Please see the following summary of comments from City staff and outside reviewing
agencies for your submittal of the above referenced project. If you have questions about
any comments, you may contact the individual commenter or direct your questions through
the Project Planner, Ted Shepard, at 970-221-6343 or tshepard@fcgov.com.
Comment Summary:
Department: Engineering Development Review
Contact: Marc Virata, 970-221-6567, mvirata@fcgov.com
Topic: Construction Drawings
Comment Number: 1 Comment Originated: 06/21/2016
06/21/2016: Please remove note #7 on the paving plan (C200). It reflects 6"
concrete paving in right-of-way, but technically 8" concrete paving is required for
the driveway out to Willow Street per LCUASS detail 707.2.
Comment Number: 2 Comment Originated: 06/21/2016
06/21/2016: The paving plan (C200) identifies proposed 30" curb and gutter for
the driveway removal along Linden Street. This area of Linden Street was built
with a wide curb head and I believe the total length of the curb and gutter is
greater than 30". Please indicate matching existing curb and gutter instead.
Comment Number: 3 Comment Originated: 06/21/2016
06/21/2016: The Storm Drain Plan and Profile Sheet C301 has a cover issue
of less than 3 feet from the top of the Willow Street roadway for a distance of
about 10 feet of the pipe into Willow Street. Alternatives to achieve the 3 foot
minimum cover would need to be explored.
Topic: Site Plan
Comment Number: 5 Comment Originated:
06/20/2016: Please change the project title on all sheets to "Lots 1 & 2, River
District Block Eight Mixed Use"
Comment Number: 6 Comment Originated:
06/20/2016: Some of the easement descriptions shown are incorrect. If they
are going to stay on the plan, they should match what is shown on the
Subdivision Plat.
Department: Traffic Operation
Contact: Nicole Hahn, 970-221-6820, nhahn@fcgov.com
Topic: General
Comment Number: 1
06/21/2016: No comments.
06/20/2016
06/20/2016
Comment Originated: 06/21/2016
Department: Water -Wastewater Engineering
Contact: Dan Mogen, 970-224-6192, dmogen@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 06/21/2016
06/21/2016: Please note that all City construction detail drawings are to be
used in their original, unaltered state. ANY modification(s) must be clearly
distinguished and all City logos/identifiers must be removed from the modified
detail. Detail drawings can be found in both .pdf and .dwg formats through the
links to "Construction Drawings" on www.fcgov.com/utility-development.
Comment Number: 2 Comment Originated: 06/21/2016
06/21/2016: Please see redlined utility plan.
Comment Number: 17 Comment Originated: 06/21/2016
06/21/2016: Please tie the coordinate values shown for utilities to the project
boundary. We would prefer that this be done by adding property corner values
to each sheet, or showing the property corner values on the horizontal control
plans and adding a note to each sheet with coordinate values.
Comment Number: 18 Comment Originated: 06/21/2016
06/21/2016: There is text that needs to be masked. Mask all text in hatched
areas. See redlines.
Topic: General
Comment Number: 14 Comment Originated: 06/20/2016
06/20/2016: BUILDING HEIGHT: Please change the project title on all sheets
to "Lots 1 & 2, River District Block Eight Mixed Use".
Comment Number: 15 Comment Originated: 06/20/2016
06/20/2016: SUN SHADE ANALYSIS: Please change the project title on all
sheets to "Lots 1 & 2, River District Block Eight Mixed Use".
Topic: Landscape Plans
Comment Number: 7
Comment Originated: 06/20/2016
06/20/2016: Please change the project title on all sheets to "Lots 1 & 2, River
District Block Eight Mixed Use".
Comment Number: 8 Comment Originated: 06/20/2016
06/20/2016: There is text that needs to be masked. Mask all text in hatched
areas. See redlines.
Comment Number: 9 Comment Originated: 06/20/2016
06/20/2016: There are line over text issues. See redlines.
Comment Number: 10 Comment Originated: 06/20/2016
06/20/2016: Please correct the title & number on sheet 4. See redlines.
Topic: Lighting Plan
Comment Number: 11
Comment Originated: 06/20/2016
06/20/2016: Please change the project title on all sheets to "Lots 1 & 2, River
District Block Eight Mixed Use"
Topic: Plat
Comment Number: 1 Comment Originated: 06/20/2016
06/20/2016: There is a missing call in the legal description. See redlines.
Comment Number: 2 Comment Originated: 06/20/2016
06/20/2016: Please add "Name" & "Title" to the signature blocks as marked.
See redlines.
Comment Number: 3 Comment Originated: 06/20/2016
06/20/2016: Please add new title commitment information as available.
Comment Number: 4
Comment Originated: 06/20/2016
06/20/2016: All reception numbers for documents recorded by separate
document, must be added prior to producing mylars.
