HomeMy WebLinkAboutROCKBRIDGE CONDO RESIDENCES PUD MINOR SUBDIVISION - 82 93B - SUBMITTAL DOCUMENTS - ROUND 1 - GEOTECHNICAL (SOILS) REPORTu '
UNIFIED SOIL CLASSIFICATION SYSTEM
Criteria for Assigning Group Symbols and Group Names Using Laboratory TestsA
Coarse -Grained
Gravels more than Cleans Gravels Less
Soils more than
i0%of coarse than 5% fines`
504o retained on
fraction retained
No. 200 sieve
on No. 4 sieve
Fine -Grained
Soils 50%or
more passes the
No. 200 sieve
Sands 50% or
more of coarse
fraction passes
No. 4 sieve
Silts and Clays
Liquid limit less
than 50
Gravels with Fines
more than 12%
finest
Clean Sands Less
than 5% fines'`
Sands with Fines
more than 12%
fines"
inorganic
organic
Cu>4and1 <Cc<3'
Cu < 4 and/or I > Cc > 3'
Fines classify as NIL or MH
Fines classify as CL or CH
Cu > 6 and I < Cc < 3'
Cu < 6 and/or I > Cc > 3'
Fines classif\as ML or MH
Fines classify as CL or CH
PI > 7 and plots on or above "A" line'
PI < 4 or plots below "A" line'
Liquid limit - oven dried
Liquid limit - not dried
Silts and Clays inorganic PI plots on or above "A" line
Liquid limit 50 or
more PI lots below "A" line
organic Liquid limit - oven dried
Liquid limit - not dried
High]\ organic soils Primarily organic matter. dart: in color- and organic odor
"Based on the material passing the 3-in. (75-
mm) sieve ECu•D °!D 10 C,. tD101
D XD
alf field sample contained cobbles or boulders. 10 `°
or both. add "with cobbles or boulders. or both"
to group name.
`Gravels with 5 to 12% fines require dual
symbols:
GW-GM "yell -graded gravel with silt
GW-GC well -graded gravel with cla"
GP -GM poorly graded gravel with silt
GP -GC poorly graded gravel with clay
"Sands with 5.to 12% fines require dual
s}'mbols:
SR'-SM well -graded sand with silt
SW -SC well -graded sand with clay
SP-SM poorly graded sand with silt
SP-SC poorly graded sand with clay
it
`If soil contains > IS%sand. add "with sand" to
group name.
°If fines classify as CL-ML. use dual symbol
GC -CM. or SC-SM.
"If fines are organic. add "with organic fines"
to roup name.
'If soil contains > 15% gravel. add "with
gravel" to group name.
'If Atterberg limits plot in shaded area. soil is a
CL-ML. silty clay.
Soil Classification
Group Group Name"
Symbol
GW Well -Waded eravelr
GP Poorly graded gravel!
G\I Silt\ gravel. G. H
GC Clayey gravel"'"
SW Well -graded sand'
SP Poorly graded sand'
SM Silty sand""'
SC Clayey sand`i"'
CL Lean clay"'-"'
ML Silt"''"
Organic clay" MN
< 0.75 OL
Organic silt"-`")
CH Fat clay"L"
\1H Elastic Silt""
Organic clay".L".J`
< 0.75 OH
Organic silt"-" Q
PT Peat
"If soil contains 15 to 29% plus No. 200. add
"with sand" or "with gravel". whichever is
predominant.
'If soil contains > 30% plus No. 200
predominantly sand. add "sand\" to group
name.
"If soil contains > 30% plus No. 200.
predominantly _gravel. add "gravelly" to group
name.
"PI > 4 and plots on or above "A" line.
"PI < 4 or plots below "A" line.
'P1 plots on or above "A" line.
