporary fire lanes or at construction sites.
Have appropriate maintenance agreements that are legally binding and
enforceable.
Be designated on the plat as an Emergency Access Easement.
Maintain the required minimum width of 20 feet throughout the length of
the fire lane.
97UFC 901.2.2.1; 901.3; 901.4.2; 902.2.1
Resolved 1 Carie Dann 03/06/2007
8 Fire [3/6/07] WATER SUPPLY: Fire hydrants, where required, must be the type
approved by the water district having jurisdiction and the Fire Department.
Hydrant spacing and water flow must meet minimum requirements based on
type of occupancy. Minimum flow and spacing requirements include:
Commercial, 1,500 gpm at 20 psi residual pressure, spaced not further than
300 feet to the building, on 600-foot centers thereafter. If possible, a fire
hydrant shall be located within 75 feet of the Fire Department Connection.
97UFC 901.2.2.2
Active 1 Carie Dann 03/06/2007
9 General [5/25/07] Adding a note to the plan is not enough. Add to schedule so that all
lights adjacent to the natural feature can be identified separately from other
fixtures.
[4/23/07] Photometric Plan provided. Use house-side shields on fixtures
adjacent to Foothills Channel.
[3/6/07] Photometric Plan is required.
Resolved 1 Dana Leavitt 03/06/2007
10 Landscape Plan [3/6/07] Native plant species are to be used in the buffer zone for the Foothills
Channel. Additional plant material is needed in the buffer zone to mitigate the
view and use of the parking lot adjacent to the channel and meet Sections
3.4.1(E)(1), 3.4.1, 3.4.1(L).
Resolved 1 Dana Leavitt 03/06/2007
3/7/2011 Page 2
Project: TIMBERLINE CHURCH EXPANSION MAJOR AMENDMENT
ID Topic Issue Status Round Comment By Initial Date
11 General [3/6/07] Locate the top of bank and edge of channel for the Foothills Channel
on the Site Plans and the Landscape Plans. Contact Dana Leavittat 224-6143
to set up a site visit to preliminarily identify top of bank and existence, or lack
of ecological characterisitcs of the channel.
Resolved 1 Dana Leavitt 03/06/2007
12 General [3/6/07] Limits of Development (LOD) shall be established and shown on the
Site Plan and the landscape PLan. Contact Dana Leavitt to set up a meeting
to establish.
Resolved 1 Dana Leavitt 03/06/2007
15 Landscape Plan [3/6/07] Additional screening and buffering per Section 3.2.1(E)(4)(b) along
the east property line to address parking lots adjacent to residential uses.
Resolved 1 Dana Leavitt 03/06/2007
16 Landscape Plan [3/6/07] Screening is needed behind the trash enclosure next to the adjoining
property.
Resolved 1 Dana Leavitt 03/06/2007
17 Site Plan [3/6/07] Provide parking lot analysis to demonstrate that 10% of the
proposed parking lot area square footage is interior landscape islands, per
3.2.2(M)(1).
Resolved 1 Dana Leavitt 03/06/2007
18 Fire [3/6/07] AUTOMATIC FIRE SPRINKLERS: The proposed additions (Phases
2 and 3) shall be equipped with automatic fire sprinklers; this sprinkler system
shall form a single system with the existing sprinkler system. Please note on
the site plan, the location of the FDC. 97UBC Table9-B (City of Fort Collins
Amendment).
Active 1 Carie Dann 03/06/2007
19 Fire [3/6/07] KNOX BOX REQUIRED: Poudre Fire Authority requires a Knox
Box to be mounted on the front of every new building equipped with a
required fire sprinkler system or fire alarm system. 97UFC 902.4; PFA
BUREAU POLICY 88-20
Active 1 Carie Dann 03/06/2007
20 Fire [3/6/07] FIRE WATER LINE: Where is the existing fire line that supplies the
automatic fire sprinklers? Construction of any portion of a building over the
existing fire line is prohibited.
Active 1 Carie Dann 03/06/2007
21 Fire [3/6/07] CONSTRUCTION/DEMOLITION: The project must conform to
applicable standards for construction/demolition as specified in the Uniform
Fire Code.
