HomeMy WebLinkAboutHARMONY TECH PARK - 01-08 A - CORRESPONDENCE -Project: HARMONY TECH PARK, 3RD FILING, CUSTOM BLENDING PDP - TYPE I AND FINAL PLANS
PDP - Final Compliance
Request for a 31,775 sq ft building consisting of an office, light manufacturing and warehouse usages on a 3 acre parcel in Harmony Technology Park.
Located at Lady Moon and Precision Dr, directly south of Harmony Technology Park. Zoning is HC - Harmony Corridor.
(Office-7,947 sq ft two story office located on the north side of the building, facing Precision Drive. Light manufacturing-
9,249 sq ft Liquid Blending and extraction portion of the building is housed in a precast concrete wall panel constrution directly to the south of the
office component. 6,930 sq ft Dry Blending storage and packaging portion is at the southern end of the facility with the same 24' height as the Liquid
Blending/Extraction Area. Warehouse-7,649 sq ft finished warehouse located between the liquid and dry production areas being the tallest at 37' feet.
(This
Project Type:
Project Desc:
File ID: 01-08/A Planner: Ted Shepard DMS Project Num: CP082079
ID Topic Issue Status Round Comment By Initial Date
1 Plat [2/4/08] The nearest power is at Lady Moon Dr. A developer of the Harmony
Technology 3rd filing will need to coordinate with Light &Power Engineering
for the installation of electric facilities and the electric development charges
for this plat. This will bring high voltage power to the corner of each lot. An
ODP would be helpful in planning electric facilities to the general area. The
plat needs a north arrow and scale block.
Active 1 Doug Martine 02/04/2008
2 Electric Utility [2/4/08] The developer of the Custom Blending lot will need to coordinate
power requirements and electric development charges with Light & Power
Engineering. (970)221-6700.
Active 1 Doug Martine 02/04/2008
3 Electric Utility [2/4/08] The transformer location shown will need to be adjusted to be a
minimum of 2 ft. from the back of the sidewalk.
Active 1 Doug Martine 02/04/2008
4 Landscape Plan [2/4/08] A streetlight is planned for immediately west of the easterly driveway
at the point where the curb becomes straight. The street tree to the west of
this point will need to be either relocated to be a minimum of 40 ft. from the
streetlight, or changed to an ornamental type which has a minimum clearance
of 15 ft.
Active 1 Doug Martine 02/04/2008
5 Zoning [4/24/08]
[2/7/08] Please show building envelope, footprint and dimensions on site
plan.
4-24-08 Building dimensions are still not shown on the site plan
Active 1 Jenny Nuckols 02/07/2008
6 Zoning [2/7/08] Please note width of parking stalls on site plan. Resolved 1 Jenny Nuckols 02/07/2008
3/7/2011 Page 1
Project: HARMONY TECH PARK, 3RD FILING, CUSTOM BLENDING PDP - TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
7 Zoning [4/24/08]
[2/8/08] Add note to landscape notes regarding installation of landscaping
prior to issuance of CO.
4-24-08 Landscape assurance note needs to include all landscaping, not just
that in the drainage tract, but all landscaping on that site.
Active 1 Jenny Nuckols 02/08/2008
8 General [2/7/08] The planning documents have the title "Custom Blending" while the
engineering/plat documents have the title "Harmony Technology Park 3rd
Filing". Please have the document titles match. Harmony Technology Park
3rd Filing, Custom Blending would be fine for the title.
Resolved 1 Marc Virata 02/07/2008
9 Construction
Drawings
[2/7/08] The access ramps at all the public street intersections need to be
directional instead of leading to the corners (middle). Please show future
access ramps at the corners of the street intersections being built in order to
ensure that when these corners are poured the future access ramps can then
be provided without having to remove curb.
Resolved 1 Marc Virata 02/08/2008
10 General [5/6/08] Carried over for reference.
[2/8/08] The offsite pond (Pond B) shown on the northwest corner of
Technology Parkway and Rock Creek Drive is considered development and
as such the street frontages abutting Pond B needs to be obligated for.