"PI plots below "A" line.
i:n4C LAi
/
/
/
/
N-
MLo+aL
�
to to zo 31 10 .. !° » 80 a° too u°
DRILLING & SAMPLING SYMBOLS
■._
SS:
Split Spoon - 1318" I.D.. 2" O.D., unless otherwise noted
PS:
Piston Sample
ST:
Thin -Walled Tube - 2" O.D., unless otherwise noted
WS:
Wash Sample
R:
Ring Barrel Sampler - 2.42" I.D.. 3" O.D. unless otherwise noted
PA:
Power .Auger
FT:
Fish Tail Bit
HA:
Hand .Auger
RB:
Rock Bit
DB:
Diamond Bit = 4", N, B
BS:
Bulk Sample
AS:
Auger Sample
PM:
Pressure Meter
HS:
Hollow Stem Auger
WB:
Wash Bore
Standard "N" Penetration: Blows per foot of a 140 pound hammer falling 30 inches on a 2-inch O.D. split spoon. except where noted.
WATER LEVEL MEASUREMENT SYMBOLS
WL :
Water Level
WS
While Sampling
WCI:
Wet Care in
WD :
\Vhile Drilling
DCI:
Dry Cave in
BCR:
Before Casing Removal
AB :
After Boring
ACR:
After Casting Removal
Water levels indicated on the boring loos are the levels measured in the borines at the time indicated. In pervious soils, the indicated
levels may reflect the location of ground water. In low permeability soils, the accurate determination of ground water levels is not
possible with only short term observations.
DESCRIPTIVE SOIL CLASSIFICATION
Soil Classification is based on the Unified Soil Classification
system and the ASTM Designations D-2488. Coarse Grained
Soils have move than 50% of their dry weight retained on a
-200 sieve: they are described as: boulders, cobbles, gravel or
sand. Fine Grained Soils have less than 50% of their dry weieht
retained on a =200 sieve: thev are described as : clays. if they
are plastic, and silts if they are slightly plastic or non -plastic.
Major constituents may be added as modifiers and minor
constituents may be added according to the relative proportions
based on grain size. In addition to gradation. coarse grained
soils are defined on the basis of their relative in -place density
and fine grained soils on the basis of their consistency.
Example: Lean clay with sand, trace gravel, stiff (CL): silty
sand. trace gravel, medium dense (SM).
CONSISTENCY OF FINE-GRAINED SOILS
Unconfined Compressive
Strength, Qu, psf Consistency
<
500
Very Soft
500 -
1.000
Soft
1.001 -
2.000
Medium
2,001 -
4.000
Stiff
4,001 -
8,000
Very Stiff
8.001 -
16.000
Very Hard
RELATIVE DENSITY OF COARSE -GRAINED SOILS
N-Blows/ft
Relative Densitv
0-3
Very Loose
4-9
Loose
10-29
Medium Dense
30-49
Dense
50-80
Very Dense
80 �
Extremely Dense
PHYSICAL PROPERTIES OF BEDROCK
DEGREE OF WEATHERING:
Slight
Slight decomposition of parent material on
joints. May be color change.
Moderate
Some decomposition and color change
throughout.
High
Rock highly decomposed, may be extremely
broken.-
HARDNESS .AND DEGREE OF CEMENTATION:
Limestone and Dolomite:
Hard
Difficult to scratch with knife.
Moderately
Can be scratched easily with knife.
Hard
Cannot be scratched with fingernail.
Soft
Can be scratched with fingemail.
Shale. Siltstone and Claystone:
Hard
an be scratched easily with knife, cannot be
scratched with fingernail.
Moderately
Can be scratched with fingernail.
Hard
Soft
Can be easily dented but not molded with
fingers.
Sandstone and Conglomerate
Well Capable of scratching a knife blade.
Cemented
Cemented Can be scratched with knife.
Poorlv Can be broken apart easily with fingers.
