Staff has reviewed your documents for the Horsetooth East Business Park PUD, 3rd
Filing (Rite Aid), that were submitted on November 24, 1998 and offers the following
comments:
The Current Planning Department stated the following:
a. Thank you for submitting proposed easements. However, there are no
dedication statements or signatures on the easements. An 8-foot grading
easement, a 6-foot water easement and a 12-foot access easement are
needed on the west property line. Please submit all signed easements in a
form acceptable to the City of Fort Collins. Please see the attached sample
easement for the acceptable format.
b. Elevations of all sides of the enclosure must be provided in the PUD plan set
(Site Plan, Landscape Plan or Building Elevations). Specific enclosure
materials and colors must be labeled.
C. The Site Plan and Landscape Plan indicate that there is ten feet of
separation from the back -of -walk to the edge of the retaining wall for the
detention pond. However the cross section indicates that there is 25 feet (30
feet from flow line to the wall less a 5-foot sidewalk). Please clarify.
Materials for the wall should match the building.
d. Please connect trees that are referenced by the same species / quantity
label with a leader line on the Landscape Plan.
e. Please provide 4 feet of separation distance between the fire hydrant and
shrubs in the parking lot island along the west property line at the north
building line extended.
f. Please provide 4 feet of separation distance between the meter pit and
shrubs on the west side of the trash enclosure.
281 North College Avenue • PO. Box 580 • Fort Collins, CO 80522-0580 • (970) 221-6750 • FAX (970) 416-2020
Nov-23-98 02:24P Northern Engineering 970 221 4159 P.02
I EXISTING WATER
/— EXISTING 4' SAN. _ SERVICES TO BE
SERVICE TO ABANDONED
REMAIN I
PROPOSED SAN.
MANHOLE C ON
13+46.71 EXISTING 8" 4Dt LF 8' D.I.P.
SEWER WATERLINE STUB
— — — —
EXISTING SAN. \ ,
MANHOLE TO
REMAIN EXISTING 8" SAN
r I \ SEWER TO BE
•� � r ems__ ` ABANDONED
EXISTING 8" \
WATERLINE
TO REMAIN LA
1-8" 45' BEND W/T.E
i / \ 1-8':8' TEE AND
1-e' GV W/T.B.
PROPOSED
30mO CLASS 11
\ RCP
:-'XISTING FIRE 30t LF 8" / \
RA W/G. DIP WATERLINE
O RE N /
REMOVE ALL
EXISTING FITTINGS AND mbiI. 8.
CONNECT TO EXISTING 8" SAN. SEWER.
WATERINE TO WEST / 99.59t PROP. SAN.
WITH 8" G.V. / / / 4518' HOLE
WAATTEERRLINEREMOVE TO SOUTH
LFr JTY PLAN DETAIL
SCALE: 1'-20'
REVISION
COMMENT SHEET
DATE: November 24, 1998 DEPT: Water/Wastewater
PROJECT: #43-94G Horsetooth East Business Park, 3rd
Filing, (Rite Aid) LDGS — Final P.U.D.
All comments must be received by Mike Ludwig no later than the staff
review meeting:
Wednesday, December 9, 1998
Coordinate proposed water and sewer layout in shared private drive with Northern
Engineering. Show coordinated layout for both project in this area.
Coordinate landscape design with civil design and provide required landscape/utility
separation distances.
Provide 10 feet of separation between water/sewer lines and light poles.
i Clearly define area of concrete encasement of sewer line in plan and profile views.
Realign water service and fire line to avoid service line being place in thrust block.
i No connection may be made to water service between main and a point 5 feet downstream of
the meter pit. Relocate proposed irrigation tap on water service to provide 5 feet of
separation.
See site, landscape and utility plans for other comments.
Date:
Signature:
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
X Plat X Site Drainage Report _Other
X Utility X Redline Utility X Landscape
Y
City of Fort Collins
3. On the grading plan, please indicate invert elevations at the ends of storm sewer pipes
and provide spot elevations for the spillway/top of berm.