R
Comment Number: 3
Comment Originated: 06/21/2016
06/21/2016: Please show how this site's release rate relates to Basin 102.
Please include an exhibit of Basin 102 showing the total area of the basin and
pro -rate the release for this site to show compliance with the basin's release
rate.
Comment Number: 4 Comment Originated: 06/21/2016
06/21/2016: Please provide complete analysis within the drainage report and
detail how the site will function with the StormTech system. The level of detail
should explain to the extent that someone unfamiliar with the site and
StormTech system would understand what is proposed; this may include
additional details within the plans as well.
Comment Number: 5 Comment Originated: 06/21/2016
06/21/2016: Please provide an easement for the underground treatment area.
Comment Number: 6
Comment Originated: 06/21/2016
06/21/2016: Please provide detail for the proposed tree wells and roof drain
connections.
Comment Number: 7 Comment Originated: 06/21/2016
06/21/2016: Please provide additional detail on the proposed spill containment
area. It is unclear from the grading plan how this would capture a spill. The
drainage report calls for a 1000-gallon cistern; however, no details for the
system are seen with the plans.
Contact: Jesse Schlam, 970-218-2932, ischiam@fcqov.com
Topic: Erosion Control
Comment Number: 1
Comment Originated: 06/16/2016
06/16/2016: Current Erosion Control Materials Submitted do not meet
requirements. Please submit; Erosion Control Plan (based upon latest
redlines), Erosion Control Report (please see redlines specifically around
contaminated sites) , and an Escrow / Security Calculation (May need to be
recalculated based upon plan redlines). If you need clarification concerning the
erosion control section, or if there are any questions please contact Jesse
Schlam 970-218-2932 or email @ jschlam@fcgov.com
Department: Technical Services
Contact: Jeff County, 970-221-6588, *county@fcgov.com
Topic: Building Elevations
Comment Number: 12
Comment Originated: 06/20/2016
06/20/2016: Please change the project title on all sheets to "Lots 1 & 2, River
District Block Eight Mixed Use".
Comment Number: 13 Comment Originated: 06/20/2016
06/20/2016: There are line over text issues. See redlines.
Topic: Construction Drawings
Comment Number: 16
Comment Originated: 06/20/2016
06/20/2016: Please change the project title on all sheets to "Lots 1 & 2, River
District Block Eight Mixed Use".
5
Comment Number: 5 Comment Originated: 06/22/2016
06/22/2016: Please re -word the note that explains why there is no off-street
parking. It's not exactly accurate to state that the T.O.D. does not require
parking. How about "Minimum required off-street vehicular parking in the T.O.D.
not in effect at the time of application."
Comment Number: 6
Comment Originated: 06/22/2016
06/22/2016: On the Lighting Plan, the FIN wall pack (quantity 20) appears to be
a contemporary and sleek fixture that is appropriate for most locations along the
southwest elevation (facing Mawson Lumber) and southeast (facing Kiefer
Concrete). But, where three of these fixtures are visible from Linden Street and
Willow Street, the fixtures appear to be mismatched with the character of the
building. Perhaps a wall pack along the streets could be selected that is
complementary to the building style.
Comment Number: 7 Comment Originated: 06/22/2016
06/22/2016: Along Willow Street, there is a symmetrical arrangement of 10
PSDNA wall packs. But at the gate to transformers at the rear of the building,
this consistency is interrupted by one FIN wall pack. Why not just continue the
PSDNA's at this location instead of introducing a very different looking fixture?
Comment Number: 8 Comment Originated: 06/22/2016
06/22/2016: 1 can't read the wall pack fixture along Willow Street along the front
building. Per the above comments, if this fixture is a FIN, please consider using
a PSDNA for consistency along Willow Street.
Comment Number: 9
Comment Originated: 06/22/2016
06/22/2016: On the Lighting Plan schedule, three of four fixtures are not
specified as to their Kelvin temperature. Please indicate that per the cut sheets
on Sheet 6, these temperatures should be noted as 3,000 degrees.
Comment Number: 10
Comment Originated: 06/22/2016
06/22/2016: On the Landscape Schedule, please indicate the size of the
mitigation trees.
Comment Number: 11 Comment Originated: 06/22/2016
06/22/2016: There are two Landscape Plan Sheet 3's. The detail sheet should
be Sheet 4.
Comment Number: 12
Comment Originated: 06/23/2016
06/23/2016: Regarding the Lighting Plan, it would be helpful if schedule
included information from the Department of Energy "Lighting Facts" which
establishes ratings for Backlight, Up -light and Glare.