Cemented
EEG
14
ROCKBRIDGE CONDOMINIUMS
FORT COLLINS, COLORADO
PROJECT NO: 1952085 DATE: NOVEMBER 1995
LOG OF BORING B-7
RIG TYPE: CME45
SHEET 1 OF 1
WATER DEPTH
FOREMAN: BDT
START DATE
11/6195
WHILE DRILLING
None
AUGER TYPE: 4" CFA
FINISH DATE
11I6195
AFTER DRILLING
None
SPT HAMMER: MANUAL
SURFACE ELEV
N/A
24 HOUR
NIA
SOIL DESCRIPTION
D
N
OU
MC
I OD
A•LIMITS
Q00
SWELL
LL
I PI
PRESSURE
500 PSF
TYPE
IFEE11
(BLOWSffTI
IPSF)
1%)
IPCF)
(%I
5" TOPSOILNEGETATION
SANDY LEAN CLAY WITH GRAVEL (CL)
1
brown
stiff to very stiff
2
12
'9000.
12.8
SSS
3
4
SS
10
-4500
10.1
CLAYEY SILT WITH GRAVEL (ML-CL)
5
tan
stiff
6
7
8
SANDY LEAN CLAY (CL)
brownlred
_ _
stiff
9
10
18
I '9000.
12.3
i
11
softer with depth
( 12
13
14
6 I
'3D00
20.6
SS
IS
BOTTOM OF BORING 15'
16
17
1B
19
20
21
22
23
24
25
Earth Engineering Consultants
1
ROCKBRIDGE CONDOMINIUMS
FORT COLLINS, COLORADO
PROJECT NO: 1952085 DATE: NOVEMBER1995
LOG OF BORING 9-6
RIG TYPE: CME45
SHEET 1 OF 1
WATER DEPTH
FOREMAN: BDT
START DATE
11/6195
WHILE DRILLING
None
AUGER TYPE: 4" CFA
FINISH DATE
1116/95
AFTER DRILLING
None
SPT HAMMER: MANUAL
SURFACE ELEV
NIA
5 DAYS AFTER DRILLING
I N/A
SOIL DESCRIPTION
J D
N
oU
MC
00
A -LIMITS
-200
SWELL
LL
PI
PRESSURE
I%G 500PSF
IfTYPE
IFEETI
IBLOWS/FTI
IPSFI
I%)
IPCFI
I%1
5" TOPSOILrVEGETATION
SANDY LEAN CLAY (CL)
1
brown
stiff to very stiff
2
12
'9000•
11.3
SS
_3_
4
14
•5000
10.1
I
I
I
SS
SANDY LEAN CLAY WITH GRAVEL (CL)
5
light brown/red
-
stiff to very stiff
6
7
8
less gravel with depth
9
I 11
•9000+
9.2
I
I
I
I
SS
10
11
soft below 12 feet
12
13
3
29.8
014
SS
15
BOTTOM OF BORING 15'
16
17
18
19
20
21
22
23
24
25
Earth Engineering Consultants
ROCKBRIDGE CONDOMINIUMS
FORT COLLINS, COLORADO
PROJECT NO: 1952085 DATE: NOVEMBER 1995
LOG OF BORING 8.5
RIG TYPE: CME45
SHEET 1 OF 1
WATER DEPTH
FOREMAN: SOT
START DATE
1116195
WHILE DRILLING
None
AUGER TYPE: 4" CFA
FINISH DATE
11/6/95
AFTER DRILLING
None
SPT HAMMER: MANUAL
SURFACE ELEV
N/A
24 HOUR
N/A
SOIL DESCRIPTION
0
R
I DU
Me
0o
A -LIMITS
-200
SWELL
LL
PI
PRESSURE
500P5F
TYPE
(FEET)
IBLOWSIFTI
IPSFI
(%)
(RCFI
1%)
5" TOPSOILfVEGETATION
SANDY LEAN CLAY (CL)
t
brown
stiff
2
10
'9000.
