Final Compliance Review
This is a request for a transit facility without repair or storage, known as the South Transit Center, PDP, to be located southwest of South College
Avenue and Harmony Road, just south of the Spradley Barr dealership (northwest of West Fairway Lane and Fossil Boulevard). The proposed
development is on approximately 4.3 acres, directly adjacent to the BNSF Railroad and the Mason Corridor Trail. The site is in the Commercial (C)
Zone District.
The site would be the south terminus of the Mason Corridor. Mason Street is proposed to extend to the site, from the north, along the railroad tracks.
The Mason Street Extension will only be used by the rapid transit buses; users will access the site via Fossil Boulevard or pedestrians can access the
site via the existing Mason Corridor Trail that runs adjacent to the railroad tracks.
The proposal includes a 169 space park-n-ride lot, 11 bus bays and a 4,253 square foot building. A north/south drive is provided along the east side
of the site, as designated by the South College Access Control Plan. It will serve to give the sites to the east and north access to Fairway Lane and
College Avenue, the future location of a traffic signal.
The proposal includes two modification of standard requests; one to the orientation to connecting walkway standard, which requires the front of a
building open directly onto a connecting walkway with pedestrian frontage that does not pass a vehicle use area; and the second is to the build-to line
standard, which requires structures be located within 15 feet of the adjoining street right-of-way.
Received Certification of Mineral Estate Owner Notification - Administrative Hearing notice published 11/10/2010
Project Type:
Project Desc:
File ID: 9-10/A Planner: Emma McArdle DMS Project Num: CP102241
ID Topic Issue Status Round Comment By Initial Date
1 Electric Utility [1/6/11]
[5/3/10] The location of electric facilities, including the electric transformer,
coordinated with Light & Power Engineering. Also need a Commercial
Service (C-1) form completed, and the name/address of who to invoice for
the Light & Power development charges. Please contact Light & Power
Engineering at (970)221-6700.
Resolved 1 Doug Martine 05/03/2010
2 zoning [5/7/10] The site plan is too cluttered. Please remove the topo lines Resolved 1 Peter Barnes 05/07/2010
3 zoning [5/7/10] Need to show distance from building envelope to lot lines. A
distance is shown to the north, south and west lot lines, but the distances
shown aren't to the envelope line.
Resolved 1 Peter Barnes 05/07/2010
4 zoning [5/7/10] Need a trash enclosure detail. Resolved 1 Peter Barnes 05/07/2010
5 zoning [5/7/10] 6 handicap parking stalls are shown, which is the minimum number
required. Is that enough?
Resolved 1 Peter Barnes 05/07/2010
3/7/2011 Page 1
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
6 zoning [6/18/10] Applicant indicates that they'll provide quantities with final submittal.
That's ok with Zoning as long as it's a condition of approval of the PDP.
[5/7/10] The landscape legend needs to indicate the quantity of each tree,
shrub, etc.
Resolved 1 Peter Barnes 05/07/2010
7 zoning [5/7/10] Are the covered bike racks covered by something other than the
overhead canopy? If so, need elevation drawings of structure.
Resolved 1 Peter Barnes 05/07/2010
8 zoning [6/18/10] The crosswalk should be labeled on the plan i.e. "raised", "painted"
or what?
[5/7/10] The main pedestrian connection/sidewalk in the south portion of the
site is mainly at the west side of the lot. An additional connection should
occur further east, near where the existing sidewalk along the access road
curves west. Need to label the name of the access road on the various
plans. Is it Fossil Blvd.?
Resolved 1 Peter Barnes 05/07/2010
9 zoning [5/7/10] It's advisable to remove a few of the southernmost parking spaces in
the east parking aisle in order to eliminate a possible vehicular conflict
situation where cars wanting to enter the lot have to wait while cars backing
out of the subject parking spaces maneuver out of the stall to exit. A situation
where cars are having to wait will create a bottle neck, and even delay
arriving buses.
Resolved 1 Peter Barnes 05/07/2010
10 Water and Sanitation [5/13/10] These comments entered for Fort Collins - Loveland Water District,
representative Terry W Farrill, District Engineer. The proposed water line
must be looped per previous discussions. The fire hydrant laterals and the
fire line nust be separated lines from the main.
Resolved 1 Emma McArdle 05/13/2010
11 Water and Sanitation [5/13/10] The District will require easements on the District's standard
easement form, for all facilities that are not located with in the public ROW.
The District requires minimum 30 foot and 20 foot wide easements for the
sanitary sewer lines and water lines, respectively.
Resolved 1 Emma McArdle 05/13/2010
12 Water and Sanitation [5/13/10] The general notes shall included the following:
-All water line construction shall conform to the Fort Collins - Loveland Water
District Standards and Specifications current to the date of construction.
- All sanitary sewer line construction shall conform to the South Fort Collins
Sanitation District Standards and Specifications current to the date of
construction.
Resolved 1 Emma McArdle 05/13/2010
3/7/2011 Page 2
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
13 Water and Sanitation [5/13/10] The District's signature block is required on the sheet G01. The
signature block may be obtained in the CAD format by contacting Ms. Sue
Vest at (970)226-3104, extension 107.
Resolved 1 Emma McArdle 05/13/2010
14 Water and Sanitation [5/13/10] The connection to the existing manhole is to be core drilled. Resolved 1 Emma McArdle 05/13/2010
15 Water and Sanitation [5/13/10] T Resolved 1 Emma McArdle 05/13/2010
16 Water and Sanitation [5/13/10] The location and size of the domestic meter pit needs to be shown. Resolved 1 Emma McArdle 05/13/2010
17 Water and Sanitation [5/13/10] The District does not allow trees, tree canopies or landscaping
within the District's easement or within 10 feet of the District Facilities.
Resolved 1 Emma McArdle 05/13/2010
18 Water and Sanitation [5/13/10] The District's typical fire hydrant installation, gate valve installation,
thrust blocks, and meter pit installation are to be included in the drawing set.
The typicals may be obtained in CAD format by contacting Mis. Sue Vest at
(970)226-3104, extension 107.
Resolved 1 Emma McArdle 05/13/2010
19 Water and Sanitation [5/13/10] The sanitary sewer line needs to be shown in profile. Resolved 1 Emma McArdle 05/13/2010
20 Water and Sanitation [5/13/10] The District will require another round of review due to the nature
and number of the above comments. Please do not hesitate to contact me at
226-3104, extension 104, if you have any questions or require additional
information.
Resolved 1 Emma McArdle 05/13/2010
21 Site Plan [5/13/10] Site plans should be a quick easy way to see what the development
plan is, this is way too busy, please take grading, existing landscaping, and
drainage details off, this information is all shown on separate plans.
Resolved 1 Emma McArdle 05/13/2010
22 Site Plan [5/13/10] This size development should be able to fit on a single sheet, I
prefer one sheet to the two provided.
Resolved 1 Emma McArdle 05/13/2010
23 Site Plan [5/13/10] North arrow and scale should be under the plan it refers to, right
not it looks to be associated with the Vicinity Map.
Resolved 1 Emma McArdle 05/13/2010
24 Site Plan [5/13/10] Vicinity map needs to be a line map and should show more context. Resolved 1 Emma McArdle 05/13/2010
3/7/2011 Page 3
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
25 Site Plan [5/13/10] "T" will not work for the trash enclosure, please show actual shape,
dimensions, and details with elevations.
Resolved 1 Emma McArdle 05/13/2010
26 Site Plan [5/13/10] Title shoule be City of Fort Collins South Transit Center, PDP
(Project Development Plan). PDP is not necessary to spell out, unless you
want to, it will be removed on the Final Plan anyway.
Resolved 1 Emma McArdle 05/13/2010
27 Site Plan [5/13/10] I would prefer the use of fills for different paving, planting beds,
landscaping, etc. rather than initials. I've provided an example plan.
Resolved 1 Emma McArdle 05/13/2010
28 Site Plan [5/13/10] Existing vs proposed should be different line weights, ie - Mason
Trail.
Resolved 1 Emma McArdle 05/13/2010
29 Site Plan [5/13/10] Is there a need for a Building Envelope? The building placement is
proposed, I don't think it is necessary. The plan shows the Building Envelope
and Overhead Canopy as the same line.
Resolved 1 Emma McArdle 05/13/2010
30 Site Plan [5/13/10] Easements should be shown on Site Plan. Resolved 1 Emma McArdle 05/13/2010
31 Site Plan [5/13/10] Approximately 150' of context should be shown, ie adjacent
property lines, ROW.
Resolved 1 Emma McArdle 05/13/2010
32 Landscape Plan [5/13/10] I would really prefer this to all be on one sheet, I think it will still be
legible.
Resolved 1 Emma McArdle 05/13/2010
33 Landscape Plan [5/13/10] Bus examples can come off Landscape Plan. Resolved 1 Emma McArdle 05/13/2010
34 Landscape Plan [5/13/10] Is there a canopy over all the plantings around the building? Please
label if so. Will these trees and plantings survive under a canopy?
