Loading...
HomeMy WebLinkAboutHEARTHFIRE PUD, 2ND FILING - FINAL - 31-95E - SUBMITTAL DOCUMENTS - ROUND 1 - DRAINAGE REPORT3.1.7 Time of Concentration In order to use the Rainfall Intensity Duration Curve, the time of concentration must be known. This can be determined either by the following equation or the "Overland Time r Flow Curves" from the Urban Storm Drainage Criteria Manual, included in this report (Se Figure 3-2). Tc=1.87 (1.1 —CC,) D112 S11J Where Tc =Time of Concentration, minutes S = Slope of Basin, % C = Rational Method Runoff Coefficient D = Length of Basin, feet Ct = Frequency Adjustment Factor Time of concentration calculations should reflect channel and storm sewer velocities as well as overland flow times. 3.1.8 Adjustment for Infrequent Storms The preceding variables are based on the initial storm, that is, the two to ten year storms. For storms with higher intensities an adjustment of the runoff coefficient is required because of the lessening amount of infiltration, depression retention, and other losses that have a proportionally smaller effect on storm runoff. These frequency adjustment factors are found in Table 3-4. Table 3-4 RATIONAL METHOD FREQUENCY ADJUSTMENT FACTORS Storm Return Period (years) 2to10 11 to 25 26 to 50 51 to 100 3.2 Analysis Methodology Frequency Factor Ct 1.00 1.10 1.20 1.25 Note: The product of C times C, shall not exceed 1.00 The methods presented in this section will be instituted for use in the determination and/or verification of runoff at specific design points in the drainage system. These methods are (1), the Rational Method and (2) the Colorado Urban Hydrograph Procedure (CUHP). Other computer methods, such as SWMM, STORM, and HEC-1 are allowable if results are not radically different than these two. Where applicable, drainage systems proposed for construction should provide the minimum protection as determined by the methodology so mentioned above. 3.2.1 tWl Wll Rational Method For drainage basins of 200 acres or less, the runoff may be calculated by the Rational Method, which is essentially the following equation: Q = C,CIA Where Q = Flow Quantity, cfs A =Total Area of Basin, acres Ct = Storm Frequency Adjustment Factor (See Section 3.1.8) C = Runoff Coefficient (See Section 3.1.6) 1 = Rainfall Intensity, inches per hour (See Section 3.1.4) Colorado Urban Hydrograph Procedure For basins larger than 200 acres, the design storm runoff should be analyzed by deriving synthetic unit hydrographs. It is recommended that the Colorado Urban Hydrogra^�, Procedure be used for such ana!ysis. This procedure is detailed in the Urban Storm Drain Criteria Manual, Volume 1, Section 4. MAY 1984 . 3-5 DESIGN CRITERIA R-M-P Medium Density Planned Residential District — designation for medium density areas planned as a unit (PUD) to provide a variation in use and building placements with a minimum lot area of 6,000 square feet. R-L-M Low Density Multiple Family District — areas containing low density multiple family units or any other use in the R-L District with a minimum lot area of 6,000 square feet for one -family or two-family dwellings and•9,000 square feet for multiple -family dwellings. M-L Low Density Mobile Home District — designation for areas for mobile home parks containing independent mobile homes not exceeding 6 units per acre. M-M Medium Density Mobile Home District — designation for areas of mobile home parks containing independent mobile homes not exceeding 12 units per acre. B-G General Business District — district designation for downtown business areas, including a variety of permitted uses, with minimum lot areas equal to 1 /2 of the total floor area of the building. B-P Planned Business District — designates areas planned as unit developments to provide business services while protecting the surrounding residential areas with minumum lot areas the same as R-M. H-B Highway Business District — designates an area of automobile -orientated busi- nesses with a minimum lot area equal to 112 of the total floor area of the building. B-L