10.0
SS
3
4
SANDY CLAYEY SILT (ML•CL) SS
23
I '8000
12.1
tan
5
stiff to very stiff
-
6
7
8
SANDY LEAN CLAY (CL)
brown
stiff
SS
9
10
11
I -8500
19.0
11
12
more sand with depth
13
14
11 I
15500
18.3
_ _
ISS
15
BOTTOM OF BORING 15'
16
17
18
19
20
21
22
23
24
25
Earth Engineering Consultants
ROCKBRIDGE CONDOMINIUMS
FORT COLLINS, COLORADO
PROJECT NO: 1952085 DATE: NOVEMBER 1995
LOG OF BORING B-4
RIG TYPE: CME45
SHEET 1 OF 1
WATER DEPTH
FOREMAN: EDT
START DATE
1116195
WHILE DRILLING
None
AUGER TYPE: 4" CFA
FINISH DATE
11/6195
AFTER DRILLING
I None
SPT HAMMER: MANUAL
SURFACE ELEV
N/A
24 HOUR
NIA
SOIL DESCRIPTION
D
N
OU
MC
DD
A -LIMITS
-200
SWELL
LL
FI
PRESSURE
500 PSF
TYPE
(FEET)
(BLOWSIFT)
IPSFI
fXl
IPCF)
(A)
5" TOPSOILIVEGETATION
1
SANDY LEAN CLAY (CL)
tan
2
10
•9000+
10.2
stiff to very stiff SS
3
4
11
•8500
1 1s.o 7-7
ss
s
6
7
SANDY LEAN CLAY WITH GRAVEL (CL)
red/brown
stiff
8
9
15
•9000.
I 12.3
i
10
11
12
13
SANDY LEAN CLAY (CL)
brown
14
12
-9000*
15.6
stiff to very still SS
15
BOTTOM OF BORING 15'
-
16
17
18
19
20
21
22
23
24
25
Earth Engineering Consultants
ROCKBRIDGE CONDOMINIUMS
FORT COLLINS, COLORADO
PROJECT NO: 1952085 DATE: NOVEMBER 1995
LOG OF BORING B•3
RIG TYPE: CME45
SHEET 1 OF 1
WATER DEPTH
FOREMAN: BDT
START DATE
1 1116195
WHILE DRILLING
None
AUGER TYPE: 4-CFA
FINISH DATE
11/6195
AFTER DRILLING
None
SPT HAMMER: MANUAL
SURFACE ELEV
I NIA
24 HOUR
N/A
SOIL DESCRIPTION
D
I N
Ou
MC
DO
A -LIMITS
-200
SWELL
LL
PI
PRESSURE
%R 500 CSF
TYPE
IFEETI
ISLOWSIFT)
(PSF)
(•n)
(PCF)
I%)
5" TOPSOIL/VEGETATION
1
SANDY LEAN CLAY JCL)
tan/light brown
2
IO
•8500
14.0
sitff to very stiff SS
3
4
11
I -9000+
I 11.3
SS
5
6
7
8
9
SS
22
•9000+
17.6
SANDY LEAN CLAY (CL)
10
brown/tan
stiff
11
12
13
14
COARSE SAND (SP)
SS
17
•1500
20.0
brown, medium dense
15
BOTTOM OF BORING 15'
16
17
18
19
20
21
22
23
24
25
tarEn t_ngineenng consunants
ROCKBRIDGE CONDOMINIUMS
FORT COLLINS, COLORADO
PROJECT NO: 1952085 DATE: NOVEMBER 1995
LOG OF BORING B-2
RIG TYPE: CME45
SHEET 1 OF 1
WATER DEPTH
FOREMAN: SOT
STARTDATE
11/6195
WHILE DRILLING
I 19.0
AUGER TYPE: 4" CFA
FINISH DATE
1116195
AFTER DRILLING
NIA
SPT HAMMER: MANUAL
SURFACE ELEV
NIA
24 HOUR
NIA
SOIL DESCRIPTION
D
N
I OU
MC
I DD
ALIMITS
-200
SWELL
LL
PI
PRESSURE
R Q SW PSF
TYPE
(FEETI
ISLOWLFT)
IPSF)
IXI
IPCF)
(%1
5" TOPSOIL(VEGETATION
SANDY LEAN CLAY(CL)
1
brownfli0ht brown
stiff to very stiff
2
SILTY SANDY LEAN CLAY WITH ss
45
I -8000
3.3
GRAVEL(CL)
tan/white
_3_
stiff to very stiff
4
I 28
L .5500
4.2
I
ss
SAND AND GRAVEL, TRACE
5
FINES (SP/SC)
-
red/brown
6
medium dense to loose
more clay with depth
i
8
9
Ss
14
I •9000+
10.3
I
COARSE SAND AND GRAVEL (SP/GP)
10
redttan/brown
loose to medium dense
11
12
13
14
14
I 5.1
SS
15
16
17
18
19
20
21
22
WEATHERED SHALE
olivelrust/gn
soft to moderately hard
23
24
22.7
AS
BOTTOM OF BORING 25'
25
Earth Engineering Consultants
ROCKBRIDGE CONDOMINIUMS
FORT COLLINS, COLORADO
PROJECT NO: 1952085 DATE: NOVEMBER 1995