Resolved 1 Emma McArdle 05/13/2010
35 Landscape Plan [5/13/10] Please provide a section view of the landscaping along the east
property line. This landscape area should be at least 30" high to screen the
parking lot.
Resolved 1 Emma McArdle 05/13/2010
36 Landscape Plan [5/13/10] Existing vs. proposed should vary in line weights. Resolved 1 Emma McArdle 05/13/2010
3/7/2011 Page 4
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
37 Landscape Plan [7/28/10]
[6/16/10] Assuming this requirement is met at Final Compliance, the note will
address my concerns.
[5/13/10] Please include a table with all trees types and species called out
and number and percentage of total trees listed meeting LUC 3.2.1((D)(3)
Minimum Species Diversity.
Resolved 1 Emma McArdle 05/13/2010
38 Utility Plan [6/22/10] The city signature block is required to be in the lower right hand
corner of ALL sheets within the utility plan set with the exception of the plat
since it it for reference only. See section 3.2.3 in LCUASS for information on
the title block requirements.
[5/14/10] Please add the City signature block to all sheets in the Utility Plan
set.
Resolved 1 Andrew Carney 05/14/2010
39 Utility Plan [5/14/10] Remove "PDP Submittal" from the title of the Utility Plan. Resolved 1 Andrew Carney 05/14/2010
40 Utility Plan [6/22/10] The provided General Notes are incomplete. Please include all of
the notes as well as the project specific information in notes 19 and 48. Also,
note 44 is missing and the text you have provided at the start of the notes
should not have been copied, please remove it. Lastly, please put the notes
pages directly after the cover sheet in the set.
[5/14/10] Please add the General Notes and the General Construction Notes
to the Utility Set. (See Appendix E-1-FC/LAR and E-2 of LCUASS).
Resolved 1 Andrew Carney 05/14/2010
41 Utility Plan [6/22/10] On several of the sheets more information was included, however
the information does not appear to be complete. In many instances, incorrect
linestyles are used and/or lines are not labeled. Please CLEARLY label
everything.
[5/14/10] Please show more off-site context on all sheets. It is difficult to tell
what the surrounding properties/areas are as existing.
Resolved 1 Andrew Carney 05/14/2010
42 Utility Plan [6/22/10] Spot elevations not provided for lot corners. See II. D. in the
LUCASS Utility Plan Checklist.
[5/14/10] Add finish grade elevations for streets, lots corners, and finish
floors/top of foundation of buildings for all lots. (See II. D. in the LUCASS
Utility Plan Checklist)
Resolved 1 Andrew Carney 05/14/2010
3/7/2011 Page 5
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
43 Utility Plan [6/22/10] Note was not added to the Erosion Control Plan - please add it.
[5/14/10] Add the following note to the Grading and Drainage and Erosion
Control plan sheets. "The top of foundation elevations shown are the
minimum elevations required for protection from the 100-year storm."
Resolved 1 Andrew Carney 05/14/2010
44 Utility Plan [5/14/10] The Utility sheet only shows the southern portion of the site. Please
carefully review Section III. In the Utility Plan Checklist and provide all of the
required information.
Resolved 1 Andrew Carney 05/14/2010
45 Utility Plan [5/14/10] As discussed at Conceptual Review, this property is subject to the
South College Access plan which shows a access circulator through this site
tying the existing public street (Fossil Blvd) to the property to the North where
the access circulator then returns to College in the Ultimate Condition. This
connection is not required to be a public street however the development of
this site can not preclude the connection from happening in the future.
Resolved 1 Andrew Carney 05/14/2010
46 Site Plan [5/14/10] Please add a date table showing when the plan was originally
prepared and then include future revision dates.
Resolved 1 Emma McArdle 05/14/2010
47 Landscape Plan [5/14/10] Following a Transportation Coordination meeting the week of May
3rd, it is Staff's consensus that they prefer the parking lot and drive aisle that
was originally submitted on the Conceptual Review Plans. This will be
discussed in greater detail at our meeting, but the any changes that are made
regarding the parking lot circulation will likely have an impact on the parking
lot landscaping, therefore, my comments WILL change if the plan changes.
Resolved 1 Emma McArdle 05/14/2010
48 Landscape Plan [7/28/10]
[6/16/10] This standard only applies to parking lot perimeter landscaping,
you've added more trees than would be required, but due to the mod of
standard request for less interior parking lot landscaping, I think the extra
trees are needed to make up for those missing on the interior.
[5/14/10] 3.2.1(E)(4)(a) requires 1 tree per 40' linear feet along a side lot line.
The side property line is 460', which requires 12 trees, only 10 are on the
plan.
Resolved 1 Emma McArdle 05/14/2010
3/7/2011 Page 6
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
49 Landscape Plan [7/28/10]
[6/17/10] A Modification of Standard Request has been submitted for this
section. Please revise the request to initially call out what the intent of the
standard is and how this plan deviates from that. Right not it just starts with a
justification, but for a hearing officer or the public that does not know what the
standard is the way it is written currently makes it hard to understand.
[5/14/10] Parking lots with more than 100 spaces shall consist of at least
10% of interior landscaping, which is apx 5,428 s.f. for this proposal. The
plan only has apx 2,614 s.f. of landscaping, please increase the interior
landscaping to meet the standard.
Resolved 1 Emma McArdle 05/14/2010
50 Landscape Plan [7/28/10]
[6/22/10] I think we need to clarify the parking lot landscaping information on
the plan. Please see redlines. Some islands are hindered by lighting, but
there are at least 2 on the north side of the site that can accommodate trees.
I still don't think that there are enough trees shown to meet the requirement.
[5/14/10] All landscape islands shall have a canopy shade tree. Code
requires 1 canopy shade tree per 150 s.f. of interior parking lot landscaping.
With the 10% requirement of 5,428 s.f. of interior landscaping the parking lot
shall have a minimum of 36 shade trees. (3.2.1(E)(5)(b))
Resolved 1 Emma McArdle 05/14/2010
51 Landscape Plan [5/14/10] Canopy Shade trees need at least 80 s.f. of ground area per tree,
please make sure all landscape islands are at least 80 s.f.
Resolved 1 Emma McArdle 05/14/2010
52 Site Plan [5/14/10] Why not switch the sidewalk and planting areas on the central
parking lot islands. This will help get more landscaping and decrease paved
area.
Resolved 1 Emma McArdle 05/14/2010
53 Landscape Plan [5/14/10] Trees are required along parking lot walkways at 1 per 40'. (this
applies along the west side of the parking lot)
Resolved 1 Emma McArdle 05/14/2010
54 Landscape Plan [5/14/10] The LUC has many tree requirements, remember 1 tree can be
counted for more than just one standard, so though it may sound like you
need apx 60 trees in the parking lot alone, that is not necessarily true if you
place trees in a way that they can meet more than one standard. ** Where
conflicts arise regarding tree placement and lighting we can make
exceptions.
Resolved 1 Emma McArdle 05/14/2010
3/7/2011 Page 7
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
55 Landscape Plan [5/14/10] Please add some landscaping around the trash enclosure. 3.2.1(E)
(6)
Resolved 1 Emma McArdle 05/14/2010
56 Landscape Plan [5/14/10] Check lights and placement of trees, many are too close. Resolved 1 Emma McArdle 05/14/2010
57 Site Plan [5/14/10] I recommend delineating the pedestrian walk ways through the
drive aisle and parking lot by using a raised walk or special paving. (3.2.2(D)
(2) and 3.2.2(E)(5).
Resolved 1 Emma McArdle 05/14/2010
58 Site Plan [5/14/10] Please show the 2' overhang for parking spaces as a typical. Resolved 1 Emma McArdle 05/14/2010
59 Site Plan [6/16/10] Why not take advantage of the possiblity to get more spaces on
this site by having some compact spaces?
[5/14/10] Are there any Compact Parking spaces? These may account for
40% of your spaces and be 8' wide as opposed to 9,' they would need to be
labeled.
Resolved 1 Emma McArdle 05/14/2010
60 Landscape Plan [5/14/10] I'm concerned about the trees and plantings underneath the
overhang. Tell me more about this.
Resolved 1 Emma McArdle 05/14/2010
61 Lighting Plan [6/22/10] The LLF should be 1, please revise plans.
[5/14/10] Please tell the Light Loss Factor on the plans, without this the
numbers mean nothing.
Resolved 1 Emma McArdle 05/14/2010
62 Lighting Plan [6/22/10] Please add a note saying this on the plan.
[5/14/10] Not clear from the plan where the ELI lights are, the plan says to
refer to the elevations, but I don't see them on the elevations either.
Resolved 1 Emma McArdle 05/14/2010
63 Lighting Plan [5/14/10] The notes on the 2nd page confuse me, the Note Specific to
Scheduled Luminaires says to refer to the notes, but the the 2 notes below
are discussing the ELIs not EPS.