Active 1 Carie Dann 03/06/2007
3/7/2011 Page 3
Project: TIMBERLINE CHURCH EXPANSION MAJOR AMENDMENT
ID Topic Issue Status Round Comment By Initial Date
22 Fire [3/6/07] OCCUPANT LOAD SIGNS: Any room having an occupant load of 50
or more where fixed seats are not installed, and which is used for assembly
purposes, shall have the capacity of the room posted in a conspicuous place
on an approved sign near the main exit from the room. Such sign shall be
maintained legible by the owner or the owners authorized agent and shall
indicate the number of occupants permitted for each room use. 97UFC
2601.16.1
Active 1 Carie Dann 03/06/2007
23 Fire [3/6/07] COMMERCIAL COOKING FIRE EXTINGUISHING SYSTEM:
With the production of grease-laden vapors, an approved, automatic
fire-extinguishing system shall be provided for the protection of
commercial-type cooking equipment. 97UFC 1006.1; 1006.2.1
Active 1 Carie Dann 03/06/2007
24 Fire [3/6/07] TRAFFIC FLOW: How is the church proposing to deal with a
possible increase of traffic entering and leaving the parking lots? Will large
numbers of private passenger vehicles be able to yield to emergency
vehicles, if the private vehicles do not enter or exit (particularly exit) the
parking lot other than at the traffic signals?
Active 1 Carie Dann 03/06/2007
25 General [3/7/07] In the Project Description several statements were made in regards
to natural areas, wetlands and buffers. First, a site visit is neccesary to
determine if an Ecological Characterization Study will be needed per Section
3.4.1(D) of the LUC. Second, until the feature (the Foothills Channel) hs been
physically defined, the location of the buffer cannot be established. After the
location of the buffer has been established per Section 3.4.1(E)(1) and the
Buffer Zone Table of 3.4.1(E), a determination will be made on the size of the
buffer. Third, the landscape material within the buffer as shown on the
landscape plan does not meet the standards as articulated in Section
3.4.1(E)(1)(e) and (g).
Resolved 1 Dana Leavitt 03/07/2007
26 Utility Plans [5/25/07] If light types are hard to read, provide another type where overlap
occurs.
[4/24/07] Show top of embanment of existing conditions also, otherwise ok.
Show LOD on all plan sets with in the Utility Plans.
[3/7/07] The edge of the Foothills Channel and the top of embankment
needs to be located on the Existing Conditions Plan, the Demolition Plan
sheets, the Horizontal Control Plan sheets, the Grading Plan sheets and the
Overlot Grading Plan sheets. The Limits of Development (LOD), once
established, shall be show on all of the plans referenced above.
Resolved 1 Dana Leavitt 03/07/2007
3/7/2011 Page 4
Project: TIMBERLINE CHURCH EXPANSION MAJOR AMENDMENT
ID Topic Issue Status Round Comment By Initial Date
27 Utility Plans [3/7/07] The Demolition Plan sheets show many exisitng trees to be
removed. There is no mention whether or not any of the removed trees will
be saved and eventually replanted as part of the Landscape Plan. The
potential removal of this many trees will impact the amount of solar radiation
coming off of the paved surfaces and the visual quality of the site. At a
minimum, contact Tim Buchanan, the City Forester to address this issue.
Tree protection standards need to be added to the Demolition plans for the
trees shown to be protected, per Section 3.2.1(F), of the LUC.
Resolved 1 Dana Leavitt 03/07/2007
29 Landscape Plan [3/7/07] Add Tree Protection stadards to the landscape Plan, per Section
3.2.1(F), of the LUC.
Resolved 1 Dana Leavitt 03/07/2007
30 Traffic Engineering [3/13/07] The Traffic Study is acceptable. Active 1 Eric Bracke 03/13/2007
31 Water/Wastewater [3/13/07] Show the water/sewer services and fire line which were stubbed
out in the original construction for the Phase III building addition. Will these
be used for the building addition? Or should the stubs be abandoned now?
Resolved 1 Roger Buffington 03/13/2007
32 Water/Wastewater [3/13/07] PVC vs DIP pipe? Resolved 1 Roger Buffington 03/13/2007
33 Water/Wastewater [3/13/07] See redlined utility plans for other comments. Resolved 1 Roger Buffington 03/13/2007
34 Landscape Plan [4/24/07] Adjust tree locations to provide 10 foot minimum separation from all
water mains.
[3/13/07] Show water/sewer mains and service lines. Adjust plantings to
meet separation requirements in Note 11 on Sht 9 of Landscape Plan.