LOG OF BORING B•1
RIG TYPE: CME45
SHEET 1 OF 1
WATER DEPTH
FOREMAN: BDT
START DATE
1116195
WHILE DRILLING I None
AUGER TYPE: 4" CFA
FINISH DATE
1116/96
AFTER DRILLING 1 None
SPT HAMMER: MANUAL
SURFACE ELEV
N/A
24 HOUR I NIA
SOIL DESCRIPTION
D
N
DU
MC
OD
A -LIMITS
.200
SWELL
LL
PI
PRESSURE
% $00 PSF
TYPE
IFEETI
(BLOWSIFT)
IPSFI
1•AI
(PCF)
1%)
5" TOPSOILNEGETATION
1
SANDY LEAN CLAY (CL)
brown/light brown
2
35
'9000•
9.6
stiff to very Stitt .SS
3
SANDY LEAN CLAY (CL)
tanked
4
1
43
'9000.
4.6
very stiff SS
6
less clay with depth
gravel with depth
6
7
8
SANDY SILTY LEAN CLAY (CL)
redttan
9
20
-3000
7.7
stiff Ss
10
11
12
LEAN CLAY W/ VERY LITTLE SAND (CL)
tan/red
soft
13
14
8 I
'3500
7.7
SS
15
BOTTOM OF BORING 15'
16
17
18
19
20
21
22
23
24
25
Earth Engineering Consultants
B-3
N
B-4
B-2
B-7
u
C
B-5
B-1
0
B-6 _
0
w
x
HARMONY DRIVE
BORING LOCATION DIAGRAM
ROCKBRIDGE CONDOMINIUMS
FORT COLLINS, COLORADO
EARTH
ENGINEERING
CONSULTANTS
I, 1
Earth Eneineerine Consultants. Inc.
Rockbridee Condominiums
November 10, 1995
- Paoe 7
construction. If variations appear evident, it will be necessary to re-evaluate the recommendations
of this report.
It is recommended that the geotechnical engineer be retained to review the plans and specifications
so that comments can be made regarding the interpretation and implementation of our geotechnical
recommendations in the design and specifications. It is further recommended that the geotechnical
engineer be retained for testing and observations during earthwork and foundation construction
phases to help determine that the design requirements are fulfilled.
This report has been prepared for the exclusive use of The Nichols Partnership, Inc. for specific
application to the project discussed and has been prepared in accordance with generally accepted
geotechnical engineering practices. No warranty, express or implied, is made. In the event that
any changes in the nature. design or location of the project as outlined in this report are planned,
the conclusions and recommendations contained in this report shall not be considered valid unless
the changes are reviewed and the conclusions of this report modified or verified in writing by the
geotechnical engineer.
Earth Engineering Consultants, Inc.
Rockbridge Condominiums
November 10, 1995
Pate 6 .
After preparation of the subgrades, care should be taken to avoid disturbing the in -place materials.
Subgrade materials which are loosened or disturbed by the construction activities or materials
which become dry and desiccated or wet and softened should be removed and replaced or
densified in place prior to construction of the overlying floor slabs or pavements.
Positive drainage should be developed away from the new buildings to avoid wetting the bearing
or subgrade materials. Positive drainage should also be developed across and away from the
pavement edges to avoid wetting the pavement base and/or subgrade.