Resolved 1 Emma McArdle 05/14/2010
64 Lighting Plan [5/14/10] I don't find anything saying the fixtures will be downward facing and
have glare shields. The table says the ELI will be mounted on the surface, I
need more information, please show locations on plan. Will all ELI be under
the canopy? Please darken the line showing where the canopy ends.
Resolved 1 Emma McArdle 05/14/2010
3/7/2011 Page 8
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
65 Lighting Plan [5/14/10] Please darken site boundary, take indoor detail off, there is more
site detail on this plan than on the site plan regarding paving, don't need it
here.
Resolved 1 Emma McArdle 05/14/2010
66 Plat [5/17/10] Please finish the Plat, see submittal requirements:
http://www.fcgov.com/currentplanning/pdf/pdp_submittal_req_10-09.pdf.
This includes:
-Name and addresses of owner, applicant, engineer and surveyor;
- Show ROW dimensions,
- Label Zoning on this and adjacent properties,
- Names of adjacent Subdivisions,
- Designation of any areas of floodplain, and
- Show easements.
Resolved 1 Emma McArdle 05/17/2010
67 Elevations [6/22/10] Maybe I just don't know the terminology, but can you clarify that
Alum. Storefront are windows and add color information to all finishes, ie.
Stained and Painted, what color?
[5/17/10] I like the color plans for review, but I will need to make sure they
are legible in black and white also, please submit black and white next time or
include both. Also, black and white plans label the colors of each material.
Resolved 1 Emma McArdle 05/17/2010
68 Elevations [5/17/10] Please label the heights and dimensions of the elements on each
façade. (see redlined plan for examples)
Resolved 1 Emma McArdle 05/17/2010
69 Elevations [6/22/10] Please add note indicating that if anything is mounted on the roof
that it will be screened from view.
[5/17/10] Will there be any vents or equipment on the roof?
Resolved 1 Emma McArdle 05/17/2010
70 Elevations [5/17/10] There are several call outs (A-D and 8-17), please add description
of what there are.
Resolved 1 Emma McArdle 05/17/2010
71 Elevations [5/17/10] Planters are shown on the site plan, please label these on the
elevation sheet.
Resolved 1 Emma McArdle 05/17/2010
72 Planning Objectives [5/17/10] What will the conference room be used for in the facility? Who will
run the coffee shop? City or private? What are the hours of the building?
Who will use the offices?
Resolved 1 Emma McArdle 05/17/2010
3/7/2011 Page 9
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
73 Planning Objectives [5/17/10] What is the plan for complying with the Raptor Nest Survey
recommendations? When will the "presence/absence survey" be done?
Resolved 1 Emma McArdle 05/17/2010
74 Modification
Requests
[5/17/10] The Modification Requests must also addess if the modification
would be detrimental to the public good (end of 2.8.2(H) Step 8).
Resolved 1 Emma McArdle 05/17/2010
75 Landscape Plan [5/18/10] Please check the Plant List. Resolved 1 Emma McArdle 05/18/2010
76 Plat [5/18/10] The boundary & legal close. Resolved 1 Jeff County 05/18/2010
77 Plat [5/18/10] Please correct "Weld County" in the legal description, to "Larimer
County".
Resolved 1 Jeff County 05/18/2010
78 Plat [5/18/10] Please add "East Line of the NE 1/4 of Section 2-6-69 to the plat.
See redlines.
Resolved 1 Jeff County 05/18/2010
79 Plat [5/18/10] Please change "Burlington Northern Santa Fe Railroad" to "BNSF
Railway", to match the legal description.
Resolved 1 Jeff County 05/18/2010
80 Existing Conditions
Plan
[5/18/10] There is incomplete text on the Existing Conditions Plan. Resolved 1 Jeff County 05/18/2010
81 Landscape Plan [5/18/10] There is incomplete text on sheet 1 of the Landscape Plans. Resolved 1 Jeff County 05/18/2010
82 Tree Mitigation Plan [5/18/10] There are several line over text issues on the Tree Mitigation Plan. Resolved 1 Jeff County 05/18/2010
83 Utility Plan [5/18/10] We were not routed a Utility Plan set. We will need to review them. Resolved 1 Jeff County 05/18/2010
84 Utility Plan [6/22/10] The stormline plan needs to show a stormline profile complete with
proposed line grades, depths, and lengths. Also, please clearly show what is
proposed to be cut, patched, or replaced. If a segment of pavement or
sidewalk is to be replaced it needs to be shown as a darker lineweight. See
redlines.
[5/18/10] On the Storm water plan please show the grading (existing and
proposed), how the stormline is tying into the existing, any off-site easements
that are needed, as well as, any street cuts/patches that are required.
Currently, there is very little detail on the sheet.
Resolved 1 Andrew Carney 05/18/2010
3/7/2011 Page 10
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
85 Landscape Plan [5/18/10] Are you aware of the Landscape Design Standards and Guidelines
for Stormwater and Detention Facilities? Please see this document regarding
the design of the detention pond. It addresses:
- varying slope,
- plantings,
- LA required construction plans,
- etc.
Resolved 1 Emma McArdle 05/18/2010
86 Utility Plan [6/22/10] For the most part, more off-site context was included, however
much more detail is needed for the proposed stormline layout and outfall.
There isn't any proposed grading shown for the outfall and very little existing
grading. See redlines.
[5/18/10] All of the sheets in the Utility Plan could use more off-site context
and background information. It is very difficult to understand the surrounding
conditions and how this design will tie in.
Resolved 1 Andrew Carney 05/18/2010
87 Water Conservation [5/18/10] Comments entered for Lauri D'Audney, Water Conservation
Specialist.
- Landscape Plan needs to show applicable hydrozones,
- A water budget chart shall be included, which shall not exceed 15 gallons
per square foot over the site.
Resolved 1 Emma McArdle 05/18/2010
88 Stormwater [5/18/10] The rainfall intensities used to calculate the quantity detention are
not consistent with the City of Fort Collin's current rainfall criteria. Please
revise the intensities.
Resolved 1 Wes Lamarque 05/18/2010
89 Stormwater [5/18/10] Due to the intensities being incorrect, the quantity detention
required is more than the required detention stated in the drainage report.
The design did provide 1 foot of freeboard with detention for the extra foot.
This additional volume does make up for the extra volume required. One foot
of freeboard is not needed below the pond spillway. The invert of the spillway
can be set at 5008.1, which is the elevation where the volume equals 1.35
ac-ft. The 1-foot freeboard requirement is from the invert of the spillway to
the top of the berm and the lowest opening of any structures.
Resolved 1 Wes Lamarque 05/18/2010
90 Stormwater [5/18/10] Please provide 10 feet separation from the storm sewers to any
trees.
Resolved 1 Wes Lamarque 05/18/2010
3/7/2011 Page 11
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
91 Stormwater [6/23/10] Reminder Comment.
[5/18/10] Onsite drainage easements or alignments are needed for the limits
of the detention pond and storm sewers.
Resolved 1 Wes Lamarque 05/18/2010
92 Stormwater [2/1/11] Please submit a copy of finalized and signed off-site easements with
mylars.
[7/30/10] Reminder Comment.
[6/23/10] Reminder Comment.
[5/18/10] Offsite drainage easements are required for the portion of the
detention pond offsite and for any portion of the outfall storm sewer that is on
private property and not within an existing drainage easement. Where an
offsite drainage easement is required, a letter of intent is all that is required
before the public hearing.
Active 1 Wes Lamarque 05/18/2010
93 Stormwater [7/30/10] Please show and label the depth gage on the grading and drainage
plan.
[5/18/10] A detention pond depth gage is required for ponds deeper than 4
feet.
Resolved 1 Wes Lamarque 05/18/2010
94 Stormwater [6/23/10] Does a conflict exist with the existing storm sewer?
[5/18/10] Please provide more detail for the outfall. This includes property
lines, topo, etc.
Resolved 1 Wes Lamarque 05/18/2010
95 General [5/18/10] On Existing Conditions Plan and Tree Mitigation Plan identify the
trees containing raptor nests. You will not be able to remove a tree with an
"active nest." You will need to add a note identifying appropriate construction
timing. Note that great horned owls typically nest earlier than other raptors.
Resolved 1 Erica Saunders 05/18/2010
96 Planning Objectives [5/18/10] How are you addressing the recommendations in the Raptor Nest
Survey?
Resolved 1 Erica Saunders 05/18/2010
97 General [5/18/10] What are you going to do with the existing structures (house, deck,
shed) on-site? Please consider deconstruction as a means to recycle
construction materials and reduce the amount of debris being transported
and dumped at the County landfill.
Resolved 1 Erica Saunders 05/18/2010
3/7/2011 Page 12
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
98 Fire [2/1/11] One additional correction is needed. The site plan still shows an
"EAE" (Emergency Access Easement) and it needs to be changed to
Emergency Access Alignment. The plat is correct.
[7/27/10] The Emergency Access Alignment is perfect on the plat. As we
discussed, it has to be an alignment, not an easement, since it's city-owned
property. Thank you.
[6/22/10] Thanks for showing the Emergency Access Easement on your
documents. Just a reminder that approved signage will need to be in place
prior to issuance of a CO.
