HomeMy WebLinkAboutCOVENTRY SUBDIVISION PRELIMINARY - 80 93 - SUBMITTAL DOCUMENTS - ROUND 1 - GEOTECHNICAL (SOILS) REPORTSWELL -CONSOLIDATION
LOAD (PSF)
500 1000 5000
Saturated at constant
pressure
►i
10000
SAMPLE OF <;1,Sauv-11 G,,p,f FROM TEST HOLE NO. Ia
AT DEPTH OF 2 -3 FEET NATURAL MOISTURE CONTENT I9,Z y, NATURAL DRY DENSITY Z FCF
zv
0 m
n
0
J
.J
J
W
v3i 4
2.
0.
`7
SWELL -CONSOLIDATION
LOAD (PSF)
500 1000 5000
Saturated at constant
pressure
SAMPLE OF Sa+tr GAo,-( FROM TEST HOLE NO._.17
AT DEPTH OF g> FEET NATURAL MOISTURE CONTENT �r� C % NATURAL DRY DENSITY
10000
Ilb.o PCF
o
m
c�
00
J
J
W
4
2.
0.
6\
`j
SWELL -CONSOLIDATION
LOAD (PSF)
500 1000 5000
Saturated at constant
pressure
10000
SAMPLE OF Suc'K'fol4i-lc_.,u-(cf-rofJr-FROM TEST HOLE NO.
AT DEPTH OF.___-7__9 FEET NATURAL MOISTURE CONTENT .__... �Z.,y� % NATURAL DRY DENSITY �og,o pCF
0
V.
•
SWELL -CONSOLIDATION
LOAD (PSF)
500 1000 5000
Saturated at constant
pressure
P]
SAMPLE OF FROM TEST HOLE NO. 1¢
AT DEPTH OF Z -3 FEET NATURAL MOISTURE CONTENT �c„ o % NATURAL DRY DENSITY
10000
117. (. PCF
O
O
n
t
0
SWELL -CONSOLIDATION
LOAD (PSF)
500 1000 5000
Saturated at constant
pressure
0]
z
0 4.
F
Q
o 6
z
0
U
SAMPLE OF Gt pn�c,-�oh�Fv
AT DEPTH OF (o --] FEET
10000
FROM TEST HOLE NO.
NATURAL MOISTURE CONTENT. ¢ �j % NATURAL DRY DENSITY jo4-.-7 PCF
0
7
a
n
0
c
z
0
D
0
z
m
z
c�
z
m
m
z
SWELL -CONSOLIDATION
LOAD (PSF)
500 1000 5000
Saturated at constant
pressure
K
10000
SAMPLE OF FROM TEST HOLE NO.
AT DEPTH OF 1-4— FEET NATURAL MOISTURE CONTENT ��,� % NATURAL DRY DENSITY boy L pCF
n o
0 w
3 m
N
N 0
o
0
o n
' N
N �O
O �
1 �
oW
i
0
f
f
SWELL -CONSOLIDATION
LOAD (PSF)
500 1000 5000
Saturated at constant
pressure
►1
SAMPLE OF FROM TEST HOLE NO.
AT DEPTH OF -7 i3 FEET NATURAL MOISTURE CONTENT
m
10000
Zz, % NATURAL DRY DENSITY lo¢,Z PCF
0
•
i
A
SWELL -CONSOLIDATION
LOAD (PSF)
500 1000 5000
Saturated at constant
pressure
rj
SAMPLE Of `��NrrrC�tA(' S�.Grc�•�c��; FROM TEST HOLE NO. q
AT DEPTH OF 3 _� FEET NATURAL MOISTURE CONTENT 14-7 % NATURAL DRY DENSITY
10000
lob.-7 PCF
0
0
•
J
J
W
3A 4
2.
0.
b�
K
SWELL -CONSOLIDATION
LOAD (PSF)
500 1000 5000
Saturated at constant
pressure
10000
SAMPLE OF FROM TEST HOLE NO. �.
c�
AT DEPTH OF z,_q FEET NATURAL MOISTURE CONTENT q,Y, % NATURAL DRY DENSITY 5 3.� PCF
n o
o a
afD
J.
Vf O
J. C.
_' C
zm
O �t
N
N �O
A t+
I �
w
D
•
0
SWELL -CONSOLIDATION
LOAD (PSF)
500 1000 5000
Saturated at constant
pressure
00)
z
0 4.