Sidewalk along Technology Parkway and Rock Creek Drive abutting Pond B
would need to be escrowed for if not being built at this time. If a repay was
filed with the City for the construction of Rock Creek Drive, the frontage
abutting Pond B would also be required.
Active 1 Marc Virata 02/08/2008
11 General [5/6/08] Carried over for reference.
[2/8/08] The offsite pond (Pond B) should have a 9 foot utility easement
dedicated along Technology Parkway and Rock Creek Drive.
Active 1 Marc Virata 02/08/2008
3/7/2011 Page 2
Project: HARMONY TECH PARK, 3RD FILING, CUSTOM BLENDING PDP - TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
12 General [2/19/08] The enhanced crosswalk shown on the south side of the
Precision/Tech Parkway intersection has some concerns. In checking with
Traffic Operations, they wouldn't typically install a crosswalk without access
ramps and a sidewalk network on both sides to connect to. Given that there's
no sidewalk in the general area being proposed at this time, perhaps
crosswalk installation should at least be deferred. I've also had some further
discussion with Transportation Planning and Traffic and the consensus was
that the location of the crosswalk itself seems a bit odd as we're not seeing
this area having a higher amount of pedestrian traffic as compared to other
intersections such as the north side of the Tech Parkway/Rock Creek Drive
intersection. What is driving the design for an enhanced crosswalk in this
location?
Resolved 1 Marc Virata 02/19/2008
13 General [2/19/08] Please be aware that the additional width of Technology Parkway
beyond the standard collector width is not reimbursable through Street
Oversizing. Is the median shown on Technology Parkway intended to have
landscaping? If so, we will look to have language in the development
agreement regarding maintenance responsibilities (which will not be the City).
Resolved 1 Marc Virata 02/19/2008
14 Water/Wastewater [2/19/08] General water main layout is okay for preliminary. Valving, fittings,
etc. will be reviewed at final when detailed notes and information have been
added.
Resolved 1 Roger Buffington 02/19/2008
15 Construction
Drawings
[5/6/08] Please remove the reference to "plus added median" below the
typical cross section on Sheet C-003. Is the use of the broken yellow line for
the inside of the reversible lane ideal given that there are no turning
movements currently to necessitate entering the center lane?
[2/19/08] With the median on Technology Parkway intended to have
landscaping per C-003 then additional information at the time of final will be
required, such as landscaping plan, subdrain systems, etc.
Active 1 Marc Virata 02/19/2008
16 Water/Wastewater [5/8/08]
[2/19/08] Information pertaining to water service size is conflicting in various
spots.
Active 1 Roger Buffington 02/19/2008
17 Water/Wastewater [2/19/08] Did PFA require both FH's on Lot 2? Resolved 1 Roger Buffington 02/19/2008
18 Easements [2/19/08] Please provide a drainage easement by separate document for the
off-site pond.
Active 1 Basil Hamdan 02/19/2008
3/7/2011 Page 3
Project: HARMONY TECH PARK, 3RD FILING, CUSTOM BLENDING PDP - TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
19 Drainage Report [2/19/08] Please provide a written explanation in the report for the overall
drainage design. Overall drainage report could be broken out into a separate
report.
Active 1 Basil Hamdan 02/19/2008
20 Utility Plans [2/19/08] The existing stub in Lady Moon Drive is being replaced, this will
cause a street cut for a new street with associated fees. Can the exiting stub
be used or is it at the wrong elevation ? If not please show extent of street
cut.
Please call out on the plans all the disturbed areas to be re-vegetated.
Provide a plug detail for the storm sewer stubs.
Please include a hydrology summary table on drainage plan and an erosion
control sequence schedule on the erosion control plan.
At final please show all spillway locations for detention ponds and provide
details for the spillways as well as for the water quality outlets.