Limited Business District — designates areas for neighborhood convenience centers, including a variety of community uses with minimum lot areas equal to two times the total floor area of the building. C Commercial District —designates areas of commercial, service and storage areas. I-L Limited Industrial District —designates areas of light industrial uses with a minimum area of lot equal to two times the total floor area of the building not to be less than ,- 20,000 square feet. I-P Industrial Park District —designates light industrial park areas containing controlled industrial uses with minimum lot areas equal to two times the total floor area of the building not to be less than 20,000 square feet. I-G General Industrial District — designates areas of major industrial development. T Transition District — designates areas which are in a transitional stage with regard to ultimate development: For current and more explicit definitions of land uses and zoning classifications, refer to the Code of the City of Fort Collins, Chapters 99 and 118. Table 3-3 RATIONAL METHOD RUNOFF COEFFICIENTS FOR COMPOSITE ANALYSIS Character of Surface Runoff Coefficient Streets, Parking Lots, Drives: Asphalt................................................................................................ 0.95 Concrete............................................................................................. 0.95 Gravel................................................................................................. 0.50 Roofs.......................................................................................................... 0.95 Lawns, Sandy Soil: Flat<2%............................................................................................. 0.15 Average2 to 7%.................................................................................. 0. Steep>7%.......................................................................................... 0.20 Lawns, Heavy Soil: Flat<2%............................................................................................. 0.20 Average2 to 7%.................................................................................. 0.25 Steep>7%.........:................................................................................ 0.35 MAY 1984 3-4 DESIGN CRITERIA 3.1.6 Runoff Coefficients The runoff coefficients to be used with the Rational Method referred to in Section 3.2 "Analysis Methodology" can be determined based on either zoning classifications or the types of surfaces on the drainage area. Table 3-2 lists the runoff coefficients for the various types of zoning along with the zoning definitions. Table 3-3 lists coefficients for the different kinds of surfaces. Since the Land Development Guidance System for Fort Collins allows land development to occur which may vary the zoning requirements and produce runoff coeffi- cients different from those specified in Table 3-2, the runoff coefficients should not be based solely on the zoning classifications. The Composite Runoff Coefficient shall be calculated using the following formula C = (s C;A;)/A, i=1 Where C = Composite Runoff Coefficient C; = Runoff Coefficient for specific area A; A; =Area of surface with runoff coefficient of C; n = Number of different surfaces to be considered A, =Total area over which C is applicable; the sum of all A;'s is equal to A, Table 3-2 RATIONAL METHOD RUNOFF COEFFICIENTS FOR ZONING CLASSIFICATIONS Description of Area or Zoning Business: BP, BL........................................................................................ Business: BG, HB, C.................................................................................. Industrial: IL, IP.......................................................................................... Industrial: IG............................................................................................... Residential: RE, RLP.................................................................................. Residential: RL, ML, RP............................................................................. ..Residential: RLM, RMP.............................................................................. Residential: RM, MM.................................................................................. Residential: RH.......................................................................................... Parks, Cemeteries...................................................................................... Playgrounds............................................................................................... RailroadYard Areas................................................................................... Unimproved Areas...................................................................................... Coefficient 0.85 0.95 0.85 0.95 0.45 0.50 0.60 0.65 0.70 0.25 0.35 0.40 0.20 Zoning Definitions R-E Estate Residential District — a low density residential area primarily in outlying areas with a minimum lot area of 9,000 square feet. R-L Low Density Residential District — low density residential areas located throughout the City with a minimum lot area of 6,000 square feet. R-M Medium Density Residential District — both low and medium density residential areas with a minimum lot area of 6,000 square feet for one -family or two-family dwellings and 9,000 square feet for a multiple family dwelling. R-H High Density Residential District —high density residential areas with a minimum lot area of 6,000 square feet for one -family or two-family dwellings, 9,000 square feet for a multiple family dwelling, and 12,000 square feet for other specified uses. R-P Planned Residential District — designation of areas planned as a unit (PUD) to pro- vide a variation in use and building placements with a minimum lot area of 6,000 square feet. R-L-P Low Density Planned Residential District — areas planned as a unit (PUD) to permit variations in use, density and building placements, with a minumum lot area of 6,000 square feet. MAY 1984 3-3 DESIGN CRITERIA No Text DRAINAGE CRITERIA MANUAL RUNOFF 6" 30 F- 2 0 z w U cc IL 10 z w a r; O 5 rn w cc 3 O U 2 w F- 1 .5 �I • I r r 1, I ' r I nil •, a�►�■=�i�■►l�i ■■■■ICI ■'�■■■■�� a 1 2 3 5 10 20 VELOCITY IN FEET PER SECOND FIGURE 3-2. ESTIMATE OF AVERAGE FLOW VELOCITY FOR USE WITH THE RATIONAL FORMULA. *MOST FREQUENTLY OCCURRING "UNDEVELOPED" LAND SURFACES IN THE DENVER REGION. REFERENCE: "Urban Hydrology For Small Watersheds" Technical Release No. 55, USDA, SCS Jan. 1975. 5 -1-84 URBAN DRAINAGE & FLOOD CONTROL DISTRICT APPENDIX III Supporting exhibits, figures, tables, etc. Figure 3-1; City of Ft.. Collins Rainfall Intensity Duration Curve Figure 3-2; Estimate of Average Flow Velocity for Use with the Rational Formula Table 3-3; Rational Method Runoff Coefficients for Composite Analysis Table 3-4; Rational Method Frequency Adjustment Factors Figure 4-2; Reduction Factor for Allowable Gutter Capacity Fig 5-2 Nomograph for Capacity of Curb Opening Inlets in Sumps Fig 5-3; Capacity of Grated Inlet in Sump Table 4 Circular Pipe Flow Capacity for Mannings 'n' = 0.012 Table 5 Circular'Pipe Flow Capacity for Mamungs 'n' = 0.013 CONSTRUCTION SEQUENCE PROJECT: _Hearthfire P.U.D., Second Filing STANDARD FORM C SEQUENCE FOR ONLY COMPLETED BY: MEO / Shear Engineering Corp. Indicate by use of a bar line or symbols when erosion control measures will be installed. Major modifications to an approved schedule may require submitting a new schedule for approval by the City Engineer. Year 197 98 Month S O N D J F M A M J J A OVERLOT GRADING *** WIND EROSION CONTROL * Soil Roughening *** Perimeter Barrier Additional Barriers Vegetative Methods Soil Sealant Other RAINFALL EROSION CONTROL STRUCTURAL: Sediment Trap/Basin *** *** *** *** *** *** *** *** *** Inlet Filters *** *** *** *** *** *** *** *** *** Straw Barriers *** *** *** *** *** *** *** *** *** Silt Fence Barriers Sand Bags Bare Soil Preparation Contour Furrows Terracing Asphalt/Concrete Paving *** *** Other VEGETATIVE: Permanent Seed