Q
0
o 6
z
0
U
SAMPLE OF -J, 6RAjr,�� FROM TEST HOLE NO. 'L
c�
AT DEPTH OF Z-� FEET NATURAL MOISTURE CONTENT 12 4,, % NATURAL DRY DENSITY
10000
9-7,5 PCF
[A
•
A
J
J
W
Cn 4
2.
.� 0.
`i
SWELL -CONSOLIDATION
LOAD (PSF)
500 1000 5000
Saturated at constant
pressure
SAMPLE OF
AT DEPTH OF 2_3 FEET
FROM TEST HOLE NO.
10000
NATURAL MOISTURE CONTENT 1$ -7 % NATURAL DRY DENSITY �0�5 pig
r
•
•
Date November 29, 1993
Commission No. 2104-01-01-01
BORING-
LOGS
u�
NNNN
sl. -p
Imo"•
�'R. �.
low
�v-
> II io
FOUNDATION
ENGINEERING FIG.9
EI
•
Date November 29' 1993
Commission No.2104-01-01-01
-'Fs-r +bLr-
µo.-7Z-
BORING.
LOGS
I4h.9 rL
cl o
rr
\
�
1o^ e,
i60
v
In4o.N�FP bn.rrJ�
Iv'. IZ 2
.�I
u rL
Rfl
55'
K.
FOUNDATION ENGINEERING
FIG. 8
Q&,
Date November 29, 1993
Commission No. 2104-01-01-01
-t�sT Not, I-4o.1
BORING- LOGS
to N�.17 4�.1 �
Z�L"
20
-7
LIFT
•'
Ia
�
I'hi T��Io
7 D-
IZ" I..IE,�-{a rtl.�'61LJvdFi
L(2n�r:usf
(oS —
N`rzT�YGIs*tu�
+loss TILT.
.
3�
�
ti
IZ�,
v�,2x=i
a
J
GWu.g.0 11/414?i
�s
FOUNDATION ENGINEERING
FIG.7
0&
Date November 29, 1993
Commission No. 2104-ni-o1-01
BORING. LOGS
.a
IZ"
Fi0
A
I
—
_
—
_
—
S I I��ol-lam GLA T�J FF•� �
TI Y So+A Py' ,
No
O
-
IZ"
G�WlD Il�lo/5Z,
ao
FOUNDATION ENGINEERING
FIG. 6
•
Date November 29, 1993
Commission No.2104-01-01-01
BORING- LOGS
IFS
�uwx S^1 0
' i•
SI, MCI
I�
I I -a-
5M4eX,
7
'
HaD, SJ�T
�5
e
'
Z•
.'
-5j Ho 1'57
Mr�v• la��.d V—K
IZ^
1 17 —
.e
Ff
e r
T'
FOUNDATION ENGINEERING
FIG. 5
Date November 29, 1993
Commission No. 2104-01-01-01
I ,? F►a�N,.S
BORING. LOGS
W.(P 14-7
I�.v
I�
Ig l2 ••
�`
+.
cite^1S'iiJ�Slli"n��011"✓1
71 Z ..
177Z„
CID
a
_
Fz
1
_
17
�y
71(l ✓f
-70 -
FOUNDATION ENGINEERING
FIG. 4
Ll
Date November 29, 1993
Commission No.2104-01-01-01
l%t'f [10Lr
40.1
BORING. LOGS
4— 7_ -5
1-lo.il'
�0
oIy,Z..
1+41.
;
•�'
as
-
.,
Zy1z..
r.
r-y'GiV- 44
:-r R{
—
a
SPH7' Sl.vaa�c+.Lt-
%S
-
-i
o•
a
2�2.� I't�IsT �I'e�.
Yv�vr4
F
-t3HFz
70++Ii
I L
e
•o
..
FOUNDATION ENGINEERING
FIG. 3
Date November 29, 1993
Commission No.2T04-01-01-01
LEGEND
OF SOI LS SYMBOLS
FILL
GRAVELS
SANDS
SHELBY TUBE SA14PLE
SILTS
GRAVELS, SAND &
SILT COMBINATIONS
STANDARD PENETRATION
SANDY GRAVELS,
TEST SAMPLER*
GRAVELLY SANDS
SILTY SANDS,
SANDY SILTS
SANDY CLAYS,
WATER TABLE AT
CLAYEY SANDS
TIME OF DRILLING
SAND, SILT & CLAY
COMBINATIONS
CLAYS
HOLE CAVED
WEATHERED BEDROCK
SILTSTONE
CLAYSTONE # 20/12 indicates that 20 blows
of a 140 lb. hammer falling
SANDSTONE 30" was required to penetrate
12"
LIMESTONE
GRANITE
FOUNDATION ENGINEERING
FIG. 2
Date: November 29, 1993
Commission No.: 2104-01-01-01
t-- — - — - — — - — — - — - — ---
e a
a
a
a
a
a
a
s
a
.I�
N7
.�
I � � k �
I
I
a;.._......_....-
.......... ..... ............................._.....