Resolved 1 Roger Buffington 03/13/2007
3/7/2011 Page 5
Project: TIMBERLINE CHURCH EXPANSION MAJOR AMENDMENT
ID Topic Issue Status Round Comment By Initial Date
35 General [5/22/07] Given that the minor amendment is being shown on the plans,
please amend the note on the cover sheet regarding the minor amendment to
read as follows: "Minor Amendment design for Timberline Church was
approved on May 16, 2007 via revisions to the Timberline Church
construction plan set. Information shown regarding the minor amendment
within this plan set is for informational purposes only. In the event of a
discrepancy between the information shown in this plan set and the revisions
to the Timberline Church plan set, the revisions to the Timberline Church plan
set shall govern. As-built/record drawing information pertaining to the minor
amendment shall be shown on the revision drawings." If there are questions
or concerns regarding this proposed note, please let me know.
[4/24/07] The response from Northern indicated that the minor amendment
information on the construction plan set is to remain as the site contractor will
be building off the plans. If this is the case, why is there a minor amendment
being approved prior to this major amendment showing the exact
information? It seems that the minor amendment should just then be
withdrawn if the contractor isn't intending to build off the revised sheets of the
minor amendment that shows this same information. I'd like to suggest a
meeting with Northern, myself, and Sheri Langenberger who is reviewing the
minor amendment.
[3/14/07] I'd like to see the minor amendment indications on the drawings to
be "faded back" so that it is evident that the information shown in not being
approved. With the assumption that the minor amendment will be approved
prior to the major amendment, please add a note at the time of mylars for the
major amendment indicating the approval date of the minor amendment.
Resolved 1 Marc Virata 03/14/2007
36 General [4/24/07] Carried over pending the City Traffic Engineer's okay in not
constructing the right turn lane.
[3/14/07] The right turn lane off of Timberline Road appears to fall short of
turn lane length requirements. A variance request should be submitted
addressing this. I don't forsee a concern with its approval, but it should at
least be submitted for evaluation. (Note: This observation is based upon the
present design submitted with a right turn lane that extends along the CSU
property.)
Resolved 1 Marc Virata 03/14/2007
3/7/2011 Page 6
Project: TIMBERLINE CHURCH EXPANSION MAJOR AMENDMENT
ID Topic Issue Status Round Comment By Initial Date
37 General [4/24/07] Carried over pending the City Traffic Engineer's okay in not
constructing the right turn lane.
[3/14/07] The construction of the right turn lane appears to have a
substanative impact on the CSU property. Sheet 13 of the construction plan
set even shows a proposed contour line cutting through one of the buildings
and a 25% grade from the sidewalk to that building. What is the plan for
mitigating the impact to CSU? Will a building be removed? A letter of intent
is required from CSU prior to a hearing.
Resolved 1 Marc Virata 03/14/2007
38 Construction Plan [4/24/07] Carried over pending the City Traffic Engineer's okay in not
constructing the right turn lane.
[3/14/07] Please show additional existing countours on the CSU property in
order to ascertain how the right turn lane construction ties into the existing
property.
Resolved 1 Marc Virata 03/14/2007
39 Construction Plan [4/24/07] Carried over pending the City Traffic Engineer's okay in not
constructing the right turn lane.
[3/14/07] The sidewalk crossing the driveway along Timberline appears
awkward. I'd like to suggest keeping the sidewalk closer to Timberline to
head straight across the driveway rather than bring it closer to the site.
Resolved 1 Marc Virata 03/14/2007
40 Construction Plan [4/24/07] Carried over pending the City Traffic Engineer's okay in not
constructing the right turn lane.
[3/14/07] Additional design information is needed for the right turn lane prior
to a hearing. What are existing flowline grades and spot elevations of the
surrounding area? At the time of final a flowline profile and cross sections will
be needed.
Resolved 1 Marc Virata 03/14/2007
41 Construction Plan [5/22/07] On Sheet 6 the demo plan indicates removal of work along
Timberline, I'm assuming that this needs to be rectified with the right turn lane
no longer being constructed.
[4/24/07] Carried over pending the City Traffic Engineer's okay in not
constructing the right turn lane. (Note that if the City's Traffic Engineer is
okay with not constructing the right turn lane, the plan set still reflects demo
work occuring in this area.)
[3/14/07] What is the hatched out area along Timberline on the plan set, and
is the median being proposed for modification?
