HomeMy WebLinkAboutHANSEN FARM - FDP190010 - CORRESPONDENCE - RESPONSE TO STAFF REVIEW COMMENTS• Engineer: Marc Virata
Project Location: Located on the west side of Timberline Rd at Zephyr Rd
Project Description: This is a request for a Final Development Plan (FDP) for a portion of the Hansen Farm property located at the West side of S Timberline Rd
at Zephyr Rd (parcel #86071000002). The FDP includes 178 dwelling units (116 single-family detached and 62 single-family attached), a central open space, a
future park and internal trail connections and a regional trail along the northern boundary. The proposed project is located in the Low Density Mixed -Use
Neighborhood (LMN).
FOR OUTSIDE AGENCIES:
Our public records database is currently under renovation and new plans are not being uploaded at this time. I have attached the Plat and Site/Landscape Plans
for your review, but if you require additional submittal documents please email tbeane@fcgov.com.
Comments are due by June 181n
Please send your comments and redlines via email to the Development Review Coordinator at: tbeane@fcgov.com. Should you need assistance or have any
other questions, please contact the Development Review Coordinator prior to the meeting.
If additional submittal documents were requested and are not provided or if there are other issues with the electronic document routing, please notify me as
soon as possible.
Thanks,
Tenae Beane
Dcvelopuicut Rcvicw Coordinator
Community Development & Ncighborliood Services
City of fort Collins
tbcaiiC@lc"'ov.com
970-22.1 61 19
From: Chris Pletcher <chrisp@fclwd.com>
Sent: Friday, May 31, 2019 9:50 AM
To: Tenae Beane <tbeane@fcgov.com>
Subject: RE: ELECTRONIC DEVELOPMENT REVIEW ROUTING: Hansen Farm Round 2 FDP190010
Tenae —
I would like to see the revised utility plans — I had outstanding comments that needed resubmittal and review. Would you mind sending them over?
Thanks,
Chris
Chris Pletcher, P.E.
Contract District Engineer
Fort Collins - Loveland Water District
South Fort Collins Sanitation District
From: Tenae Beane <tbeane@fcgov.com>
Sent: Friday, May 31, 2019 8:38 AM
To: rosannharris@email.com; Chris Pletcher <chrisp@fclwd.com>; Willits, Brendan <bwillits@psdschools.ore>; Don Kapperman
<don kapperman@cable.comcast.com>; Mott, Kenneth <Kenneth.Mott@centurylink.com>; Stephanie Rich<stephanie.rich @xcelenergv.com>;
'mharrity@la rime r.org' <mharrity@la rimer.ore>; donna. m.gibeau@usps.gov; brentbartlett@fbepc.com
Subject: ELECTRONIC DEVELOPMENT REVIEW ROUTING: Hansen Farm Round 2 FDP190010
ELECTRONIC ROUTING
This email is to notify you that the following project has been routed for review.
Hansen Farm — FDP190010
Round: 2
Project Team
• Coordinator: Tenae Beane tbeane@fcgov.com
• Planner: Pete Wray
4
From: Tenae Beane <tbeane@fcgov.com>
Sent: Tuesday, June 18, 2019 3:17 PM
To: Chris Pletcher <chrisp@fclwd.com>
Subject: RE: ELECTRONIC DEVELOPMENT REVIEW ROUTING: Hansen Farm Round 2 FDP190010
Hi Chris,
I am just checking in to see if you have any comments for the Hansen Farm project (Round 2) or if your comment from Round 1 has been resolved with the
recent set of plans. Let me know when you have a chance!
Thanks,
Tenae Beane
De elopmcnt Review Coordinator
Community Development & Neighborhood Services
City of Fort Collins
ibCw1C'((1Ac ;ov.com
970-224-6119
From: Tenae Beane
Sent: Friday, May 31, 2019 10:02 AM
To: Chris Pletcher<chrisp@fclwd.com>
Subject: RE: ELECTRONIC DEVELOPMENT REVIEW ROUTING: Hansen Farm Round 2 FDP190010
Hi Chris,
Absolutely! I will be sending those through a secure portal for your review as they are too large to attached here. Let me know if you don't receive the file.
Thanks,
Tenae Beane
Developmcnt Review Coordinator
Community Development & Neighborhood Serviccs
City of Fort Collins
t1cane4f4rov.coni
970-221-6119
3
I would like to see a resubmitta Ion this project prior to approval.
Thanks,
Chris
Chris Pletcher, P.E.
Contract District Engineer
Fort Collins - Loveland Water District
South Fort Collins Sanitation District
From: Tenae Beane <tbeane@fcgov.com>
Sent: Tuesday, June 18, 2019 3:41 PM
To: Chris Pletcher <chrisp@fclwd.com>
Subject: RE: ELECTRONIC DEVELOPMENT REVIEW ROUTING: Hansen Farm Round 2 FDP190010
Ok, no problem! Thank you, Chris.
Tenae Beane
Development Rcview Coordinator
Conununity Development & Neighborhood Services
City of Port Collins
tbCWmCCPPcg'ov.com
970-22 1-6119
From: Chris Pletcher <chrisp@fclwd.com>
Sent: Tuesday, June 18, 2019 3:40 PM
To: Tenae Beane <tbeane@fcaov.com>
Subject: RE: ELECTRONIC DEVELOPMENT REVIEW ROUTING: Hansen Farm Round 2 FDP190010
I should be done with them this evening — looks like it will be a few minor comments.
Chris Pletcher, P.E.
Contract District Engineer
Fort Collins - Loveland Water District
South Fort Collins Sanitation District
Stephen Olt
From: Chris Pletcher <chrisp@fclwd.com>
Sent: Tuesday, June 18, 2019 6:28 PM
To: Tenae Beane
Subject: RE: ELECTRONIC DEVELOPMENT REVIEW ROUTING: Hansen Farm Round 2 FDP190010
Follow Up Flag: Follow up
Flag Status: Flagged
Tenae —
Here are my comments on Hansen Farm, FDP190010, Round 2:
Utility Plan Sheets:
1. OU1
a. Please clarify the source of water for the irrigation of landscape areas, and if it is coming from FCLWD, please show location, tap size and
backflow prevention device.
2. U1
3. U2
4. U4
a. The waterline radius at the elbow on Knobby Pine Drive is too tight at 300' for typical C900 pipe. Please revise to a radius that all C900 pipe
can meet.
b. Please specify the size and type of Air Valve on Happy Woodland Drive.
a. On Fallen Branch Drive between Knobby Pine and Floating Leaf, waterline radius is too tight at 300'.
a. On Burly Tree north of Zephyr, please specify the size and type of Air Valve.
Sanitary Sheets:
1. SS4 —Please provide a casing for the sanitary sewer at station 15+25 under the 24" RCP.
Detail Sheets:
1. Per the FCLWD Standard Construction Specifications, thrust blocks are allowed by approval only, except in locations where there is a connection to
an existing pipe. At existing pipes, thrust blocks are required in conjunction with mechanical joint restraints. All new pipe, including waterline
lowerings, shall be exclusively restrained with mechanical joint restraints. This applies to the thrust block detail and the waterline lowering detail.
2. On the Air & Vacuum Relief Valve detail, the District requests that the Brass Gate Valve be replaced with a Brass Ball Valve.