Issue Contact: Mark Jackson
Development agreement for Buckingham improvements
Have development agreement in place that guarantees improvements to
Buckingham, including connection to the existing sidewalk system, occur with
the next phase of development and no later than a date to be specified by the
City in conjunction with the developer. This is per our meeting with the
applicant on June 25th. Sheri Wamhoff and Ted Shepard also were in
attendance.
Is it appropriate to have a note on the site plan referrinq to this aqreement?
Issue Contact. Mark Jackson
Repeat previous comment (7/17) re: developer agreement about Buckingham
improvements
Water Wastewater
77
78
79
80
Zoning
2
4
Issue Contact: Jeff Hill
Water mains may not be located in the bottom of drainage swales.
Issue Contact: Jeff Hill
Provide all information necessary for the steel casing on the proposed water
main at the rail spur crossing (Le. Diameter, wall thickness, etc.).
Issue Contact: Jeff Hill
Include the steel casing detail with the next submittal. if required, include the
typical water service and meter pit details.
Issue Contact. Jeff Hill
Provide sufficient room in the proposed drive for the future water main
extension.
Issue Contact: Jenny Nuckols
Chain link fences arilince
owed - 3.8.11(B)
7-10-01 Is the chain for screening purposes or security purposes?
3.8.11(B) does not ascreening - please clarify.
Issue Contact. Jenny Nuckols
Site plan - need to see building envelope, dimension, distance to property lines
7-10-01 REPEAT COMMENT
3of4
6 Issue Contact: Jenny Nuckols
General notes #5 - refers wilding and pole mounted lighting but I don't see
any lights referenced on th ite plan or elevation - please review
7-10-01 REPEAT COMM
72 Issue Contact: Jenny Nuckols
Above comments don't ap ea t have been resolved. If Planning has ok'd
these items, please let me otherwise the above still need to be
addressed.
Be sure and return all of your redlined plans when you re -submit.
If you have questions regarding these issues or any other issues related to this project,
please feel free to call me at (970) 221-6750.
Yours Truly,
TED SHEPARD
City Planner
4of4
f
Issue Contact: Ron Gonzales
WATER SUPPLY
A fire hydrant is required Win 300 ft of the building. T
11 Issue Contact. Ron Gonzales
FIRE SPRINKLERS
Sprinklers required for expansion fire protection. PO o a C T� n ,-rs P4�n,v
Also required in H-7 Occupancy.
12 Issue Contact., Ron Gonzales
HAZMAT
Enough hazmat (corrosives) to warrant H-7 Occupancy. All UFC Art. 80
systems required for use and storage of corrosives.
13 Issue Contact. Ron Gonzales
KNOX BOX REQUIRED
58 Issue Contact: Michael Chavez
Refer to comments by Ron Gonzales posted 6-5-01
Stormwater Utility
75 Issue Contact: Basil Harridan
The retention pond along Buckingham should be called out on the
landscape plan and a wetland seed should be specified for that pond
as was done for the north retention pond.
As a reminder, the applicant will need to submit a floodplain use permit
prior to issuance.
All other comments by Stormwater were addressed. We are ready
ready to accept utility plan mylars. Please provide two additional signed
and stamped copies of the drainage and erosion control report along with
the mylars for approval.
Transportation Planning
27 Issue Contact. Mark Jackson
-Need to make improvements to frontage on Buckingham, including connection
of sidewalk from its current termination at 1 st street east to site boundary. S&F R
Improve sidewalk, parkway, bike lanes to Collector Street standards.
29 Issue Contact: Mark Jackson
Buckingham cross section shown in the TIS is incorrect. 4' Bike Lanes are not
satisfactory. fgzv«6 ONE 'Osfe-c Z'e-r ck .
2of4
s
V
6a STAFF
BHA Design
Luke Oldenburg
4803 Innovation Drive
Fort Collins, CO 80525
%'-rG/� K<
L Vic 6- d -
PROJECT REVIEW
o_3-01
Date: 8/8/01
Staff has reviewed your submittal for NEW BELGIUM BREWERY - PROCESS WATER
FACILITY, PDP and FINAL COMPLIANCE #1-95D AND 1-95E, and we offer the following
comments:
ISSUES:
Engineering
60 Issue Contact. Sheri Wamhoff
Need to show the new row line on the site and landscape plans
What is shown is not correct, per the plat the north half of the row will be 38 feet
not 30 feet.
66 Issue Contact. Sheri Wamhoff
The ditch easement on the plat is this part of the easement that was dedicated
at reception # 9502257? Is this new? If it is new the ditch co will need to sign
the plat accepting the easement. As shown the ditch co will need to sign the
plat. Provide a signature block for there acceptance of the easement.
73 Issue Contact: Sheri Wamhoff
See the plat - an additional foot of row is needed for a total of 22'
74 Issue Contact: Sheri Wamhoff
comments on the prelliminary layout design - The 50 foot flow line needs to be
measured from the current south flowline.
The road section at the future access drive needs to include a 12 foot center
turn lane. Shown, but not labeled correctly.
The row cross section at this point is 82 feet not 81 feet. The flowline section is
6 feet wider than the standard section for a minor collector.
The cross section label below the scale is incorrect. The section here would be
the standard section.
PFA
7 Issue Contact: Ron Gonzales
ACCESS
A fire lane will be required. Submit a plan for review/approval prior to start of
construction. 1M S , —1-r- &,4,j