Resolved 1 Marc Virata 03/14/2007
42 Site Plan [3/14/07] The vicinity map is not scannable. Resolved 1 Marc Virata 03/14/2007
3/7/2011 Page 7
Project: TIMBERLINE CHURCH EXPANSION MAJOR AMENDMENT
ID Topic Issue Status Round Comment By Initial Date
43 Construction Plan [4/24/07] Carried over pending the City Traffic Engineer's okay in not
constructing the right turn lane.
[3/14/07] Please show existing striping along Timberline in conjunction with
the demo plan to verify if patching limits are appropriate.
Resolved 1 Marc Virata 03/14/2007
44 General [5/22/07] The response indicated that the emergency access easement has
been processed with the minor amendment, in reality it will br processed with
this major amendment and the minor amendment was approved without it.
[4/24/07] Deeds of dedication were provided, which require a $250
Transportation Development Review Fee for each deed. Note that Sheri
Langenberger had requested the emergency access easement as part of the
minor amendment, which will likely be process through the minor amendment
instead of the major amendment.
[3/14/07] Will the various easement and right-of-way dedications be done via
plat or deed?
Resolved 1 Marc Virata 03/14/2007
45 General [4/24/07] Carried over pending the City Traffic Engineer's okay in not
constructing the right turn lane.
[3/14/07] A 15' utility easement is typically required behind the right-of-way.
With the right turn lane being done, a 15' easement can't be done behind the
right-of-way. The utility providers will need to okay this.
Resolved 1 Marc Virata 03/14/2007
46 Construction Plan [4/24/07] Carried over pending the City Traffic Engineer's okay in not
constructing the right turn lane.
[3/14/07] Please provide a striping plan sheet that shows the right turn lane
in conjunction with the existing lanes along Timberline.
Resolved 1 Marc Virata 03/14/2007
47 Traffic Engineering [3/14/07] I recently discovered that the Church does not intend to use Police
traffic control at the key intersections as was stated in the TIS. If this is so,
then the traffic study needs to be revised to analyze the queues for the SB left
turns into the site to determine if there will be an impact to the SB through
lanes.
Active 1 Eric Bracke 03/14/2007
48 General [3/15/07] On all plans - Site to Utility plans, extend rxisitng conditions of
Foothills Channel as it turns east so that the extent of the buffer can be
shown on the property.
Resolved 1 Dana Leavitt 03/15/2007
3/7/2011 Page 8
Project: TIMBERLINE CHURCH EXPANSION MAJOR AMENDMENT
ID Topic Issue Status Round Comment By Initial Date
49 General [3/15/07] Please ensure all documents have the same title, the title of the
construction plans "Timberline Church Expansion" is fine. The site plan title
of "Timberline Church" is problematic if used on all the documents as it would
share the title of the original project.
Resolved 1 Marc Virata 03/15/2007
50 Construction Plan [4/24/07] Carried over pending the City Traffic Engineer's okay in not
constructing the right turn lane.
[3/15/07] Please show existing Timberline Road (flowline curb and gutter,
median, striping (on the striping and demo plan) up to the northern boundary
of the overall site.
Resolved 1 Marc Virata 03/15/2007
51 Release rate from
detention pond
[3/22/07] The modeling shows an increase in flows downstream at one node.
Please revise detention release rate in order to ensure that no adverse
conditions occur downstream due to release from this site.
Active 1 Basil Hamdan 03/22/2007
52 Utility Plans [3/22/07] Please indicate where ponding in the parking lot would occur, make
sure it is no more than 6 inches in the 100 year storm scenario.
Call out existing drainage structures such as pans, inlets and pipes.
Provide a spillway location and design for the detention pond.
Provide one foot of cover on pipe is possible. Storm Line A-1 seems to have
quite a bit of exposed pipe in the detention pond, please address by
shortening pipe or altering grading. Shallow cover is also a problem at inlet
A-3 and C-3, accounting for pipe thickness some of these pipes would be
extruding into the parking lot.
Please see redlines for additional comments.
Active 1 Basil Hamdan 03/22/2007
3/7/2011 Page 9
Project: TIMBERLINE CHURCH EXPANSION MAJOR AMENDMENT
ID Topic Issue Status Round Comment By Initial Date
53 Landscape Plans [3/22/07] Please indicate what the detention pond mix is on the landscape
plan. A dry seed mix was found but it was not clear whether that was the
same as the detention pond mix.
Detention pond landscaping should be altered to use water tolerating grasses
in shallow swales or pans should be added. It is recommended that the
water quality portions of the pond be vegetated with wetland grasses.