-......I
' Nq.
•
u
I\
�4
ia
,
--
sU�D�JISIot-�-
Co l.oe-art�o
.sV-fk—
I.Ie3',o f
BORING LOCATION MAP
FIG. 1
M O I S T U R E- D E N S I T Y D E T E R M I N A T I O N
Samples of representative fill materials to be placed shall be
furnished by the contractor to the soils engineer for determination
of maximum density and optimum moisture for these materials. Tests
for this determination will be made using methods conforming to
requirements of ASTM D698. Copies of the results of these tests
will be furnished to the contractor. These test results shall be
the basis of control for compaction effort.
D E N S I T Y T E S T S
The density and moisture content of each layer of compacted fill
will be determined by the soils engineer in accordance with ASTM
D1556 or D2167. Any material found not to comply with the minimum
specified density shall be recompacted until the required density
is obtained. The results of all density tests will be furnished to
both the owner and the contractor by the soils engineer.
4
optimum compaction. The moisture shall be uniform throughout the
fill. The contractor may be required to add necessary moisture to
the backfill material in the excavation if, in the opinion of the
soils engineer, it is not possible to obtain uniform moisture
content by adding water on the fill surface. If, in the opinion of
the soils engineer, the material proposed for use in the compaction
is too wet to permit adequate compaction, it shall be dried in an
acceptable manner prior to placement and compaction. Moisture
requirements for utility backfill, roadway, and curb and gutter
subgrades should be plus or minus two percent (+2%) of standard
Proctor.
C O M P A C T I O N
When an acceptable uniform moisture content is obtained, each layer
shall be compacted by a method acceptable to the soils engineer and
as specified in the foregoing report as determined by the standard
Proctor test (ASTM D698). Compaction shall be performed by rolling
with approved tamping rollers, pneumatic -tired rollers, three -wheel
power rollers, or other approved equipment well -suited to the soil
being compacted. If a sheepsfoot roller is used, it shall be
provided with cleaner bars attached in a manner which would prevent
the accumulation of material between the tamper feet. The roller
should be so designed that the effective weight can be increased.
3
P R E P A R A T I O N O F S U B G R A D E
All topsoil and vegetation shall be removed to a depth satisfactory
to the soils engineer before beginning preparation of the subgrade.
The subgrade surface of the area to be filled shall be scarified
to a minimum depth of six (6) inches, moistened as necessary, and
compacted in a manner specified below for the subsequent layers of
fill. Fill shall not be placed on frozen or muddy ground.
P L A C I N G F I L L
No sod, brush or frozen material or other deleterious or unsuitable
material shall be placed in the fill. Distribution of material in
the fill shall be such as to preclude the formation of lenses of
material differing from the surrounding material. The materials
shall be delivered and spread on the fill surface in such a manner
as will result in a uniformly compacted fill. Prior to compacting,
each layer shall have a maximum thickness of eight (8) inches and
its upper surface shall be relatively horizontal.
M O I S T U R E C 0 N T R 0 L
The fill material in each layer, while being compacted, shall as
nearly as practical contain the amount of moisture required for
2
APPENDIX A
Suggested Specifications for Placement of Compacted Earth Fills
and/or Backfills.
G E N E R A L
A soils engineer shall be the owner's representative to supervise
and control all compacted fill and/or compacted backfill on the
project. The soils engineer shall approve all earth materials prior
to their use, the methods of placing, and the degree of compaction
obtained. A certificate of approval from the soils engineer will
be required prior to the owner's final acceptance of the filling
operations.
M A T E R I A L S
The soils used for compacted fill beneath interior floor slabs and
backfill around foundation walls shall be impervious and non -
swelling for the depth shown on the drawings. No material shall be
placed for fill which has a maximum dimension of six (6) inches or
greater. All materials used in either compacted fill or compacted
backfill shall be subject to the approval of the soils engineer.
1
0
•
condition which might affect the performance of the foundation
systems and roadways.