Pavements
We anticipate the traffic on the on -site pavements will involve low to moderate volumes of light
vehicles including automobiles and light trucks. Based on previous experience with similar
subgrade and traffic conditions, we recommend the pavement section for this project consist of
3 inches of hot bituminous pavement overlying 6 inches of aggregate base. Asphalt for the
pavement should consist of SCI or SCII surface asphalt in accordance with City of Fort Collins
standard criteria. Aggregate base should be compatible with. Class 5 or Class 6 base as defined
by Colorado Department of Transportation Standard Specifications for Road and Bridge
Construction.
Thinner pavement sections could be used in areas where the pavement will be used solely for
parking of automobiles. The recommended pavement section is a minimum and, as such, periodic
maintenance should be expected.
GENERAL COMMENTS
The analysis and recommendations presented in this report are based upon the data obtained from
the soil borings performed at the indicated locations and from any other information discussed in
this report. This report does not reflect any variations which may occur between borings or
across the site. The nature and extent of such variations may not become evident until
c
9
Earth Engineering Consultants, Inc.
Rockbridee Condominiums
November 10, 1995
Page 5
minimum width of 30 inches. Trenched foundations could be used in the near surface cohesive
soils. If used, we recommend those foundations have a minimum width of 12 inches.
Care should be taken during construction to avoid disturbing the bearing materials. Materials
which are loosened or disturbed by the construction activities. or materials which become dry and
desiccated or wet and softened should be removed and replaced prior to placement of foundation
concrete.
We estimate the lone -term settlement of footing foundations designed and constructed as outlined
above would be less than 3/4 inch.
Floor Slab and Pavement Subgrades
All existing vegetation and/or topsoil should be removed from the floor slab areas. After
stripping and completing all cuts and prior to placement of any floor slabs, fill or pavements, we
recommend the exposed subgrades be scarified to a minimum depth of 9 inches, adjusted in
moisture content and compacted to at least 95 % of the material's maximum dry density as
determined in accordance with ASTM Specification D-698, the standard Proctor procedure. The
moisture content of the scarified soils should be adjusted to be within the range of ±2% of
standard Proctor optimum moisture prior to compaction.
Fill materials required to develop the floor slab or pavement subgrade should consist of approved.
low -volume change soils which are free from organic matter -and debris. Normally, low volume
change soils will have a liquid limit of 40 or less and plasticity index of 18 or less. Based on
results of the field borings and laboratory testing, we believe the near surface soils could be used
as low -volume change fill beneath the floor slabs and pavements. Soils in these areas should be
placed in loose lifts not to exceed 9 inches thick, adjusted in moisture content as recommended
for the scarified materials and compacted to at least 95 % of the material's maximum dry density
as determined in accordance with the standard Proctor procedure.
J
Earth EnEineering Consultants, Inc.
Rockbridge Condominiums
November 10, 1995
Page 4
WATER LEVEL OBSERVATION
Observations were made while drilling and after completion of the borings to detect the presence
and depth to hydrostatic groundwater. Free water was observed only in boring B-2 at the time
of drilling. The depth to groundwater at that location was approximately 19 feet. The site
cohesive soils would have low permeability so that longer term observations would be required
to more accurately evaluate groundwater conditions. Zones of perched and/or trapped water may
also be encountered at times throughout the year in the more permeable zones in the interbedded
soils. The location and amount of perched/trapped water and the depth to the h} drostatic
groundwater table can vary over time depending on hydrologic conditions and other conditions
not apparent at the time of this report.
ANALYSIS AND RECONUMENDATIONS
Foundations
Based on results of the field borings and laboratory testing as outlined in this report, it is our
opinion the proposed condominium buildings could be supported on conventional footing
foundations bearing in the natural site soils. We recommend footing foundations extend through
all existing vegetation and/or topsoil and bear in the natural, stiff to very stiff sandy lean clay or
medium dense silty/clayey fine to medium sand. For design of footing foundations bearing on the
natural, stiff to very stiff cohesive soils or medium dense essentially granular materials, we
recommend using a net allowable total load soil bearing pressure not to exceed 2,500 psf. The
net bearing pressure refers the pressure at foundation bearing level in excess of the minimum
surrounding overburden pressure. Total load should include both dead and live loads. A
minimum dead load pressure of 500 psf should be used on the footings to reduce the potential for
movement of the footings with moisture fluctuations in the bearing soils.