Please specify how the disturbed area on the City of Fort Collins property will
be revegetated. Specify a seed mix for that area.
Active 1 Basil Hamdan 03/22/2007
54 Demolition Plans [3/22/07] Please indicate what will be done to the existing tiles/pipes that are
located within the future construction area. These should be called out to be
abandoned and removed if no longer in use, otherwise, they should be tied
back into any subdrain system they may be serving.
Indicate which existing storm sewers are to be protected in place.
Indicate any existing trees that will be protected, specifically in the channel
area.
Active 1 Basil Hamdan 03/22/2007
55 Details [3/23/07] Please use the updated water quality outlet detail, there is one new
revision to the detail used. I can email you a copy of the latest detail, if you
send me a request at bhamdan@fcgov.com
Please turn on the layer for the inlet detail.
Clarify whether the concrete pan detail will be used throughout the project.
Specify what riprap details will be used at what location.
Provide a detail for the one foot chase called out in the parking lot.
Active 1 Basil Hamdan 03/23/2007
3/7/2011 Page 10
Project: TIMBERLINE CHURCH EXPANSION MAJOR AMENDMENT
ID Topic Issue Status Round Comment By Initial Date
56 Grading Plans [3/23/07] Clean up text make it scannable.
Add concrete pans to swale at less than 2 % at eastern edge of parking lot,
as well as to the bottom of the detention pond.
Add notes that require that the channel disturbance will be limited to the
delineated construction area.
Grading on USDA property will require an easement from that property
owner.
Active 1 Basil Hamdan 03/23/2007
57 Erosion Control
Plans
[3/23/07] Specify what sheets are being used as erosion control plans, label
appropriately, provide erosion control standard notes, schedule and details.
Provide erosion control efficiency calcs, and escrow. Use tru dams in parking
lot inlet.
Provide silt fence along disturbance in the channel.
Active 1 Basil Hamdan 03/23/2007
58 General [4/23/07] The response letter indicated that the right turn lane into the site
was removed after discussion with the church and traffic engineer consultant.
In talking with the Traffic Engineer, he'd like a letter or information from the
traffic engineer consultant as to why this is no longer being provided.
Resolved 2 Marc Virata 04/23/2007
59 Easements [4/24/07] Will the existing and proposed drainage easements be vacated and
dedicated by separate document ? If so please provide deeds of dedication.
Active 2 Basil Hamdan 04/24/2007
60 Demolition Plans [4/24/07] Please indicate that the exiting outlet box and pipe in the existing
pond is to be protected in place.
Active 2 Basil Hamdan 04/24/2007
61 Phasing Plans [4/24/07] Please label the current major amendment as Phase 1. Phase
numbering should be clarified so that it includes only those phases that are
being approved by these plans.
Active 2 Basil Hamdan 04/24/2007
3/7/2011 Page 11
Project: TIMBERLINE CHURCH EXPANSION MAJOR AMENDMENT
ID Topic Issue Status Round Comment By Initial Date
62 Utility Plans [4/24/07] Please move storm manhole A2 for storm Line A north away from
the Foothills Channel, in order to minimize potential grading impacts on
channel. As currently designed the manhole is right at the edge of City
property.
Please realign new proposed outlet pipe so that it is more in line with the
channel, it now comes out at a 90 degree angle, and could cause serious
erosion along the channel bank.
Active 2 Basil Hamdan 04/24/2007
63 Erosion Control
Plans
[4/24/07] Please ad an erosion control schedule to the plan as well as the a
schedule.
Please provide some silt fence protection around the outlet pipe that will be
bult out into the Foothills Channel.
Active 2 Basil Hamdan 04/24/2007
64 Water/Wastewater [4/24/07] Revise the various notes on abandonment of water services to
include the removal of the curb stops.
Resolved 2 Roger Buffington 04/24/2007
65 Landscape Plans [4/24/07] Please specify how the disturbed area within the Foothills Channel
where the pipe outlet from the detention pond is being installed will be
re-vegetated. Re-vegetation should match existing seed mix for the channel.
Active 2 Basil Hamdan 04/24/2007
66 Grading Plans [4/24/07] Please call out pond spillway location and elevation on the grading
plans. Please provide erosion protection for the proposed spillway overflow
structure downstream of the spillway. Is the existing pedestrian path the top
of the spillway ? Did you check path elevation ?