Just a reminder to include the EAE when you show easements on future
documents.
Active 1 Carie Dann 05/19/2010
99 Fire A 6-inch "water service" line is shown. Is that supposed to be the Fire Line? If
so, please label as such; if not, please show location of the Fire Line.
Active 1 Carie Dann 05/19/2010
100 Utility Plan [6/22/10] The Access circulator design through the site is acceptable to
engineering. However, because this is a city property, and the city can not
grant easements to itself, all of the "Easements" on the site needs to be
called "Alignments". The process and end result is the same, however, they
will all need to be called out as Alignments not Easements on both the utility
plans as well as the Plat.
[5/19/10] The Access circulator through the site will need to be in an Access
Easement. Please show this and any other easements on site such as the
Emergency Access Easement on the Utility Sheet.
Resolved 1 Andrew Carney 05/19/2010
3/7/2011 Page 13
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
101 Utility Plan [5/19/10]
Species list:
Dont use:
Red Sunset Maple
Autumn Blaze Maple
Brandywine Crab
Newport Plum
Additional shade trees to use on this project:
Bur Oak
Chinkapin Oak
Hackberry
Catalpa
Skymaster English Oak
Additional ornamental trees to use on this project:
Canyon Maple
Adams Crabapple for Brandywine
Thunderchild Crabapple for Newport Plum
Hotwings Tatarian Maple for Tatarian Maple
Japanese Tree Lilac
The minimum species diversity of a maximum of 15% of any tree type needs
to be applied for this project.
Mitigation:
109 Mitigation trees have been identified. Note number 2 on sheet 1 of 2
states that only 64 trees are to be upsized for mitigation. Final plan needs to
identify upsized trees.
Tree Spacing:
To get all the mitigation trees on this project and hopefully some of the trees
that will be transplanted, close spacing appears to be necessary. Applicant
should try to provide for these minimum spacings between trees. To get all
the mitigation trees on site that may not be possible.
Active 1 Tim Buchanan 05/19/2010
3/7/2011 Page 14
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
Shade trees 20 feet
Conifers 12-15 feet
Ornamental trees 12 feet
Plant Notes:
Plant note number 18 should delete the word street, which is the 11th word of
the statement.
All of the 7 tree protection statements under 3.2.1 G should be placed in the
plant notes.
Tree Transplanting:
Thirty four trees are shown to be transplanted. Those to be kept on site need
to be identified. Others should be labeled for off site tree transplanting.
A plant note should be added on tree transplanting:
The City Forester will make a final determination of which of tree trees
located in the groups are suitable for transplanting. Tree transplanting
method and season shall be approved by the City Forester.
102 Utility Plan [5/20/10] After a Transportation Coordination meeting on 5-20, several
conclusions have been made regarding the overall site layout and the
location of the Access Circulator within the site. Staff is Okay with the Access
Circulator going through the site, provided that some treatment of the through
movement be done to show that it is a through movement and not only a
drive isle. Also, provide access point(s) to the property to the East so that in
the future when they develop they have access to the circulator. As the
design is submitted with the next round of review, staff will review and
comment.
Resolved 1 Andrew Carney 05/20/2010
103 General [5/21/10] Show cross access point on plans to business to North. Build
pedestrian connection to business to North. Example use, customers can
drop off vehicle for service and take BRT north while vehicle is being
serviced.
Resolved 1 Jennifer Petrik 05/21/2010
3/7/2011 Page 15
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
104 General [5/21/10] When using attached walks, width needs to be 6 to include shy
distance. Add sidewalks for pedestrian connection from SE of site. See
redlines. Suggest adding a pedestrian crossing from pedestrians accessing
site from south to connect to internal walkway. See redlines.
Resolved 1 Jennifer Petrik 05/21/2010
105 General [5/21/10] Please specify appropriate size of cobble along Mason Trail to
ensure cobble does not spill out onto Mason Trail.
Resolved 1 Jennifer Petrik 05/21/2010
106 General [5/21/10] South access control rail on site plan should be pointing to
railings.
Resolved 1 Jennifer Petrik 05/21/2010
107 General [5/21/10] Ensure a strong E/W pedestrian spline from property to east
through site to transit center. See South College Corridor Plan for example
illustration.
Resolved 1 Jennifer Petrik 05/21/2010
108 General [5/21/10] If possible, please show rumble strips and lighting for Mason Trail
users on plans as work done by others to ensure this element is not lost.
Resolved 1 Jennifer Petrik 05/21/2010
109 General [5/21/10] Colored concrete bike route please add pedestrians to this label. Resolved 1 Jennifer Petrik 05/21/2010
110 General [5/21/10] Ramp at south of site may be mislabeled. This may be a light
rather than a ramp.
Resolved 1 Jennifer Petrik 05/21/2010
111 General [5/21/10] Per meeting 5/20/10 please stripe drive isle connector similar to
property to the North to show visual cue that this is intended as a drive
through connection.
Resolved 1 Jennifer Petrik 05/21/2010
112 General [5/21/10] Per meeting 5/20/10 please provide access easement along east
property line for future connection from property to the east to the connector
drive isle. Provide at least 3 potential access points. When this property
develops and the exact location of these access points can be negotiated.
Resolved 1 Jennifer Petrik 05/21/2010
113 Utility Plan [6/22/10] Please add LCUASS details: 701, 702, 1201, 1601, 1602, 1603,
1606, 1606(a), 1607. Also, why is some of the text in the details bolded? It is
difficult to read, please do not bold that text. Please ensure that all of the
details are the most recent edition, some of the dates are from 2000.
[5/21/10] Site details are needed for the utility plan set. Please see Appendix
A in LCUASS for all of the applicable details.
Resolved 1 Andrew Carney 05/21/2010
3/7/2011 Page 16
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
114 Utility Plan [6/22/10] If you wish to use a single abbreviations sheet for the set it is OK,
however there are several linestyles that are incorrect. Please use the correct
linestyles.
[5/21/10] For this site, would it be cleaner to do away with the general
abbreviations sheet and simply call out what is needed on each sheet? It is a
fairly straight forward plan and having to refer back to a master list that is
much bigger than needed seems wasteful. Also, there is plenty of room on
each page for a small legend.
Resolved 1 Andrew Carney 05/21/2010
115 Utility Plan [6/22/10] Spot elevations are still missing. See redlines and checklist item II.
D. for what is required.
[5/21/10] On the grading sheet, many spot elevations are needed. See the
checklist (Appendix E-4) item II.D. for what spot elevations are needed. Also,
please make the property lines much darker. The background lineweight is
also too light and will not scan properly.
Resolved 1 Andrew Carney 05/21/2010
116 Utility Plan [6/22/10] The lineweight still needs some work. Grey scale is acceptable
however it appears that there are only two lineweights (dark and light). Feel
free to look at any utility plan set that has been accepted by the city for
reference. The Union Place Development is a good example of a site that is
of similar size.
[5/21/10] On most sheets the lineweight needs some work. Please show
whatever is proposed as a dark lineweight and what is existing as a lighter
lineweight that what is proposed. The current existing conditions lineweight is
too light and will not meet the city's scanning criteria. Also, please show
property lines etc as the darker weight.
Resolved 1 Andrew Carney 05/21/2010
117 Utility Plan [5/21/10] The stormline that is shown proposed to drain into the Red Tail
Development needs more detail. Will the street need to be cut and patched?
If so show the approx. limits of the cut. Also there are no grading lines
(existing or proposed) shown for most of the lines path. Please show more
detail about this connection and how exactly it will tie into what is existing.
Resolved 1 Andrew Carney 05/21/2010
3/7/2011 Page 17
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
118 Utility Plan [6/22/10] The C&G along Fossil Blvd is within the area shown for the
proposed storm line. This C&G will need to be replaced as well as sidewalk if
it is disturbed. Also, since the C&G along Fossil Blvd at the intersection with
Fairway Ln. is being torn up, the installation of Handicap Ramps may be
required.
[5/21/10] Is the curb and gutter along Fairway Ln. and Fossil Blvd. being
reconstructed? If not, please do not show it in a proposed lineweight.
Resolved 1 Andrew Carney 05/21/2010
119 Utility Plan [5/21/10] The utility sheet needs some work. Currently only a portion of the
site is displayed on the sheet so I have not been able to review the entire
sheet. Please show the whole site on the Utility sheet. See the Utility plan
checklist for details on what is required on utility sheet.
Resolved 1 Andrew Carney 05/21/2010
120 Utility Plan [6/22/10] It is still not shown or called out where the existing street ends and
what is proposed at the end of the existing Fossil Blvd. Is any of what will
need to be built within existing ROW?
[5/21/10] On all sheets in the Utility set, please show where existing Fossil
Blvd ends and if any street cuts and/or patches are required for the new
utilities.
Resolved 1 Andrew Carney 05/21/2010
121 Utility Plan [6/22/10] Note not added to the Utility sheet.
[5/21/10] Please add the following street cut note to the Utility and Grading
sheets:
"Limits of street cut are approximate. Final limits are to be determined in the
field by the City Engineering Inspector. All repairs to be in accordance with
the City street repair standards."
