HomeMy WebLinkAboutPARK SOUTH COMMERCIAL PLAZA - MINOR SUBDIVISION - 37-94 - CORRESPONDENCE - STAFF'S PROJECT COMMENTSt
8. The alignment of the shared access, separating Lots 2 and 3,
must be consistent and line up with the location of the access
road identified on the ODP for the property to the west of
Manhattan Avenue. From review of the plans, it appears that
this access easement does not line up. Street standards
require that driveways and streets either align or be off -set
a minimum of 200' centerline to centerline. It appears that
this shared access will need to be moved further to the south
in order to align.
9. Does the ditch easement include enough space for the ditch
riders' access road?
10. The outer boundary monuments must be described.
11. Both of the control monuments must be described.
12. Please show the "right angle" width of Horsetooth Road from
the section line.
13. The plat does not close, (0.651 N-S, 0.003.E-W).
14. At the time of development, fire hydrants will have to be
located within 400' of. any building, capable of 1000 gpm with
20 psi residual pressure. At the time of submittal of
development plans, please show location of hydrants on the
site plan.
This concludes staff comments at this time. I have tentatively
scheduled the public hearing for this minor subdivision for
Tuesday, July 26, 1994 at 1:30pm. The hearing will be held at the
Planning Department conference room, located at 281 N. College
Avenue. We will send out notification letters and notify the
newspaper. Please contact your engineer about making the above
corrections to the plat and bring a signed mylar of the plat to the
hearing.
If you have any questions about these comments or would like to
schedule a time to meet to discuss them, please contact me at 221-
6750.
Sincerely,
Kirsten Whetstone, AICP
City Planner
cc Kerrie Ashbeck, Engineering Department
Stewart and Associates
.:f
City of Fort Collins
Comm:. _.y Planning and Environmental ,,rvices
Planning Department
July 13, 1994
Loren Dilsaver
Dilsaver Development Cc
1423 Front Nine Drive
Fort Collins, CO 80525
Dear Mr. Dilsaver,
City Staff has reviewed your submittal for the Park South
Commercial Plaza Minor Subdivision and offers the following written
comments:
1. Review of these plans should not be construed as a commitment
that telephone facilities sufficient to serve this project are
presently available. US West will provide telephone service
in accordance with the rates and tariffs on file with the
Colorado Utilities Commission.
2. Telephone facilities generally occupy rear lot utility
easements, which must be located on terrain which permits
trenching operations.
3. The owner is responsible for provision of all conduit, ditch,
and street crossings for telephone facilities within the
project, and the owner provides terminal room space and power
for the main terminal at one building, generally in a
janitors' closet or utility room. The owner's vendor provides
all facilities beyond the main terminal. Contact the US WEST
engineer for conduit specifications for the main telephone
entrance cable.
4. Any relocation of existing telephone facilities required by
these plans will be paid for by the developer.
5. At the time a development proposal is submitted, utility
plans, development agreement, drainage report and plans, site
and landscape.plans, etc. will be required for City review.
6. The utility easement along Horsetooth Road should be 15' wide,
not 12'.
7. The north -south 20' wide utility easement should be 30' wide
if it is for water or sewer mains.