Active 2 Basil Hamdan 04/24/2007
67 Storm Sewer
Profiles
[4/24/07] Please call out the ponding elevations in the parking lot on the
storm line profiles.
Active 2 Basil Hamdan 04/24/2007
68 Water quality pond
outlet details
[4/24/07] Please provide an actual water quality outlet box detail with the
proposed outlet plates. The detail provided is an outdated one with the
generic water quality plate detail, rather than the actual ones.
Active 2 Basil Hamdan 04/24/2007
3/7/2011 Page 12
Project: TIMBERLINE CHURCH EXPANSION MAJOR AMENDMENT
ID Topic Issue Status Round Comment By Initial Date
69 Phasing Plans [4/24/07] Echoing Stormwater comments, please relabel the phasing plan as
follows:
"Major Amendment Phase" is "Phase 1"
"Major Amendment Future Phase" is "Phase 2"
"Major amendment" should just be removed from any indication on the plan
set. It is my understanding that the existing building is intended to be Phase
1, this is problematic for the City, as we'd be issuing Phase 2 and Phase 3
DCP's for "Timberline Church Expansion" without a Phase 1.
Resolved 2 Marc Virata 04/24/2007
70 Phasing Plans [5/22/07] Please show work that is being done within the channel area as
being part of Phase I.
The storm sewersystem that goes through Phase II bringing flows from the
existing parking lot should be designated to be built with Phase I.
Provide an interim grading plan for swale along east property line for Phase I
plans.
Please call for revegetation of areas within Phase II that will be disturbed
during Phase I grading operations.
Active 3 Basil Hamdan 05/22/2007
71 Easements [5/22/07] Please provide separate easements for areas within future pond
that are being dedicated as drainage easements.
Active 3 Basil Hamdan 05/22/2007
72 Details [5/22/07] Please provide an actual detail for Line E riprap with dimensions. Active 3 Basil Hamdan 05/22/2007
73 Landscape Plan [5/22/07] There is a conflict between the proposed storm line and the tree in
one of the islands in Phase II construction, please adjust tree location to
provide a minimum of 5 feet of clearance.
Active 3 Basil Hamdan 05/22/2007
74 Utility Plans
[5/22/07] Please provide riprap on downstream end of spillway.
Resolved 3 Basil Hamdan 05/22/2007
75 General [6/21/07] Carried over for reference.
[5/24/07] At the time of final submittal after public hearing, a Transportation
Development Revew Fee of $1,000 is required. A Development Construction
Permit (DCP) will be required prior to any work pertaining to this major
amendment.
Active 3 Marc Virata 05/24/2007
3/7/2011 Page 13
Project: TIMBERLINE CHURCH EXPANSION MAJOR AMENDMENT
ID Topic Issue Status Round Comment By Initial Date
76 Site Plan [6/21/07] Technical Services has indicated that there are still areas of
concern. See attached redlines.
[5/24/07] Technical Services has redlined areas on the site plan that may be
of concern for scannability purposes. Please see the attached redlines.
Active 3 Marc Virata 05/24/2007
77 Fire [6/19/07] PFA has no additional comments or concerns at this time. Active 4 Carie Dann 06/19/2007
78 Utility Plans [6/20/07] Please add a boulder to the riprap detail for the outfall into the
Foothills Channel to hide the pipe outfall.
Plans look OK for mylars submittal at final.
Active 4 Basil Hamdan 06/20/2007
79 Erosion Control
Plans
[6/20/07] The erosion control security estimate is calculated for Phase I.
Please clarify in the estimate calculations sheet that the figure calculated is
for Phase I improvements only. A separate Phase II security escrow
calculation should also be provided.
Active 4 Basil Hamdan 06/20/2007
80 Stormwater Fees [6/20/07] Since no building permit is associated with Phase I improvements
please add a note to the phasing plans stating that fees for Phase I
improvements will need to be paid prior to issuance of a DCP for Phase I.
Fees for the future Phase II improvements can be associated with a building
permit of a DCP for Phase II.
Please provide a breakdown for the increase in impervious area associated
with Phase I and those associated with Phase II improvements, in order to
subdivide the stormwater fees into two separate amounts, one for each
phase.
Active 4 Basil Hamdan 06/20/2007
81 General [6/21/07] With the final submittal, we'll discuss permitting process via the
DCP and whether an amendment to the original development agreement
and/or a new development agreement is required.
Active 4 Marc Virata 06/21/2007