Resolved 1 Andrew Carney 05/21/2010
122 Utility Plan [5/21/10] Please see redlines for additional comments/concerns. Resolved 1 Andrew Carney 05/21/2010
3/7/2011 Page 18
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
123 Utility Plan [6/22/10] Again, this set needs some drastic work before it can be accepted
by the city. I have tried to identify the major issues and provide much
feedback with my redlines. Again, feel free to contact me if you have any
questions regarding the Utility Plan requirements, I am more than happy to sit
down and discuss them with you.
[5/21/10] Overall, the Utility plan set needs some work. Please take another
look at the Utility Plan checklist provided in Appendix E-4 of LCUASS to see
what exactly is required. I have tried to identify the majority of the big issues
with this round, however the set needs some work before the next round.
Please don't hesitate to contact me if you have any questions.
Resolved 1 Andrew Carney 05/21/2010
124 Utility Plan [6/21/10] Please provide an update on the status of the traffic signal at Hwy
287 and Fairway.
Resolved 2 Jennifer Petrik 06/21/2010
125 Utility Plan [6/21/10] The following comments are from Engineering Inspection:
1) The utility plan needs a sheet containing the stormline profiles with grades.
2) Is it possible to move the stormline manhole out of the sidewalk along the
detention pond? Not having the manhole directly in the walk is preferred.
3) Please add handicap ramps at all cross-walk locations as well as the
handicap ramp details from LCUASS.
4) The South fire hydrant line is also labeled as a fire line. The line is shown
as just a hydrant line.
Resolved 2 Andrew Carney 06/21/2010
126 Utility Plan [6/22/10] The PE stamp and signature is only required on the final mylars,
not on each submittal.
Resolved 2 Andrew Carney 06/22/2010
127 Utility Plan [6/22/10] Before printing mylars, remove all the text in the revision block. Resolved 2 Andrew Carney 06/22/2010
128 Utility Plan [6/22/10] The two standard text notes that you have attached to the signature
block are only required on the cover sheet. Please remove them from the
other sheet. Also, they are not required to be attached to the signature block.
Resolved 2 Andrew Carney 06/22/2010
129 Utility Plan [6/22/10] Add "(For Reference Only)" to the plat sheet since the plat within
the utility set will not be signed. Also, the plat should be located after the
notes sheet within the utility set. See cover sheet and plat sheet redlines.
Resolved 2 Andrew Carney 06/22/2010
3/7/2011 Page 19
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
130 Utility Plan [6/22/10] As mentioned earlier, all easements on this site need to be labeled
as "Alignments" not Easements. See redlined plat for these changes. Also, it
would be cleaner and easier to dedicate all the onsite Alignments on the plat
instead of dedicating them by separate document which has additional fees
associated with each dedication. All the off-site dedications will still need to
be done via separate document.
Resolved 2 Andrew Carney 06/22/2010
131 Utility Plan [6/22/10] The general notes sheets (General Construction Notes and the
General Notes) should be located directly after the cover sheet in the Utility
Set. See notes sheets for redlines.
Resolved 2 Andrew Carney 06/22/2010
132 Utility Plan [6/22/10] The grading plan is showing some off-site grading on the property
to the East. This grading will require a temporary construction easement form
that property owner unless the grading can be revised to stay within the
property. If a easement is required, a letter of intent will also be required prior
to hearing.
Resolved 2 Andrew Carney 06/22/2010
133 Utility Plan [6/22/10] Spot elevations are still needed on the grading plan for the lot
corners. See redlines.
Resolved 2 Andrew Carney 06/22/2010
134 Utility Plan [6/22/10] On the Utility sheet, a enlarged detail of the proposed drainage
outfall into the Redtail development is needed to show what exactly is
proposed and how this design will tie into Redtail Phase 2. Existing and
proposed grading is required as well as outfall elevations and how exactly this
design will work in the interim and ultimate conditions as Redtail constructs
their improvements. Much more detail is needed in this enlargement showing
the surrounding conditions and what Redtail Phase 2 will be constructing.
However since grading lines are not required on the utility sheet this
enlargement may be better suited for the Grading sheets. Removing the
grading lines from the utility plan will allow more clarification of lines and
make for a cleaner plan. Also, be sure to include both the existing conditions
with ample labeling as well as the ultimate Redtail Phase II improvements
called out as such.
Resolved 2 Andrew Carney 06/22/2010
135 Utility Plan [6/22/10] A drainage/construction easement may be required for the
proposed storm outfall into the Redtail development. If so, a letter of intent is
also required prior to hearing.
Resolved 2 Andrew Carney 06/22/2010
3/7/2011 Page 20
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
136 Utility Plan [6/22/10] The proposed outfall must coordinate with the Redtail Phase 2
design. It appears that the stormline is currently shown going through a
building envelope.
Resolved 2 Andrew Carney 06/22/2010
137 Utility Plan [6/22/10] Quite a bit more detail is needed to show what is proposed for the
storm outfall. See redlines for additional comments.
Resolved 2 Andrew Carney 06/22/2010
138 Utility Plan [6/22/10] It appears that the installation of the stormline in Fossil Blvd is
require the removal of the C&G along Fossil Blvd. Handicap ramps will be
required to be installed along Fossil Blvd at the time of re-construction. Also,
since the sidewalk along the north side of Fossil Blvd is the main pedestrian
connection to the site, a mid block handicap ramp is encouraged on Fossil
Blvd on the North side of the street. See redlines.
Resolved 2 Andrew Carney 06/22/2010
139 Utility Plan [6/22/10] Label the width of all existing and proposed sidewalks. Resolved 2 Andrew Carney 06/22/2010
140 Utility Plan [6/22/10] Where is the existing ROW along Fossil Blvd and Fairway Lane? It
is missing, mis-labeled, or difficult to tell.
Resolved 2 Andrew Carney 06/22/2010
141 Elevations [6/22/10] What does D.S., TYP mean? Active 2 Emma McArdle 06/22/2010
142 Elevations [6/22/10] The shadows may not be good for scanning purposes, but I'll leave
that up to Technical Services to address.
Active 2 Emma McArdle 06/22/2010
143 Water and Sanitation [6/22/10] These comments are entered in for Terry Farrill, with Fort Collins -
Loveland Water District and the South Fort Collins Sanitation District. Sheet
C08 shows three proposed sections of the sanitary sewer line extension. The
length and pipe diameter of the proposed sections are 146 LF of 8 inch, 171
LF of 8 inch and 163 LF of 4 inch. On sheet C09 the las section is shown as
161 feet of 8 inch. The discrepancy needs to be corrected.
Resolved 2 Emma McArdle 06/22/2010
144 Water and Sanitation [6/22/10] There may be vertical conflicts between the proposed water,
sanitary sewer and the storm water at the south end of the project.
Resolved 2 Emma McArdle 06/22/2010
145 Utility Plan [6/22/10] An enlarged detail of the portion of the site at the end of the
currently constructed Fossil Blvd is needed to show what is proposed to
happen to the curb line, the existing crown of the road and the proposed
transition into the site, and the proposed sidewalk connection to the North.
See redlines.
Resolved 2 Andrew Carney 06/22/2010
3/7/2011 Page 21
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
146 Utility Plan [6/22/10] If the proposed sidewalk along the detention pond was a public
sidewalk in ROW we would require that 1 foot behind the walk be flat before
the 4:1 grading took place to ensure pedestrian safety. Since this is not a
public sidewalk we can not require that 1 foot however is anything similar
proposed to ensure pedestrian safety?
Resolved 2 Andrew Carney 06/22/2010
147 Utility Plan [6/22/10] What is proposed to happen to the existing bike path at the
Northwest corner of the detention pond? The plan shows some concrete in
the pond. See redlines.
Resolved 2 Andrew Carney 06/22/2010
148 Utility Plan [6/22/10] Are the sidewalk chases under the existing bike path existing or
proposed? If proposed please call them out as such and include the
appropriate sidewalk chase detail from Stormwater.
Resolved 2 Andrew Carney 06/22/2010
149 Utility Plan [6/22/10] There are many locations on the Utility set that have the incorrect
linestyle which is identified as a property line. See redlines and revise.
Resolved 2 Andrew Carney 06/22/2010
150 Utility Plan [6/22/10] Is the western most storm inlet proposed to be within the sidewalk?
If so what will it be draining? Shouldn't it be along the curb line?
Resolved 2 Andrew Carney 06/22/2010
151 Utility Plan [6/22/10] Handicap ramps are required at all pedestrian crossings on the
site. See redlines.
Resolved 2 Andrew Carney 06/22/2010
152 Utility Plan [6/22/10] The proposed fire hydrants are shown as being in the bus drive
isle. Is this correct?