20
geotextile. Adequate discharge areas must be provided. Where the
bedrock strata are not exposed in the subgrade, the edge drains
without the blanket drain are recommended.
G E N E R A L I N F O R M A T I O N
The data presented herein were collected to help develop designs
and cost estimates for this project. Professional judgments on
design alternatives and criteria are presented in this report.
These are based on evaluation of technical information gathered,
partly on our understanding of the characteristics of the structure
proposed, and partly on our experience with subsurface conditions
in the area. We do not guarantee the performance of the project in
any respect, only that our engineering work and judgments rendered
meet the standard of care of our profession.
The test holes drilled were spaced to obtain a reasonably accurate
picture of subsurface conditions for design purposes. These
variations are sometimes sufficient to necessitate modifications
in design.
We recommend that construction be continuously observed by a
qualified soils technician trained and experienced in the field to
take advantage of all opportunities to recognize some undetected
19
wall. The slab should be reinforced as necessary for the span
involved.
PRELIMINARY PAVEMENT RECOMMENDATIONS
All interior roadways, as well as a portion of Harmony Road, are
to be paved for this project. At this time, R-value test results
had not been completed and the City of Fort Collins does not have
adequate information to supply the required traffic criteria
necessary to complete the pavement thickness recommendations. These
recommendations will follow in a later report.
Roadways where groundwater levels and/or bedrock surfaces are
located within three (3) feet of the pavement surface will require
a subdrain. Where bedrock is exposed at the subgrade, we recommend
that a blanket drain be constructed between the aggregate base
course and the subgrade. The blanket drain should consist of four
(4) inches of Class B or C (Colorado Department of Transportation)
filter material. The blanket drain shall be fully wrapped in a
geotextile suitable for such usage. The blanket drain should be
connected to edge drains located underneath the edge of the
roadways. The invert of the edge drains should be a minimum of
three (3) feet below the pavement subgrade. The edge drains should
be a minimum width of twelve (12) inches with four (4) inch
diameter perforated pipe at the bottom. The trench shall then be
filled with Class B or C filter material and fully wrapped in
18
M
M
lieu of a plastic membrane.
All plants located next to the
foundation should be hand watered only using the minimum amount of
water.
Backfill around the outside perimeter of the structure, except as
noted above, should be compacted from optimum moisture to three
percent (3%) above optimum moisture, and from eighty-five percent
(85%) to ninety percent (90%) of Standard Proctor Density as
determined by ASTM Standard Test D-698. The backfill should be
mechanically compacted in loose lifts not to exceed twelve (12)
inches. Expansive soils and/or bedrock fragments should not be used
for backfill materials. If imported material is used, the soil
should be relatively impervious and non -expansive. The foundation
walls should be well -cured, braced or subfloor installed prior to
backfilling. Past experience has shown that severe damage could
occur to the foundation walls if expansive material is placed for
backfill and allowed to become wet.
The backfill placed immediately adjacent to the foundation walls,
if not properly compacted, can be expected to settle with resulting
damage to sidewalks, driveway aprons, and other exterior slabs -on -
grade. To avoid settlement and disfigurement of the slabs in the
event that the backfill is not properly compacted, we recommend
that concrete slabs which must span the backfill be supported by
the foundation walls. This is conventionally done by use of a brick
ledge or haunch. Exterior slabs could be dowelled to the foundation
17
M M
pounds may be needed to excavate the firm bedrock. Bedrock used
as fill should be broken into pieces less than six (6) inches in
diameter. Proper placement of the bedrock as fill may be dif-
ficult, and a disc or other mixing equipment may be needed to
obtain uniform moisture and proper compaction. It is recommended
that bedrock not be used as backfill adjacent to proposed build-
ings.
L A N D S C A P I N G A N D D R A I N A G E
Every precaution should be taken to prevent wetting of the subsoils
and percolation of water down along the foundation elements.
Finished grade should be sloped away from the structure on all
sides to give positive drainage. A minimum of twelve (12) inches
fall in the first ten (10) feet is recommended. Sprinkling systems
should not be installed within ten (10) feet of the structure.
Downspouts are recommended and should be arranged to carry drainage
from the roof at least five (5) feet beyond the foundation walls.
Plantings are not recommended around the perimeter of the founda-
tions. However, if the owners are willing to accept the risks of
foundation and slab movement, low water use plant varieties could
be used. A horizontal impervious membrane, such as polyethylene,
should not be used next to the foundation wall. We recommend the
use of a landscape fabric which will allow normal evaporation in
16
40
7. All exterior slabs should be constructed using a more durable
sulfate resistant concrete containing Type II cement and with
higher air contents and lower water cement ratios.