Department: Stormwater Engineering
Contact: Dan Mogen, 970-224-6192, dmogen@fcgov.com
Topic: General
Comment Number: 2 Comment Originated: 06/21/2016
06/21/2016: Please see redlined drainage report and utility/grading plan.
4
Department: Light And Power
Contact: Ted Shepard, 970-221-6343, tshepard@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 06/22/2016
06/22/2016: Comcast would like to do joint trench with Light and Power.
Please contact Don Kapperman at Comcast and Janet McTague at Light and
Power for further details.
Department: PFA
Contact: Jim Lynxwiler, 970-416-2869, Ilynxwiler@poudre-fire.org
Topic: General
Comment Number: 1 Comment Originated: 06/08/2016
06/08/2016: FIRE PITS
Fire pits fueled by natural gas are allowed. Wood burning or smoke producing
fire pits are prohibited. Fire pits shall have a 10' separation to combustible
construction and/or vegetation. In particular, the fire pit shown on the West side
of Building 2 is placed against an exterior wall. At time of building plan review,
plans will need to show that this is addressed by a UL rated device for this
application and construction is noncombustible.
Department: Planning Services
Contact: Ted Shepard, 970-221-6343, tshepard@fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 06/22/2016
06/22/2016: Along the Willow Street side of the front building, the Landscape
Plan indicates a 6' Metal Fence" but the Architectural Elevations, Sheet 7,
indicates a wire mesh screen that is approximately 16 feet high. Please
resolve. Also, please indicate the color of this metal screen fence/wall. Staff
expects that given the quality of the two buildings and the character that is being
established along Willow Street, this fence/wall will be a wire mesh and not
chain link and be black or vinyl -clad with black coating. This fence/wall should
not be galvanized.
Comment Number: 2 Comment Originated: 06/22/2016
06/22/2016: Please further describe the fence at the rear property line. Is this
an existing fence that separates the site from Kiefer Concrete? Please further
describe this fence.
Comment Number: 3
Comment Originated: 06/22/2016
06/22/2016: The surface treatment of the Outdoor Dining area is described as
crusher fines. Is this accurate? This seems like an odd surface for this area.
Comment Number: 4 Comment Originated: 06/22/2016
06/22/2016: Please indicate the location of the enclosed bike parking spaces.
3
Comment Number: 4
Comment Originated: 06/21/2016
06/21/2016: The diagonal parking/striping shown on Willow Street in the
ultimate condition (cross section sheets and signing and striping sheet) should
be indicated as being for reference only and for illustrative purposes. Final
design for Willow Street might provide a different configuration of the striping
along Willow Street, including the diagonal parking (striping alternatives are
currently being looked at for the portion of Willow Street west of Linden Street.)
Comment Number: 5 Comment Originated: 06/21/2016
06/21/2016: The interim and ultimate (for reference only) roadway designs for
Willow Street are satisfactory provided that all parties agree that the local street
portion of pavement and subgrade along the frontage of Lots 1 & 2 will be
provided. A "temporary" subgrade design along Willow Street for the road
widening and curb & gutter/sidewalk, will be considered by our Director as part
of a proposed pavement design report.
Comment Number: 6
Comment Originated: 06/21/2016
06/21/2016: The design of the drive approach off of Willow Street should be
shown on the civil plans, and its conformance with the 707.2 detail. Please show
the proposed access ramp/truncated dome design on the plans as part of the
detail.
Topic: General
Comment Number: 7
Comment Originated: 06/21/2016
06/21/2016: The pre -hearing drawings were known as Lot 1, River District
Block Eight Mixed Use. Since the hearing, it appears that Lot 1 is now
subdivided into two lots (Lot 1 and Lot 2), with the development plan comprising
of Lots 1 and 2, with the plat also platting Lot 3. The drawings should be titled
Lots 1 and 2, River District Block Eight Mixed Use, to reflect the fact that the
associated final approval and vesting is for Lots 1 and 2 only, not Lot 3. Are
there any implications in general on the development plan now being for two
lots, which was previously only one lot?
Comment Number: 8 Comment Originated: 06/21/2016
06/21/2016: Additional comments may be provided after the 22nd, I'm out of
the office on the 22nd and won't be at staff review.
Department: Historic Preservation
Contact: Maren Bzdek, 970-221-6206, mbzdek@fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 06/24/2016
06/24/2016: On April 27, 2016, the Landmark Preservation Commission voted
to recommend approval for this project based on findings that included a water
tower that is compatible with the overall proportions of the associated distillery
buildings. The current elevations for the FDP indicate a proportional change
between the water tower and the buildings. Staff is looking at the implications
and rationale for this change. Because this issue may constitute a major change
to the plans that the LPC approved, it may require a return to the LPC if it can't
be resolved at the staff level. Please contact us asap to discuss.