Resolved 2 Andrew Carney 06/22/2010
153 Utility Plan [6/22/10] An enlarged detail would be helpful to identify what exactly is
proposed at the Northwest corner of the site. Please identify how the existing
sidewalk is going to change and who exactly will be constructing the bus
guide way. Are any of these areas in existing easements? If any off-site work
is proposed with this plan set a off-site construction easement will be needed
as well as a letter of intent prior to hearing. This area needs some
clarification as it is currently not clear what is proposed. See redlines. After
a discussion at the Staff Review meeting on 6-23 it appears that no off-site
work is proposed at this location with this project. This is by far the cleanest
option, please show via lineweight and callouts that all of this work is to be
performed by others and the BRT project and no off-site work is proposed
with this utility set.
Resolved 2 Andrew Carney 06/22/2010
3/7/2011 Page 22
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
154 Utility Plan [6/22/10] The North arrow on the Utility sheet is incorrect, please revise. Resolved 2 Andrew Carney 06/22/2010
155 Utility Plan [6/22/10] A Type III barricade is required at the end of the access circulator
and the sidewalk on the North end of the site.
Resolved 2 Andrew Carney 06/22/2010
156 Utility Plan [1/27/11] Carried forward as a reminder that the off-site utility easement will
need to be recorded prior to final plan approval.
[7/27/10] Carried forward as a reminder that the letter of intent is needed
prior to hearing and the utility easement will need to be recorded by separate
document prior to final plan approval.
[6/22/10] The proposed water line connection through the property to the
North will require a utility easement and a letter of intent prior to hearing.
Active 2 Andrew Carney 06/22/2010
157 Utility Plan [6/22/10] Who is the owner of the overhead line running East/West on the
Southern portion of the site? It may need to be undergrounded. After a site
visit on 6-23 it appears that this line is no longer current. Remove the OHU
line from the utility plan
Resolved 2 Andrew Carney 06/22/2010
158 Utility Plan [6/22/10] Please call out the widths of all proposed and existing sidewalks
and drive isles.
Resolved 2 Andrew Carney 06/22/2010
159 Utility Plan [6/23/10] Grading lines are not required on the Utility sheet. See comment
#134. Removing the grading from the utility sheet will clean up the sheet
drastically and make for a cleaner looking sheet. However, if this is done, the
grading details for the proposed storm outfall and the end of Fossil Blvd will
need to be done on the grading plan since grade lines are required for those
details.
Resolved 2 Andrew Carney 06/23/2010
160 Utility Plan [6/24/10] After a site visit on 6-23 it appears that there is an existing storm
inlet on the East curb line near where the proposed stormline passed under
the NW corner of Fossil Blvd and Conjoes Rd. Please show this inlet and
how the proposed line will impact and/or tie into this existing structure. See
redlines.
Resolved 2 Andrew Carney 06/24/2010
161 Utility Plan [6/24/10] On the Utility sheet there are several locations where text is
displayed that is not needed. I have tried to make a note of all of them on the
redlines. Please remove text that is not needed.
Resolved 2 Andrew Carney 06/24/2010
3/7/2011 Page 23
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
162 Utility Plan [6/24/10] In numerous locations on many sheets there are water meter
symbols that are clearly not water meters. Please remove.
Resolved 2 Andrew Carney 06/24/2010
163 Utility Plan [6/24/10] . Resolved 2 Andrew Carney 06/24/2010
164 Utility Plan [6/24/10] Overall, I have tried to encapsulate the majority of the major
comments and concerns in these comments, however there are quite a few
more issues with the Utility Set that I have noted as redlines on the plans
themselves. I have checked and corrected them as much as feasible at this
point, however once the plans are cleaned up and the appropriate information
is displayed new comments regarding the design may be made in later
rounds.
Resolved 2 Andrew Carney 06/24/2010
165 Utility Plan [6/25/10] The tree transplanting and mitigation plan was re-reviewed in the
field on 6-25-10. Orange flagging was placed on 37 trees for transplanting.
The previous count for trees to transplant was 33. Mitigation trees required
were reduced to 98 pending the final determination if 3 large trees are
transplantable. We reviewed minimum spacing between transplanted
evergreen trees with a contractor and determined the minimum spacing
needs to be 10 feet between transplanted trees. The landscape architect
needs to contact the City Forester to discuss these changes and plans to
transplant some trees off-site if necessary. Ornamental trees can be used for
mitigation.
Active 2 Tim Buchanan 06/25/2010
166 Plat [6/25/10] The Plat boundary & legal close. Resolved 2 Jeff County 06/25/2010
167 General [6/25/10] The 2 Utility Easement & 1 Drainage Easement boundaries &
legals close.
Active 2 Jeff County 06/25/2010
168 Site Plan [6/25/10] Please change the Railroad name to "BNSF Railway" on the Site
Plans & Existing Conditions Plan, to be consistant with the Subdivision Plat.
Resolved 2 Jeff County 06/25/2010
169 Utility Plan [6/25/10] There are line over text & text over text issues on the Utility Plans
sheets C04, C05, C06, C07 & C10.
Resolved 2 Jeff County 06/25/2010
3/7/2011 Page 24
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
170 Plat [7/27/10] We are leaving comment #170, with the understanding that this
Subdivision Plat will be filed after the purchase of the property at the
southwest corner.
[6/25/10] 6/25/10- We talked with Emma McArdle about the small tract at the
southwest corner of the property. The City is in the process of purchasing
this. The soonest the City would have title is September. It would be nice to
include this in the plat, but would require the boundary to change.
Active 2 Jeff County 06/25/2010
171 Stormwater [2/1/11] This needs to be discussed further.
[7/30/10] The drainage report now states 1.22 ac-ft is provided. This can be
resolved at final compliance.
[6/25/10] The drainage report states that 1.19 ac-ft of detention is required.
When adding the quantity detention and quality detention stated in the report,
1.29 ac-ft results in being required. Please revise.
Active 2 Wes Lamarque 06/25/2010
172 Stormwater [6/25/10] What is the field inlet near the southern end of the outlet storm
sewer for? Is this proposed or existing? There is an existing detention pond
located in this area with an existing outlet structure.
Resolved 2 Wes Lamarque 06/25/2010
173 Utility Plan [6/25/10] Please correct the direction of the north arrow on sheet C06, and
add a north arrow to sheet C10.
Resolved 2 Jeff County 06/25/2010
174 Utility Plan [7/26/10] All Transportation Planning comments have been addressed. Active 3 Jennifer Petrik 07/26/2010
175 Fire PFA's comments and requirements are resolved at this time. Active 3 Carie Dann 07/27/2010
176 Plat [7/27/10] The Subdivision Plat legal & boundary close. Resolved 3 Jeff County 07/27/2010
177 General [7/27/10] The 2 Utility Easement boundaries & legals close. Active 3 Jeff County 07/27/2010
178 General [1/31/11] This easement was not included in this round of review, so it could
not be checked.
[7/27/10] There is an error in the Tract D Retail utility easement legal. Please
change "PCC - Point of Compound Curvature" to "PRC - Point of Reverse
Curvature". See redlines.
Active 3 Jeff County 07/27/2010
179 Plat [7/27/10] Please make sure that all reception numbers for off site easements
are shown on the Subdivision Plat prior to mylars.
Active 3 Jeff County 07/27/2010
3/7/2011 Page 25
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
180 Utility Plan [7/27/10] ] On the proposed detail showing how this project will tie into the
end of existing Fossil Blvd, the sawcut needs to be perpendicular to the traffic
direction. See redlines for some additional minor comments and questions.
Active 3 Andrew Carney 07/27/2010
181 Utility Plan [7/27/10] Once a letter of intent for the proposed off-site utility easement is
received, Engineering is ready for hearing.
Resolved 3 Andrew Carney 07/27/2010
182 Utility Plan [7/27/10] Directional handicap ramps are required at all locations. See
redlines.
Resolved 3 Andrew Carney 07/27/2010
183 Utility Plan [1/27/11] If the plat is to be filed after the purchase of the property the
easements should actually be alignments because at the time of platting they
will be on City property.
[7/27/10] On the plat there are still two drainage easements being shown on
the southern portion of the site. If this area is being purchased and becoming
a part of the south transit center property, they do not need to be dedicated
via separate document and can be dedicated as utility alignments on the plat.
Active 3 Andrew Carney 07/27/2010
184 Utility Plan [7/27/10] See redlines for additional minor comments. Resolved 3 Andrew Carney 07/27/2010
185 Stormwater [2/1/11] Reminder for next submittal.
[7/30/10] At final compliance, please provide a basin summary table on the
drainage plan. This should include as sub-basins and their areas, c-factors,
flows for the 2 and 100-year storm.
Active 3 Wes Lamarque 07/30/2010
186 Stormwater [2/1/11] Reminder for next submittal.
[7/30/10] At final, please include a pond summary table on the drainage plan.
This should include quantity detention required and proposed, water quality
required and proposed, 100-year HWL, and release rate.
Active 3 Wes Lamarque 07/30/2010
187 Stormwater [2/1/11] Not completed.
[7/30/10] At final, please show and label an emergency spillway on the
grading and drainage plan. The spillway can be set at an elevation of
5007.70, which will give you the required volume. The berm should be set at
5008.7, which gives you a foot freeboard. The spillway should be sized to
take the 100-year developed flow for the site with a flow depth of 6 inches.