S I T E G R A D I N G A N D U T I L I T I E S
Specifications pertaining to site grading are included below and
in Appendix A of this report. It is recommended that the upper ten
(10) inches of topsoil below building, filled and paved areas be
stripped and stockpiled for reuse in planted areas. The upper six
(6) inches of the subgrade below paved and filled areas should be
scarified and recompacted plus or minus two percent (±2%) of
optimum moisture to at least ninety-five percent (95%) of Standard
Proctor Density ASTM D-698-78 (See Appendix A of this report).
Additional fill should consist of the onsite clayey soil or
imported materials approved by the geotechnical engineer. Fill
should be placed in uniform six to eight (6-8) inch lifts and
mechanically compacted plus or minus two percent (+2%) of optimum
moisture to at least ninety-five percent (95%) of Standard Proctor
Density ASTM D-698-78.
Bedrock encountered at the site may be used as fill material in
selected areas. Heavy-duty construction equipment equivalent to
an excavator having a gross weight of ninety thousand (90,000)
15
M !t
(two (2) inches for caisson foundations) above or below
interior nonload bearing partitions where floors consist of
slabs -on -grade. All phases of construction should be con-
structed to allow the void to function as intended.
3. Eliminate underllab plumbing where feasible. Where such
plumbing is unavoidable, it should be pressure tested during
construction to minimize leaks which would result in wetting
of the subsoils.
4. Separate slabs -on -grade into panels by use of control joints.
We recommend joints be placed no more than fifteen (15) feet
on center. Control joints should also be located at potential
weak areas such as the corners of driveway slabs.
5. All slabs -on -grade should be underlain with a four (4) inch
layer of clean, crushed rock or gravel to help distribute
floor loads and to provide a capillary break should moisture
penetrate under the slab.
6. Due to the proximity of the groundwater and/or bedrock, any
lower levels (i.e. basements), in some areas, should be
provided with a perimeter drain as described in this report.
The requirement for the drain should be made by the Engineer
during the open hole inspection.
14
Where basement level construction is desired where groundwater
levels will be within three (3) feet of the finished floor
elevations, an area subdrain should be considered. The subdrain
should be located underneath the sanitary sewer main and be
designed to accommodate the perimeter drains described above, as
well as lowering the groundwater underneath the roadway.
F L O O R S L A B S
Soils at proposed foundation elevations are stable at their natural
moist condition. However, should moisture contents of the clayey
soils or bedrock stratum increase, heaving will result, particular-
ly at basement elevations. This phenomenon can result in cracking
of the garage slabs or other slabs -on -grade. With the above in
mind, construction of the structure, as much as possible, should
be done to accommodate movement of the slabs without damage. We
recommend the following:
1. Slabs should be constructed "free floating". The slab should
be isolated from all structural components and utilities which
penetrate the slab. Isolation may be accomplished with 112
inch isolation material or by sleeving.
2. Provide a one and one-half (1-112) inch minimum void space
13
so
BASEMENT S AND SUBDRA INS
Basement construction is feasible at most of the site. However,
where basement or other habitable lower levels are located within
three (3) feet of the bedrock and/or groundwater, we recommend that
such lower levels be provided with a perimeter drainage system.
The drainage system should contain a four (4) inch diameter
perforated drain pipe encased in a minimum of twelve (12) inches
of clean, 314 inch gravel graded in accordance with ASTM C 33-78.
The drain pipe should extend around the lower level with the invert
being placed a minimum of four (4) inches below the bottom of the
footing to facilitate moisture transfer to the perimeter drain
system. The gravel should be placed a minimum of eight (8) inches
over the pipe the full width of the trench. The whole system
should then be covered with untreated building paper or geotextile
to minimize clogging of the gravel with the backfill material.
The above drain system should be run at 118 inch per foot minimum
to either a sump constructed in the basement or "daylighted" well
beyond the foundation system. The sump should be a minimum of
eighteen (18) inches diameter by three (3) feet deep and surrounded
by at least six (6) inches of clean gravel similar to that provided
around the drain. The sump should be provided with a pump designed
to discharge all flow from the sump a minimum of five (5) feet
beyond the backfill zone or into a subdrain designed to accommodate
the anticipated flow.
12
6. A minimum of four (4) inches air space should be provided
beneath all grade beams to insure the concentration of dead
load pressure on all piers.