Exterior foundations and foundations in unheated areas should be located a minimum of 30 inches
i
below final adjacent exterior grades to provide frost protection. We recommend formed
continuous footings have a minimum width of 16 inches and isolated column foundations have a
Earth Eneineerin_ Consultants, Inc.
Rockbridse Condominiums
November 10, 1995
— Pa2e 3
grass Around covering. Site drainage appears to be the south and east with maximum difference
in ground surface elevations across the site on the order of 2 to 3 feet. Evidence of prior building
construction was not observed at the site by EEC field personnel.
An EEC geologist was on site during drilling to evaluate the subsurface materials encountered and
direct the drilling activities. Field loos prepared by the EEC geologist were based on visual and
tactual observation of disturbed samples and auger cuttings. Final boring logs included with this
report may include modifications to those field logs based on the results of laboratory testing and
engineering evaluation. Based on the results of the field borings and laboratory testing.
subsurface conditions can be generalized as follows.
Approximately 4 to 5 inches of vegetation and/or topsoil was encountered at the ground surface
at the boring locations. The topsoil/vegetation was underlain by brown and light brown lean clay
with varying amounts of silt and sand. The cohesive soils were stiff to very stiff and exhibited
low to moderate plasticity. At some boring locations. interbedded zones of silry/clayey sand were
encountered in the predominately cohesive soil subgrade. The thickness of the granular or
essentially granular soils ranged from 2 to 6 feet. The granular site soils were medium dense.
The interbedded cohesive and granular soils extended to depth of approximately 21 feet in boring
B-2 and to the bottom of the other borings at depths of approximately 15 feet.
In boring B-2, the overburden soils were underlain by highly weathered shale bedrock. The shale
bedrock was colored light brown and was soft to moderately hard. Those materials were
moderately to highly plastic. The highly weathered bedrock extended to the bottom of boring B-2
at a depth of approximately 25 feet below existing ground surface.
The stratification boundaries indicated on the boring logs represent the approximate locations of
changes in soil and rock types; in -situ, the transition of materials may be gradual and indistinct.
Classification of the bedrock was based on visual and tactual observation of disturbed samples
Iand auger cuttings. Coring and/or petrographic analysis may reveal other rock types.
J
Earth Ensineering Consultants, Inc.
Rockbridee Condominiums
November 10. 1995
Paee 2
The borings were performed using a truck mounted. CME 45 drill rig, equipped with a hydraulic
head employed in drilling and sampling operations. The boreholes were advanced using 4-inch
nominal diameter continuous flight augers and samples of the subsurface materials encountered
were obtained using split -barrel sampling techniques in general accordance with ASTM
Specifications D-1546. In the split -barrel sampling procedure, a standard 2-inch O.D. split -barrel
sampling spoon is driven into the ground by means of a 140 pound hammer falling a distance of
30 inches. The number of blows required to advance the split barrel sampler is recorded and is
used to estimate the in -situ relative density of cohesionless materials and, to a lesser degree of
accuracy, the consistency of cohesive soils and hardness of weathered bedrock. All samples
obtained in the field were sealed and returned to the laboratory for further examination,
classification and testing.
Moisture content tests were performed on each of the recovered samples. The unconfined
compressive strength of appropriate samples was estimated using a calibrated hand penetrometer.
Atterberg limits and washed sieve analysis tests were performed on selected samples to establish
the quantity and plasticity of fines in the subgrade materials. Swell/consolidation tests were also
performed on selected samples to evaluate the soils tendency to change volume with variation in
moisture content. Results of the outlined tests are indicated on the attached borine log and
summary sheets.