This will give another 6 inches of clearance to the top of berm.
Active 3 Wes Lamarque 07/30/2010
3/7/2011 Page 26
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
188 Stormwater [7/30/10] The project should use the following tree protection notes on the
landscape plan.
Tree Protection Notes
1. Within the drip line of any protected existing tree there shall be no cut or
fill over a four-inch depth unless a qualified arborist or forester has evaluated
and approved the disturbance.
2. All protected existing trees shall be pruned to the City of fort Collins tree
management standards for thinning and cleaning.
3. Prior and during construction, barriers shall be erected around all
protected existing trees with such barriers to be of orange fencing a minimum
of four (4) feet in height, secured with metal T-posts, no closer than six (6)
feet from the trunk or at the drip line, which ever is greater, There shall be no
storage or movement of equipment, material, debris or fill within the fenced
tree protection zone. Modification of protective fence locations to
accommodate construction shall be approved by the City Forester prior to
moving or erecting a protective fence,. Where the drip line of trees touch or
overlap, place fence around groups of trees.
4. During construction there shall be no cleaning of equipment or materials
or the storage and disposal of waste material such as paints, oils, solvents,
asphalt, concrete, motor oil or any other material harmful to the life of a tree
within the drip line of any protected tree or group of trees.
5. No damaging attachments, wires, signs or permits may be fastened to
any protected tree.
6. The installation of utilities, irrigation lines or any underground fixture
requiring excavation deeper than six (6) inches shall be accomplished by
boring under the root system of protected existing trees at a minimum depth
of twenty-four (24) inches. The auger distance is established from the face of
the tree (outer bark) and is scaled from the tree diameter at breast height as
described in the tree protection chart of the Fort Collins land use code section
3.2.1.
Active 3 Tim Buchanan 07/30/2010
3/7/2011 Page 27
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
7. Construction shall be performed in a manner to not damage any existing
tree. Clearance pruning of any tree on site shall only be by a Fort Collins
licensed arborist following City of Fort Collins tree management standards
under the direction of the City Forester.
8. Equipment access/drives shall be positioned to minimize travel over the
root system of any existing tree. Equipment drive locations over the root
system of any significant tree shall be approved by the City Forester with
requirements to protect the soil from being compacted. .
189 Water and Sanitation [2/2/11]
[8/3/10] These comments are entered for Terry Farrill with Fort Collins -
Loveland Water District and the South Fort Collins Sanitation District.
Active 3 Emma McArdle 08/03/2010
190 Water and Sanitation [2/2/11]
[8/3/10] The fire flow requirements need to be submitted to evaluate water
line sizing and connections.
Active 3 Emma McArdle 08/03/2010
191 Water and Sanitation [8/3/10] The Construction note E.1. on sheet G02 needs to be corrected to
indicate a minimum bury of 5 feet and the maximum bury of 6 feet.
Resolved 3 Emma McArdle 08/03/2010
192 Water and Sanitation [8/3/10] The meter pit needs to be shown. The meter pit cannot be located
in a traffic area or pedestrian traffic area.
Resolved 3 Emma McArdle 08/03/2010
193 Water and Sanitation [2/2/11]
[8/3/10] The District will require easements on the District's standard
easement form.
Active 3 Emma McArdle 08/03/2010
194 Water and Sanitation [8/3/10] The existing water line on sheet C08 is incorrectly identified as DI, it
is PVC.
Resolved 3 Emma McArdle 08/03/2010
195 Water and Sanitation [8/3/10] The proposed water line lowering on sheet C08 is too deep. Resolved 3 Emma McArdle 08/03/2010
196 Water and Sanitation [2/2/11] An outside drop manhole connection is required at the existing
manhole at 4+80.7. Both connections are to be core drilled.
[8/3/10] The proposed manhol connection is too be core drilled.
Active 3 Emma McArdle 08/03/2010
197 Water and Sanitation [8/3/10] All water line and sanitary sewer line crossings need to be identified
and shown on plan and profile.
Resolved 3 Emma McArdle 08/03/2010
3/7/2011 Page 28
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
198 Landscape Plan [8/3/10] Please take note 3 of the Landscape Plans, even though this project
is outside of the City's water/sewer service area, it still needs to meet the
City's approved Hydrazone and Water Budging requirements. An irrigation
plan must be submitted to water conservation meeting the City's Standards
prior to building permit.
Resolved 3 Emma McArdle 08/03/2010
199 General [8/3/10] The letters of intent and acknowledgement must be submitted to me
by August 10th to proceed with the August 24th hearing date. Please contact
me with any questions.
Resolved 3 Emma McArdle 08/03/2010
200 Utility Plan [1/27/11] On sheet C01, please label each cross section as "(On-Site)" to
ensure that there is no confusion that the sections are not in LCUASS and
are to be used only on-site.
Active 4 Andrew Carney 01/27/2011
201 Utility Plan [1/27/11] On the utility plan please call out each of the ADA ramps as to be
constructed according to LCUASS detail 1606 or simply add a note on the
utility sheet. See redlines.
Active 4 Andrew Carney 01/27/2011
202 Utility Plan [1/31/11] Just a reminder from the Engineering Inspector who is assigned to
this project that typically street cuts and sidewalk cuts and patches are to be
done perpendicular to the direction of travel. The patches shown on Conejos
road are not perpendicular so the actual patching will need to be altered
slightly. Also, the patches on Fossil Blvd may need to be enlarged/re-shaped
at the inspectors direction.
Active 4 Andrew Carney 01/31/2011
203 Utility Plan [1/31/11] Near the S end of storm line A where the existing fire hydrant is
proposed to be moved, does the water main continue down Fossil Blvd or is
the existing hydrant the end of the line? If the line continues on and needs to
be lowered, the proposed street cut will need to be enlarged. Please provide
more detail of what is happening as the lines cross and what exactly is
proposed to happen with the existing water line. See redlines.
Active 4 Andrew Carney 01/31/2011
204 Utility Plan [1/31/11] Construction note #18 is incomplete. Active 4 Andrew Carney 01/31/2011
205 Plat [1/31/11] The Subdivision Plat boundary & legal close. Active 4 Jeff County 01/31/2011
208 Utility Plan [1/31/11] Please add benchmark 5-96 as shown on sheet G01 of the Utility
Plans, to the cover sheet (G00) with the other benchmark.
Active 4 Jeff County 01/31/2011
3/7/2011 Page 29
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
209 Stormwater [2/1/11] The detention pond and all storm sewers need to be in a drainage
easement, not a utility easement. Please revise.
Active 4 Wes Lamarque 02/01/2011
210 Fire NEW PHONE NUMBER: Please change phone number for Carie Dann on
page 1 of the Utility Plan Set to 970-221-6574.
Active 4 Carie Dann 02/01/2011
211 Fire ADDRESS NUMERALS
Address numerals shall be visible from the street fronting the property, and
posted with a minimum six-inch high numerals on a contrasting background.
(Bronze numerals on brown brick are not acceptable). If the numerals are
mounted on a side of the building other than the side off of which it is
addressed, the street name is required to be posted along with the numerals.
2006 International Fire Code 505.1
Active 4 Carie Dann 02/01/2011
212 Fire FIRE SPRINKLERS: Per recent email communication, please discuss and
resolve fire-sprinkler issues with Joe Jaramillo from Poudre Fire Authority,
phone 219.5319 or jjaramillo@poudre-fire.org.
Active 4 Carie Dann 02/01/2011
213 Stormwater [2/1/11] The City's standard water quality outlet structure is required with
Detail D-46 included in the utility plans.
Active 4 Wes Lamarque 02/01/2011
214 Stormwater [2/1/11] A riprap detail is needed in the utiltiy plan set. Riprap needs to be
buried with temporary erosion control until the ground is stable.
Active 4 Wes Lamarque 02/01/2011
215 Stormwater [2/1/11] The storm sewer plan and profiles have a bunch of labeling errors
which make it hard to review. Please revise.
Active 4 Wes Lamarque 02/01/2011
216 Fire ALARM PANEL: Per recent email correspondence, please resolve the FACP
issue with Ron Gonazles, phone 970-219-5316, email
rgonzales@poudre-fire.org
Active 4 Carie Dann 02/01/2011
217 Utility Plan [2/1/11] On sheet C19, the Fossil Blvd Connection Detail needs some work.
The existing sidewalk will need to be removed to an existing joint line. The
city does not allow a sidewalk addition to create a "sliver" of concrete. Also,
15' radii curves are required in the transition, not abrupt angles. See redlines.
Active 4 Andrew Carney 02/01/2011
3/7/2011 Page 30
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
218 Utility Plan [2/1/11] On sheet C19, additional spot elevations are needed. Please provide
spot elevations at both EOAs and centerline at both ends of the transition, the
middle, as well as 10' back from the saw cut on the existing roadway. See
redlines.