7. All piers should be carefully cleaned and dewatered before
pouring concrete. in our opinion, casing and/or dewatering
may be required. Concrete and reinforcement should be placed
immediately after drilling of each pier.
8. Most of the bedrock at the site can be drilled with normal
heavy commercial -size pier drilling rigs. Some of the bedrock
may be very hard and a problem may arise if the contractor
attempts to drill the pier holes in some of the areas with
small drill rigs. in case drilling refusal is encountered,
the depth of penetration into bedrock may be reduced if design
criteria are adjusted accordingly.
9. All pier holes should be inspected during construction by a
competent representative of the geotechnical engineer in order
to insure that the required penetration and depths are met,
that no loose material remains in the hole, and that the holes
are properly dewatered prior to placement of the concrete.
11
so
so
given above may be used in uplift provided the sides of the hole
are grooved.
In drilling the piers, the following design and construction
details should be observed:
1. Piers should be designed for the maximum end bearing, minimum
dead load and skin friction specified in this report.
2. Grade beams should be reinforced with rebar to span between
each pier. Rebar should be run continuously around corners
and be properly spliced.
3. Bearing walls should be omitted in the basement. Partitions
should be hung from the floor joists and beams which are
supported by adjustable steel columns. A minimum two (2) inch
void should be constructed under all partition walls located
over slabs.
4. All piers should penetrate a minimum of five (5) feet into the
firm bedrock with a minimum length of ten (10) feet.
5. All piers should be reinforced their full length to resist
tension. We recommend the use of at least two (2) #5 bars.
The rebar should extend into the grade beam to tie the pier
to the grade beam.
10
The foundation walls and other structural elements should be
designed by a qualified structural engineer for the appropriate
loading conditions. All footings or pads should be placed below any
topsoil or fill unless the fill has specifically been placed and
compacted for support of footings or pads. All exterior footings,
pads, and grade beams should be placed below frost depth (thirty
(30) inches in this area) to provide adequate cover for frost
protection.
Drilled Piers and Grade Beams
Where footings and/or grade beams will bear partially on the
bedrock and partially on the upper soils, or where footing
elevations are located within three (3) feet of the bedrock strata,
we recommend the use of a drilled pier and grade beam type
foundation system. The piers should be drilled a minimum of five
(5) feet into the firm bedrock with a minimum length of ten (10)
feet. The piers should be designed for a maximum end bearing value
of 15,000 PSF, maximum side shear on that portion of the pier in
bedrock of 1,500 PSF and a minimum dead load of 5,000 PSF. A
nominal amount of reinforcing steel should be used in all piers.
Difficulty is sometimes experienced in achieving the desired
minimum dead load. If this occurs, we suggest the piers be
reinforced full length to take the difference between the "desired"
and the "obtainable" dead load in tension. The side shear value
E
1. All footings, pads, and\or grade beams should be below frost
depth. Frost depth in this area is considered to be thirty
(30) inches.
2. Foundation walls should be reinforced with rebar to span an
unsupported length of ten (10) feet or between each pad. Rebar
should be run continuously around corners and be properly
spliced. Foundations should be designed by a Registered
Engineer for the conditions described in this report.
3. Bearing walls should be omitted in the basement. Partitions
should be hung from the floor joists and beams supported by
adjustable steel columns. A 1-112 inch void should be con-
structed under all partition walls located over slabs.
4. it is our opinion that basement construction is feasible for
this site. However, all finished floor slabs located within
three (3) feet of the groundwater and/or bedrock stratum
should be protected by a perimeter drain as detailed in this
report.
5. All footings, pads, and/or grade beams should bear on similar
strata.
6. We recommend the performance of an excavation inspection for
each lot to make a final determination on foundation type.
P
depending upon variations in precipitation, surface irrigation and
runoff on the site. Due to the shallow depth of bedrock in some
areas, surface water from the above sources could percolate through
the upper soils or backfill becoming trapped upon -the relatively
impervious bedrock stratum forming a perched water table. The
ambient groundwater table at the site is not expected to rise to
a level which would affect the construction or utilization of a
residence constructed over a basement unless a source of water not
presently contributing becomes available.
F O U N D A T I O N R E C O M M E N D A T I O N S
Spread Footings
Where clays and sands are encountered at footing elevations and at
least three (3) feet above the bedrock strata, we feel that the
structure should be supported by a continuous balanced spread
footing and/or grade beam foundation. The footings should be
designed for a maximum allowable bearing capacity of 1500 pounds
per square foot (dead load plus 112 live load) with a minimum dead
load of 500 pounds per square foot to help counteract potential
swelling of the subsoils.
