HomeMy WebLinkAbout2900 S COLLEGE AVE AT & T - FDP190015 - SUBMITTAL DOCUMENTS - ROUND 2 - SUPPLEMENTAL INFORMATION (3)City of
Fort Collins
Water Engineering
& Field Services
Water Field Operations Hydrant Flow Test
Flow Test For: 2900 S College Ave.
Date: 08-09-19
Time: 1:00 PM
Flow Test Hydrant: 12347 Mfg. Mueller
Flowed Nozzle Size: 4.5
Flowed at: 30 PSI
Hose Monster Conversion Chart: 1830 GPM
Side Gauge Reading During Flow Test: 45 PSI
Static and Residual Hydrant: 12352 Mfg. Mueller
Static Reading: 72 PSI
Residual Reading During Flow Test: 68 PSI
Notes: John Marriott
VELOCITEL
Parker, CO 80134
Phone:303-840-1837
jarriott@Velocitel.com
DISCLAIMER
The above hydrant flow readings and information (readings) are from a single test performed at an arbitrary point
in time and as such are not and should not be assumed to be representative of typical or any specific water system
conditions. The City of Fort Collins (City) makes no representation of the readings' accuracy or representativeness.
The City disclaims any and all liability with respect to the readings and any use thereof. The readings are provided
for general information purposes only and are not intended to be used for any other or specific purpose, including
as the basis for the development of construction plans or any type of engineering. The readings are not guaranteed
to be accurate or suitable for any use. Any use of the readings and any conclusions drawn therefrom shall be
strictly the responsibility of the user, and not the City.
\\UFP\Utilities\WEFS\WEFS-Ops-Mgr\Templates WEFS\WFO Hydrant Flow Test Form Revision Date: July 17, 2018