As a part of the testing program, all samples were examined in the laboratory by an engineer and
classified in accordance with the attached General Notes and the Unified Soil Classification
System, based on the soil's texture and plasticity. The estimated group symbol for the Unified
Soil Classification System is shown on the boring logs and a brief description of that classification
system is included with this report.
SITE AND SUBSURFACE CONDITIONS
The Rockbridge Condominiums will be constructed north of Harmony Road and west of Wheaton
Drive in Fort Collins, Colorado. The development site is an existing open field with weed and
9
SL"BSLRFACE EXPLORATION REPORT
PROPOSED ROCKBRIDGE CONDOMINIUMS
HARMONY ROAD AT WHEATON DRIVE
FORT COLLINS, COLOR -ADO
EEC PROJECT NO. 1952085
INTRODUCTION
The subsurface exploration for the proposed Rockbridge Condominiums at Harmony Road and
Wheaton Drive in Fort Collins. Colorado, has been completed. Seven soil borings extending to
depths ranging from approximately 15 to 25 feet below present site grades were advanced in the
proposed development area to obtain information on existing subsurface conditions. Individual
boring Ions and a diagram indicating the approximate boring locations are included with this
report.
We understand this project involves the development of approximatel} 10 acres of open field
located north of Harmony Road and west of Wheaton Drive in Fort Collins. Colorado. The
development will include 24, 17 and 26 plex condominium units as two and three-story wood
frame structures. Foundation loads for the proposed buildings will be light with continuous wall
loads less than 4 kips per lineal foot and column loads less than 100 kips. Paved drive and
parking areas will be constructed as a part of the condominium development. Cuts and fills less
than 2 feet will be required to develop the final site grades.
The purpose of this report is to describe the subsurface conditions encountered in the borinss.
analyze and evaluate the test data and provide geotechnical recommendations concerning design
and construction of foundations and support of floor slabs and pavements.
EXPLORATION AND TESTING PROCEDURE
The boring locations were established in the field by Earth Engineering Consultants, Inc. (EEC)
personnel. The field locations were determined by pacing and estimating angles from the
references indicated on the attached boring location diagram. The locations of the borings should
be considered accurate only to the degree implied by the methods used to make the field
measurements.
I
0-1
November 10. 1995
The Nichols Partnership. Inc.
>j Madison Street. Suite 280
Denver, Colorado 80206
Attn: Ms. Joii Robertson
Re: Subsurface Exploration Report
RockbridQe Condominiums
Harmony Road and Wheaton Drive
Fort Collins. Colorado
EEC Project No. 1952085
Ads. Robertson:
EARTH ENGINEERING
CONSULTANTS, INC.
Enclosed, herewith, are the results of the subsurface exploration you requested for the RockbridQe
Condominiums to be constructed northwest of the intersection of Harmony Road and Nk7heaton Drive
in Fort Collins. Colorado. In summary, the subsurface soils at this site consisted of low plasticity
cohesive materials with varying amounts of sand interbedded with essentially granular materials
containing van-ing amounts of low plasticity fines. Weathered shale bedrock was encountered at
a depth of approximately 21 feet in one of the test borings. Based on the results of the field borings
and laboratory testing, it is our opinion the near surface soils could be used for direct support of the
proposed site structures using conventional footing foundations. The near surface low plasticity soils
could also be used for direct support of floor slabs and pavements for this project.
Geotechnical recommendations concerning design and construction of foundations and support of
floor slabs and pavements are presented in the text of the attached report. If you have any questions
concerning the enclosed report, or if we can be of further service to you in any other wvay, please do
not hesitate to contact us.
Very truly yours.
Earth Engineering Consultants, Inc.
Lester L. Litton. P.E.
' Principal Engineer
LLL/dmf
Centre For Advanced Technology
2301 Research Boulevard, Suite 104
Fort Collins, CO 60526
(970) 224-1522 FAX 224-4564
SUBSURFACE EXPLORATION REPORT
ROCKBRIDGE CONDOMINIUMS
HARMONY ROAD AND WHEATON DRIVE
FORT COLLINS, COLORADO
EEC PROJECT NO. 1952085