Active 1 Basil Hamdan 02/19/2008
21 Fire [2/20/08] REQUIRED ACCESS: A fire lane is required. This fire lane shall be
visible by painting and signage, and maintained unobstructed at all times. A
fire lane plan shall be submitted for approval prior to installation. In addition
to the design criteria already contained in relevant standards and policies, any
new fire lane must meet the following general requirements:
Be designed as a flat, hard, all-weather driving surface (asphalt or
concrete) capable of supporting fire apparatus weights. Compacted road
base shall be used only for temporary fire lanes or at construction sites.
Have appropriate maintenance agreements that are legally binding and
enforceable.
Be designated on the plat as an Emergency Access Easement.
Maintain the required minimum width of 20 feet throughout the length of
the fire lane.
If a fire lane cannot be provided, the building shall be fire sprinklered.
NOTE: When the structure is expanded in the future and the entire loop drive
is paved, PFA likely will require that the fire lane be "filled in" throughout the
entire loop.
97UFC 901.2.2.1; 901.3; 901.4.2; 902.2.1
Active 1 Carie Dann 02/20/2008
3/7/2011 Page 4
Project: HARMONY TECH PARK, 3RD FILING, CUSTOM BLENDING PDP - TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
22 Fire [2/20/08] ADDRESS NUMERALS: Address numerals shall be visible from
the street fronting the property, and posted with a minimum of 6 inch
numerals on a contrasting background. (Bronze numerals on brown brick are
not acceptable).97UFC901.4.4
Active 1 Carie Dann 02/20/2008
23 Fire [2/20/08] WATER SUPPLY: Fire hydrants, where required, must be the type
approved by the water district having jurisdiction and the Fire Department.
Hydrant spacing and water flow must meet minimum requirements based on
type of occupancy. Minimum flow and spacing requirements include:
Commercial, 1,500 gpm at 20 psi residual pressure, spaced not farther than
300 feet to the building, on 600-foot centers thereafter; residential within
Urban Growth Area, 1,000 gpm at 20 psi residual pressure, spaced not
farther than 400 feet to the building, on 800-foot centers thereafter; residential
outside Urban Growth Area, 500 gpm at 20 psi residual pressure, spaced not
farther than 400 feet to the building, on 800-foot centers thereafter.
These requirements may be modified if buildings are equipped with automatic
fire sprinkler systems.
97UFC 901.2.2.2
Active 1 Carie Dann 02/20/2008
24 Fire [2/20/08] SPRINKLER REQUIREMENTS: This proposed building shall be
equipped with approved, automatic fire-sprinkler systems.
Active 1 Carie Dann 02/20/2008
25 Fire [2/20/08] FIRE LINE REQUIREMENT: Buildings that are required to be fire
sprinklered shall have a minimum 6-inch fire line unless hydraulic calculations
can support a smaller fire line.
Active 1 Carie Dann 02/20/2008
26 Fire [2/20/08] FIRE DEPARTMENT CONNECTION: Fire department connections
shall be installed on the street or fire lane side of buildings, fully visible and
recognizable from the street or nearest point of fire department vehicle
access or as otherwise approved by the fire code official. If possible, a fire
hydrant shall be located within 100 feet of the FDC. PFA Bureau Policy
Active 1 Carie Dann 02/20/2008
27 Fire [2/20/08] KNOX BOX REQUIRED: Poudre Fire Authority requires a Knox
Box to be mounted on the front of every new building equipped with a
required fire sprinkler system or fire alarm system. 97UFC 902.4; PFA
BUREAU POLICY 88-20
Active 1 Carie Dann 02/20/2008
3/7/2011 Page 5
Project: HARMONY TECH PARK, 3RD FILING, CUSTOM BLENDING PDP - TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
28 Fire [2/20/08] COMMERCIAL COOKING FIRE EXTINGUISHING SYSTEM: An
approved fire-protection system shall be installed in hood-and-duct locations
where grease-laden vapors are produced from cooking operations. A permit
and plan review is required by the Poudre Fire Authority for the installation of
required hood-and-duct fire extinguishing systems. Two sets of plans, along
with an application, are required to be submitted to the Fire Prevention
Bureau at 102 Remington St. 97UFC 1006.1; 1006.2.1
Active 1 Carie Dann 02/20/2008
29 Fire [2/20/08] HMIA: Thank you for submittal of Hazardous Materials Impact
Analysis.