The following recommendations should be followed in the design of
, the foundation system:
7
of the deeper clays. Laboratory and field tests indicate that these
deposits exhibit low to moderate bearing capacities with a low to
no swell potential when wetted.
The upper clays grade into clean to clayey sands. The sands contain
traces to moderate amounts of gravel. These deposits exhibit low
to moderate bearing capacities with no swell potential. The sands
were encountered to depths ranging from two (2) feet to greater
than twenty (20) feet.
Siltstone, sandstone, and claystone bedrock strata were encountered
below the upper sands and clays. Siltstone with claystone layers
appear to be predominant material along the west side. Minor
sandstone beds were observed in this area. Soft claystone was
encountered primarily at the east end of the project. The bedrock
strata exhibits moderate to high bearing capacities. The siltstone
and claystone exhibits a moderate swell potential when wetted. The
sandstones exhibit no swell potential. The bedrock strata were
encountered to the depths explored.
Groundwater observations were made as the borings were being
advanced and immediately after completion of the drilling
operation. At the time of our field investigation, groundwater was
encountered in Test Hole Nos. 1, 21 3, 4, 7, 9, 10, 11 and 18 at
depths ranging from twelve (12) feet to eighteen (18) feet. The
groundwater table can be expected to fluctuate throughout the year
volume. Results of those tests are presented at the end of this
report.
A calibrated hand penetrometer was used to estimate the approximate
unconfined compressive strength of selected samples. The calibra-
ted hand penetrometer has been correlated with unconfined compres-
sion tests and provides a better estimate of soil consistency than
visual examination alone.
As part of the testing program, R-value tests were performed on
selected samples to determine the soil support characteristics for
roadway design purposes. At this time, R-value test had not been
completed.
S U B S U R F A C E C O N D I T I O N S
Generally, very thin to moderately thick layers of alluvial and
pediment soils overlie bedrock strata of the Pierre Shale. Free
groundwater was encountered in nine (9) of the eighteen (18)
borings.
Clays containing slight to high amounts of sand and traces of
gravel were encountered in the upper one (1) to twelve (12) feet
of the borings. The clays appear to be more plastic near the north
end of the project. Minor layers of sand were encountered in some
5
0 to
(3) inch O.D. thin wall samplers (Shelby), pushed hydraulically
into the soil in accordance with ASTM D-1587. In this sampling
procedure, a seamless steel tube with a beveled cutting edge is
pushed hydraulically into the ground to obtain a relatively
undisturbed sample of cohesive or moderately cohesive soil. All
samples were sealed in the field and preserved at natural moisture
content until time of test.
L A B O R A T O R Y T E S T I N G P R O C E D U R E S
The recovered samples were tested in the laboratory to measure
their dry unit weights, natural water contents, grain size and for
classification purposes. Selected samples were tested for strength
and stability characteristics. These include swelling,
compressibility, collapse and shear strength of the soil and/or
rock.
One dimensional consolidation -swell tests were performed on
selected samples to evaluate the expansive, compressive and
collapsing nature of the soils and/or bedrock stratum. In the
consolidation -swell test, a trimmed specimen is placed in a one-
dimensional confinement ring and a vertical load is applied. After
seating, the sample is inundated with water and the height change
of the specimen is recorded. The confining load is then incremen-
tally increased until the specimen is compressed to its original
4
on the attached diagram, are approximate and were made by pacing.
Angles for locating the borings were estimated. Elevations of the
borings are approximate and were obtained using a level and rod.
The elevations were referenced to an assumed elevation of 100.0
feet using the top of the north nozzle of the fire hydrant at the
northwest entrance to McGraw Elementary. The approximate location
of the benchmark is shown on the attached boring location map,
Figure 1. The locations and elevations of the borings should be
considered only to the degree implied by the methods used to make
those measurements.
Complete logs of the boring operations were compiled by a represen-
tative of our firm as the borings were advanced. The approximate
location of soil and rock contacts, free groundwater levels, and
standard penetration tests are shown on each boring log. The
transition between different strata can be and most often is
gradual.
An index of soils relative density and consistency was obtained by
use of the standard penetration test, ASTM Standard Test D-1586.
The penetration test result listed on the log is the number of
blows required to drive the two (2) inch split -spoon sampler twelve
(12) inches (or as shown) into undisturbed soil by a one hundred
and forty (140) pound hammer dropped thirty (30) inches.