RESPONSE:
4. Please provide a detail of the 18" concrete channels.
RESPONSE:
5. For the storm sewer profiles, please indicate the pond 100-year WSEL only where it
is applicable — it is currently a bit misleading. In addition, the profile for storm line D
does not appear to show the retaining wall correctly — please revise to match actual
conditions.
RESPONSE:
Erosion/Sediment Control Comments
1. The erosion control plan is ok.
Please refer to the redlined plans and report for additional review comments
HrsethEBp-b&c4.doc .
REVISION
COMMENT SHEET
DATE: November 24, 1998 TO: Stormwater
PROJECT: #43-94G Horsetooth East Business Park, 3rd
Filing (Rite Aid) - Final P.U.D. (LDGS)
All comments must be received by Mike Ludwig no later than the staff
review meeting:
Wednesday, December 9, 1998
❑ No Comment
Problems or Concerns (see below or attached)
1. The plat which is included in the Final Utility Plans does not have all the necessary
drainage easements shown; however, the plat which was included separately does so.
Please include the updated plat in the Final Utility Plans.
RESPONSE:
2. The outlet of storm line B is shown to have an invert elevation of 47.48. However,
the plan view shows the outlet between contours 49 and 50. Please change plan view
of storm sewer to clarify this discrepancy.
RESPONSE:
(continued on
Date: t CV Signature: LIIJ ��
cc Mx
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS a:.
XPW _ Site XDra*e Repot Other
14ltiliity X' Redline Utility _ bn6* w= c�.�« E.. us
City of Fort Collins
DATE: November 24, 1998 TO: Engineering
PROJECT: #43-94G Horsetooth East Business Park, 3rd
Filing (Rite Aid) - Final P.U.D. (LDGS)
All comments must be received by Mike Ludwig no later than the staff
review meeting:
Wednesday, December 9, 1998
❑ No Comment
Problems or Concerns (see below or attached)
Horsetooth East Business Park, 3`d Filing December 17, 1998
• A sketch and a legal description for one of the easements was received, nothing more was received.
• Prior to this project being scheduled for a hearing either 1) letters of intent for all off -site easements
must be received or 2) Signed easements for all off -site easements must be received. An compete
easement document consists of a Deed of dedication with proper language and all signatures (original,
no copies), legal description, attorney certification and sketch.
Plat
• The amount of Row to be dedicated on Horsetooth Road is to be 57.50 feet
• The ordinance in which Elk Road and Otter Drive were vacated by is No. 213, 1998. The areas that
were vacated were retained as emergency access, utility and drainage easements. Need to show this
area as being such or show that it is being vacated.
• Need to make sure that the off -site easements being dedicated by the second filing are reflected on this
plat if they are within the platted area. Depending on timing they may or may not be recorded prior to
this plat being filed.
Utility plans
• Section A on Sheet C4.10 shows the retaining wall to be located 25 feet behind the sidewalk. Scaling
off of the plan this distance is only approx. 10 feet. Which is correct?
Date: j 2/l u 1 ` 5 Signature:
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
✓Pict _ Site _ Dla We Report _ Oler
vt9Glity _ Redline Utility _ landscape
City of Fort Collins
2. Comments and redlined plans from the Engineering Department are attached.
Please return all redlined documents with plan revisions.
3. Comments and redlined utility plans from the Stormwater Utility are attached.
Please return all redlined documents with plan revisions.
4. Comments and redlined utility plans from the Water and Wastewater Utility are
attached. Please return all redlined documents with plan revisions.
This completes the review comments at this time. Additional comments may be
forthcoming as the various departments and reviewing agencies continue to review this
request.
All revisions must be received by noon on Monday December 21, 1998 to have the
project reviewed at the December 23, 1998 Staff Review for potential placement on
the January 21, 1999 Planning and Zoning Board Hearing.
The ability of this project to be placed on the January 21, 1999 P&Z agenda is also
subject to the Horsetooth East Business Park 2nd Filing being scheduled for the
same meeting.
Please contact Bob Blanchard at 221-6750 if you have any questions or concerns related
to these comments.
Sincerely,
Michael Ludwig, AICP
City Planner