Active 1 Carie Dann 02/20/2008
30 Fire [2/20/08] . Active 1 Carie Dann 02/20/2008
31 Construction
Drawings
[2/20/08] The storm pipe crossing Technology Parkway on either side of the
inlets may have a cover issue. Please look at achieving additional depth over
the pipe to ensure no cover concerns.
Resolved 1 Marc Virata 02/20/2008
32 Construction
Drawings
[5/6/08] The applicant's response is fine, though interestingly, I'm now
realizing that west of Technology Parkway may not necessarily be a public
street. Maybe a note on the construction plan should be provided indicating
that Precision Drive may or may not develop as a public street west of
Technology Parkway. Information shown for reference only.
[2/20/08] For the future Precision Drive section please provide horizontal
curve data.
Active 1 Marc Virata 02/20/2008
33 Construction
Drawings
[5/6/08] See response to #32.
[2/20/08] For the future Precision Drive section, please clarify the profile view
information, the lines arent apparent as which might be proposed, existing, or
other.
Active 1 Marc Virata 02/20/2008
34 Construction
Drawings
[2/20/08] The storm pipe crossing Precision Drive on either side of the inlets
may have a cover issue. Please look at achieving additional depth over the
pipe to ensure no cover concerns.
Resolved 1 Marc Virata 02/20/2008
35 General [2/20/08] I'm understanding that entitlement will only occur for the Custom
Blending lot and that the remainder of the lots in the plat will be subject to
their own project development plans and associated development
agreements.
Resolved 1 Marc Virata 02/20/2008
3/7/2011 Page 6
Project: HARMONY TECH PARK, 3RD FILING, CUSTOM BLENDING PDP - TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
36 General [2/20/08] Letters of intent should be provided from the property owner west
of Technology Parkway where the offsite detention occurs.
Resolved 1 Marc Virata 02/20/2008
37 Plat [5/7/08] Technical Services has the following revised comments:
1. Boundary and legal close but have minor differences.
2. Remove all references to Cambridge Avenue.
[2/20/08] Technical Services has the following comments:
1. No north arrow and scale plat.
2. Plat closes, legal does not match plat at curve C7. Area is good.
3. Show how all the adjoining streets were dedicated.
4. Minor line over text issues.
5. Looks good as a preliminary plat.
6. Who own and maintains Tract A.
Active 1 Marc Virata 02/20/2008
38 Plat [2/22/08] Please correct the title on the first page of the plat (remove
"Center" and replace with "Park").
Resolved 1 Marc Virata 02/22/2008
39 Pond Maintenance [2/22/08] Since the pond will be a joint maintenance area, a maintenance
agreement with the master property owner will be needed prior to final plan
approval.
Active 1 Basil Hamdan 02/22/2008
40 Traffic [2/24/08] Please define the cross hatched area on the median ends, sheet
13/16.
Active 1 Ward Stanford 02/24/2008
41 Traffic [2/24/08] Please provide full dimensioning and signage on the S&S plan. Active 1 Ward Stanford 02/24/2008
42 Traffic [2/24/08] Please provide all existing lane striping and configuration at the
Tech Prkwy & Rock Crk, and Lady Moon & Precision intersections.
Active 1 Ward Stanford 02/24/2008
43 Traffic [2/24/08] The TIS indicates that the East bound left turn (EbL) at Lady Moon
and Harmony will be LOS F due to short term background growth. Using the
TIS's volumes and PHF in our current Harmony timing plan, the LOS is at D
or E depending on the evaluation method. Therefore the LOS is acceptable.
Active 1 Ward Stanford 02/24/2008
44 General [5/2/08] Please note that the Engineering Development Review Manager has
determined that there is $300 owed in TDR Fees from the PDP.