Undisturbed samples for use in the laboratory were taken in three
3
Road, east of Front Range Community College and west of Crest Road.
The 28+ acre site consists of old alluvial and pediment deposits
located over bedrock strata of the upper Cretaceous Pierre Shale.
The southwest corner of the project had been previously stripped
of overburden soils for use for the building pad for McGraw
Elementary School. Two (2) irrigation ditches are located at the
west end of the project. Twelve (12) lots are located east of the
elementary school on Crest Road. The site is vegetated with grasses
and has a slight to moderate slope towards the east.
F I E L D I N V E S T I G A T I O N
The field investigation consisted of eighteen (18) deep borings at
selected locations on the site. Three (3) of the borings were
sleeved for groundwater monitoring purposes. Twelve (12) additional
shallow test holes were drilled for pavement recommendations.
Distances between borings are as indicated on the attached test
boring location map, Figure 1. The borings were advanced using a
four (4) inch diameter continuous flight power auger. All borings
were continued to hard bedrock or to depths considered sufficient
for the purposes of this report as set forth in the scope.
The borings were laid out by Foundation & Soils Engineering, Inc.
personnel based on a plat provided by Land Design Studio. Distances
from the referenced features to the boring locations, as indicated
2
a
S C 0 P E
The following report presents the results of our subsurface
investigation on Coventry Subdivision, situated in the North Half
of Section 2, Township 6 North, Range 69 West of the 6th Prime
Meridian, Larimer County, Colorado. This investigation was
performed for Colorado Land Source at the request of Ms. Kay Force
of Jim Sell Design, Inc.
We understand the site is to be developed into one hundred nine
(109) single family residential lots. Construction is to be typical
wood frame type and brick veneer and as such, should generate only
light loading, on the order of 1,000 to 2,000 PLF. Concentrated
loads, if any, should not exceed 15 to 20 KIPS.
The purpose of this investigation is to identify subsurface condi-
tions and to obtain test data to properly design and construct the
foundation system, floor slabs, and roadways. The conclusions and
recommendations presented in this report are based upon the
acquired field and laboratory data and previous experience with
similar subsurface conditions in the area.
S I T E D E S C R I P T I O N
The site is located in southwest Fort Collins, south of Harmony
1
a
a
TABLE OF CONTENTS
Letter of Transmittal
i
Scope
1
Site Description
1
Field Investigation
2
Laboratory Testing Procedures
4
Subsurface Conditions
5
Foundation Recommendations
7
Basement and Subdrains
12
Floor Slabs
13
Site Grading and Utilities
15
Landscaping and Drainage
16
Pavement Recommendations
is
General Information
19
Test Boring Location Map
Figure 1
Legend of Soil Symbols
Figure 2
Boring Logs
Figures 3 - 9
Consolidation Swell Test
Figures 10 - 20
Summary of Test Results
Figures 21 - 26
Suggested Specifications for Placement
Appendix A
of Compacted Earth Fills and/or Backfills
a
a
November 29, 1993
Commission No.: 2104-01-01-01
Colorado Land Source
9085 East Mineral Circle #200
Englewood, Colorado 80112
Gentlemen:
The enclosed report presents the results of a subsurface investi-
gation for Coventry Subdivision, a proposed subdivision of Fort
Collins, Colorado.
In summary, low to non -swelling sands, clays and moderately
swelling bedrock strata were encountered in the borings. Although
the site soils and/or rock are suitable for support of the proposed
structures, care will be needed in both the design and construction
of the buildings to minimize the potential for foundation and floor
slab movement.
The attached geotechnical report presents the results of our
investigation and recommendations concerning design and construc-
tion of the foundation system and support of floor slabs.
We appreciate the opportunity to be of service to you on this
project. If you have ons;. please feel free to call.
Respect ul1y,
23841
Kevin W. Patterson,
FOUNDATION & SOILS
KWP1jlb
,cC7rJ sfi Sell :Design Ih-
46 a
SUBSURFACE INVESTIGATION
FOR
COVENTRY SUBDIVISION
FORT COLLINS, COLORADO
Prepared for
Colorado Land Source
9085 East Mineral Circle #200
Englewood, Colorado 80112
November 29, 1993
Commission No.: 2104-01-01-01
Prepared By
FOUNDATION & SOILS ENGINEERING, INC.
CONSULTING ENGINEERS
100 East Third Street
Loveland, CO 80537