Active 4 Andrew Carney 02/01/2011
219 Utility Plan [2/1/11] On sheet C19, on the Fossil Road detail, please label the existing
C&G and what will be removed.
Active 4 Andrew Carney 02/01/2011
220 Utility Plan [2/1/11] On sheet C19, remove the SD line after it exits the outlet structure,
there is no line there. Also, what is the grey dashed line, an UE? Please
label.
Active 4 Andrew Carney 02/01/2011
221 Utility Plan [2/1/11] Is there any subgrade material proposed for the pavement section or
will the 9in concrete pavement be laid directly onto bare ground? If so, please
indicate on the site cross sections.
Active 4 Andrew Carney 02/01/2011
222 Utility Plan [2/1/11] On the grading plan it is difficult to tell what the proposed grading is
to the east of the parking area to the property line. Please label any existing
grade lines.
Active 4 Andrew Carney 02/01/2011
223 Utility Plan [2/1/11] Why are there no proposed grade lines on the grading sheets?
Please show what is proposed.
Active 4 Andrew Carney 02/01/2011
224 Utility Plan [2/1/11] On the grading sheet, it appears that the barricade on the North end
of the site is mislabeled, please revise. See redlines.
Active 4 Andrew Carney 02/01/2011
225 Utility Plan [2/1/11] Are the proposed walks that cross the bus drive isles a different
material than the drives themselves or simply painted? Please clarify and
label as such on the planset.
Active 4 Andrew Carney 02/01/2011
226 Utility Plan [2/1/11] On sheets C04 and C05, what are the lines that I have marked?
Access and Utility alignments? Please label them.
Active 4 Andrew Carney 02/01/2011
227 Utility Plan [2/1/11] On all sheets that it is shown, please label the "future" C&G for the
BRT connection as such.
Active 4 Andrew Carney 02/01/2011
228 Utility Plan [2/1/11] On the utility sheet, some of the proposed lineweights are too dark
and bold to scan correctly. Please revise so they are scanable. They need to
be dark, but not so dark and bold that they are difficult to read.
Active 4 Andrew Carney 02/01/2011
3/7/2011 Page 31
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
229 Utility Plan [2/1/11] Overall, there are scanning issues on several sheets in the utility set
as a whole, please look carefully and ensure that everything is legible and
meets city scanning criteria
Active 4 Andrew Carney 02/01/2011
230 Water and Sanitation [2/2/11] The phone number for the Fort Collins- Loveland Water District on
sheet G00 is 226-3104, the number shown is the District's fax number.
Active 4 Emma McArdle 02/02/2011
231 Water and Sanitation [2/2/11] The words sanitary sewer and water need to be removed from
construction note #5 on sheet G01.
Active 4 Emma McArdle 02/02/2011
232 Water and Sanitation [2/2/11] Note #13 on sheet G01 needs to be deleted it is contrary to note E.1
on sheet G02.
Active 4 Emma McArdle 02/02/2011
233 Water and Sanitation [2/2/11] What is the purpose of the 8 inch water line lowering identified on
sheet C07?
Active 4 Emma McArdle 02/02/2011
234 Water and Sanitation [2/2/11] The 6 inch water line connection at 9+74.5 is to be made by cutting
in a tee. A valve is to be installed on the east and south side of the tee.
Active 4 Emma McArdle 02/02/2011
235 Water and Sanitation [2/2/11] The term "C900" in note #1 on sheet C09 should be deleted. Active 4 Emma McArdle 02/02/2011
236 Landscape Plan [2/2/11] The print on the plant list is hard to read, the letters blur together,
may want to consider something with more spacing.
Active 4 Emma McArdle 02/02/2011
237 Landscape Plan [2/2/11] Note 3 was added for the hearing, I need you to show me that the
trees meet the diversity requirements. Please give me a table with trees and
precentages of each that meet Section 3.2.1(D)(3).
Correction, the percentages are there, please take off existing transplanted
trees from the percentages included, you should not be dinged for not
meeting the % diversity due to existing/transplanted trees. Also, see
Forestry's comment about this.
Active 4 Emma McArdle 02/02/2011
238 Landscape Plan [2/2/11] I don't see what the ground cover is in planting areas, am I missing
this somewhere?
Active 4 Emma McArdle 02/02/2011
239 Landscape Plan [2/2/11] Please add a legend of the fills used on the 3rd sheet of the
Landscape Plan.
Active 4 Emma McArdle 02/02/2011
3/7/2011 Page 32
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
240 Site Plan [2/2/11] A bench is labeled "future bench," what does this mean. Will some
benches be built right away and others not?
Active 4 Emma McArdle 02/02/2011
241 Site Plan [2/2/11] Some fills not consistent, colored concrete not always filled. The
platform area confuses me, what are all the dotted lines? Are these paving
details?
Active 4 Emma McArdle 02/02/2011
242 Site Plan [2/2/11] I would prefer the use of less labels and more consitent use of fill.
All the labels make this messy and hard to read.
Active 4 Emma McArdle 02/02/2011
243 Site Plan [2/2/11] I would rather not see all the paving lines on the concrete walks, all
the lines makes it hard to read.
Active 4 Emma McArdle 02/02/2011
244 Site Plan [2/2/11] Please label the curb around the platform, is this a 1' - 2' curb, is it
consistently 1' or?
Active 4 Emma McArdle 02/02/2011
245 Site Plan [2/2/11] What's the curvy dotted line between the light posts? Active 4 Emma McArdle 02/02/2011
246 Stormwater [2/2/11] Please provide a detail for the low flow cobble channel in the bottom
of the detention pond. Drainage pans are normally required for slopes less
than 2%.
Active 4 Wes Lamarque 02/02/2011
247 Landscape Plan [2/2/11] An adjustment for the species diversity requirement should be made.
Since Shademaster Honeylocust and Skyline Honeylocust are technically the
same species reduce the combined quantity from 29 to 20 or fewer to meet
the 15% maximum requirement. Increase quantities of lesser used species
by the reduced quantity.
Add this note:
Prior to removing any trees on the site contact the City Forester for an on site
meeting to verify trees for removal and those for retention.
Active 4 Tim Buchanan 02/02/2011
248 Utility Plan [2/7/11] The vicinity map on the cover sheet of the utility plans will not scan
properly, please remove the background shading so that it will scan correctly.
Active 4 Andrew Carney 02/07/2011
3/7/2011 Page 33
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
249 Utility Plan [2/7/11] I see now that there is a utility easement needed at the corner of
Fossil Blvd and Conejos Road that is to be dedicated via separate document.
As with the other separate dedications, the applicable fees apply. Also, on the
utility sheet and the stormline detail sheet, please call out the easement as
being dedicated by separate document and recorded at reception #_____.
See redlines.
Active 4 Andrew Carney 02/07/2011
250 Utility Plan [2/7/11] Are there any C&G or sidewalk cuts/patches for the cornier of Fossil
and Conjeos roads? If so, show them.
Active 4 Andrew Carney 02/07/2011
251 Utility Plan [2/7/11] On both the Utility plan as well as the storm line detail sheets show
the existing 20' curb inlet structure that the proposed line will tie into.
Active 4 Andrew Carney 02/07/2011
252 Utility Plan [2/7/11] Please move sheet C19 (roadway and storm line detail sheets) to
before sheet C14 (standard detail sheets).
Active 4 Andrew Carney 02/07/2011
253 Utility Plan [2/7/11] Just a reminder that prior to final plan approval and DCP issuance,
the 4 required easements/allignments that are being dedicated by separate
document will need to be filed. Each dedication includes a TDRF dedication
fee of $250 (each), a signed and stamped legal that has been check by the
city's technical services department (if they have not already been checked),
a Deed of dedication filled out by the property owner, and a check for
recording the document at the county.
Active 4 Andrew Carney 02/07/2011
254 Utility Plan [2/7/11] Please see my redlines for clarification of any comments. Active 4 Andrew Carney 02/07/2011
255 Landscape Plan [2/9/11] I had staff look at the enhanced landscaping along the west end of
the site and you received a kudos for effort! Our new environmental planner
was very complementary about the size and quality of vegetation you have
chosen.
Active 4 Emma McArdle 02/09/2011
256 Landscape Plan [2/9/11] Please check formatting of notes on Site and Landscape Plans. Active 4 Emma McArdle 02/09/2011
257 Site Plan [2/9/11] I would prefer not seeing the utilitydetails such as vaults, inlets etc.
on the site plan. It is not necessary.
Active 4 Emma McArdle 02/09/2011
258 Site Plan [2/9/11] Check for repiticous labels. Active 4 Emma McArdle 02/09/2011
3/7/2011 Page 34
Project: SOUTH TRANSIT CENTER PDP- TYPE I AND FINAL PLANS
ID Topic Issue Status Round Comment By Initial Date
259 Elevations [2/9/11] Please call out the materials and color on the east and west
elevations more. See redlines for a few comments/questions.
Active 4 Emma McArdle 02/09/2011
3/7/2011 Page 35