Active 2 Marc Virata 05/02/2008
3/7/2011 Page 7
Project: HARMONY TECH PARK, 3RD FILING, CUSTOM BLENDING PDP - TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
45 Detention Pond
Landscaping
[5/6/08] Thank you for providing adequate landscaping for the detention pond
on Tract A. The lower portion of the pond is to be planted with a wetland
seed mix, will there be sufficient water in this pond to sustain wetland
vegetation ? If not what would be done to address that.
Active 2 Basil Hamdan 05/06/2008
46 Plat [5/7/08] The "sight visibility easement" specified on the plat and other
documents should be called out as a "sight distance easement" on the
various documents. In addition, please provide our standard sight distance
easement language on the plat.
Active 2 Marc Virata 05/07/2008
47 Construction
Drawings
[5/7/08] Please update the details in LCUASS, many of the details are not
the current version.
Active 2 Marc Virata 05/07/2008
48 Construction
Drawings
[5/7/08] The typical road sections sheet seems to have the Precision Drive
cross section shown incorrectly at the future sidewalk would be in the 11'
parkway delineation.
Active 2 Marc Virata 05/07/2008
49 General [5/7/08] As a heads-up, the additional width in Technology Parkway that
encompasses the center turn lane which was previously a median, is not
reimbursable from street oversizing.
Active 2 Marc Virata 05/07/2008
50 Utility Plans [5/7/08] Why is the storm drainage being discharged into the pond through a
subdrain system and a level spreader ?
Active 2 Basil Hamdan 05/07/2008
51 Construction
Drawings
[5/7/08] Please add additional spot elevations at the PI per LCUASS 7-28. Active 2 Marc Virata 05/07/2008
52 Construction
Drawings
[5/7/08] The use of a cross pan at the high point of a flowline (Tech Parkway
and Precision) is odd and technically not to standard. Can it just be
eliminated? Perhaps in general it might be better not to build the curb return
at the west leg of this intersection since it may not be a public street or a
street for that matter with future development.
Active 2 Marc Virata 05/07/2008
53 Water/Wastewater [5/8/08] Water main from Rock Creek to Precision to be 24". Active 2 Roger Buffington 05/08/2008
54 Water/Wastewater [5/8/08] Add 24" butterfly valve at point of connection near Rock Creek. Active 2 Roger Buffington 05/08/2008
3/7/2011 Page 8
Project: HARMONY TECH PARK, 3RD FILING, CUSTOM BLENDING PDP - TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
55 Water/Wastewater [5/8/08] Use joint restraint for the water main lowerings rather than thrust and
gravity blocks. Provide calc's on the required restrained lengths on each side
of the lowerings and label clearly on the plans. Add a note (as outlined in the
redlines) regarding MEGALUGS or pre-approved equal.
Active 2 Roger Buffington 05/08/2008
56 Water/Wastewater [5/8/08] Label lengths of pipe between valves, fittings, etc, etc. Active 2 Roger Buffington 05/08/2008
57 Water/Wastewater [5/8/08] Add butterfly valve, air release valve and tracer wire (2) details. Active 2 Roger Buffington 05/08/2008
58 Water/Wastewater [5/8/08] See redlined plans for other comments. Active 2 Roger Buffington 05/08/2008
59 Plat [5/14/08] n order to promote compliance with Sections 12-120, 12-121 and
12-122 of the City Code related to Resource Conservation, a note must be
placed on the Project Development Plan (PDP) site plan alerting future
Propert Owners Associations of private property owner rights to use resource
saving devices or techniques under certain conditions.
Said note shall read:
Private Conditions, Covenants, and Restrictions (CC&R's), or any other
private restrictive covenant imposed on landowners within the development ,
may not be created or enforced which has the effect of prohibiting or limiting
the installation of xeriscape landscaping, solar/photo-voltaic collectors (if
mounted flush upon any established roof line), clothes lines (if located in back
yards), odor-controlled compost bins, or which has the effect of requiring that
a portion of any individual lot be planted in turf grass.
Active 2 Dana Leavitt 05/14/2008