Planting *** *** Mulching/Sealant Temporary Seed Planting *** *** Sod Installation *** *** Nettings/Mats/Blankets Other STRUCTURES: INSTALLED BY: DEVELOPER MAINTAINED BY: DEVELOPER VEGETATION/MULCHING CONTRACTOR: DEVELOPER DATE PREPARED: 06/26/97 DATE SUBMITTED: 07/16/97 APPROVED BY THE CITY OF FORT COLLINS ON: SHEAR' ENGINEERING CGRPGRATIGN July 16, 1997 Project No: 1552-02-97 Re: EROSION CONTROL SECURITY DEPOSIT REQUIREMENTS: Hearthfire P.U.D., Second Filing; Fort Collins, -Colorado An erosion control security deposit is required in accordance with City of Fort Collins policy (Chapter 7, Section C: SECURITY; page 7.23 of the City of Fort Collins Development Manual). In no instance shall the amount of the security be less than $1000.00. a. The cost to install the proposed erosion control measures is approximately $15,675.00 Refer to the cost estimate attached in Appendix I. 1.5 times the cost to install the erosion control measures is $23,512.50. b. Based on current data provided by the City of Fort Collins Stormwater Utility, and based on an actual anticipated net affected area which will be disturbed by construction activity (approximately 20 acres), we estimate that the cost to re - vegetate the disturbed area will be $10,620.00 ($531 per acre x 20 acres). 1.5 times the cost to re -vegetate the disturbed area is $15,930.00. The $531 per acre cost for re -seeding sites greater than 5 acres was quoted to us by City of Fort Collins Stormwater Utility personnel. CONCLUSION: The erosion control security deposit amount required for Hearthfire P.U.D., Second Filing will be S 23,512.50. 4836 S. College, Suite 12 Ft. Collins, CO 80525 (970) 226-5334 FAX (970) 282-031 1 July 16, 1997 Project No: 1552-02-97 Basil Hamdan City of Fort Collins Stormwater Utility P.O. Box 580 Ft. Collins, Colorado 80522 Re: Erosion Control Cost Estimate Hearthfire P.U.D., Second Filing; Fort Collins, Colorado Dear Basil, Z///,, SHEAR ENGINEERING CORPORATION Attached is the erosion control security deposit estimate for Hearthfire P.U.D., Second Filing. ESTIMATE 1: 9 - Gravel Inlet Filter Q $75.00 each $ 675.00 10 - Haybale barriers ® 75.00 each $ 3,000.00 4000 lineal feet silt fence ® $3.00 per foot $ 12 000.00 TOTAL ESTIMATED COST: $ 15,675.00 x 1.50 S 239512.50 I_M11 M IT0Ifs► re -vegetate the disturbed area of 20 acres at $ 531.00 per acre $ 10 620.00 TOTAL ESTIMATED COST: $ 10,620.00 x 1.5 $ 159930.00 In no instance shall the amount of the security be less than $1,000.00. Therefore, the total required erosion control security deposit for Hearthfire P.U.D., Second Filing will be $239512.50. If you have any questions, please call at 226-5334. Sincerely, Mark Oberschmidt. Shear Engineering Corporation MEO / meo cc: Richards Lake Development Jean Pakech, Stormwater Utility 4836 S. College, Suite 12 Ft. Collins, CO 80525 (970) 226-5334 FAX (970) 282-031 1 EFFECTIVENESS CALCULATIONS PAGE 2 OF 2 STANDARD FORM B PROJECT: HEARTHFIRE P.U.D. SECOND PROJ. NO.1552-01-96 BY: MARK OBERSCHMIDT DATE 07/14/97 ------------------------------------------------------------------------------------------ MAJOR PS SUB AREA CALCULATIONS BASIN % BASIN acre AREA C P ------------------------------------------------------------------------------------------ ALL 84.60% 5 2.71 ROOF 1.12 ACRES 1.00 0.90 SOD 0.75 ACRES 0.01 1.00 EQUATIONS. ASPHALT 0.84 ACRES 0.01 1.00 C = WEIGHTED AVG OF C X AREA P= (WEIGHTED AVG OF P X AREA) X P C= 0.4192 EFF - (1 - P X C) X 100 P = 0.3068 EFF 87.14% ------------------------------------------------------------------------------------------ 6 9.02 ROOF 1.80 ACRES 1.00 0.90 SOD 7.22 ACRES 0.01 1.00 ASPHALT 0.00 ACRES 0.01 1.00 C = 0.2080 P = 0.3136 EFF 93.48% ------------------------------------------------------------------------------------------ 7 10.47 ROOF 2.09 ACRES 1.00 0.90 SOD 8.38 ACRES 0.01 1.00 ASPHALT 0.00 ACRES 0.01 1.00 C = 0.2080 P = 0.3136 EFF 93.48% ------------------------------------------------------------------------------------------ 8 5.31 ROOF 1.06 ACRES 1.00 0.90 SOD 4.25 ACRES 0.01 1.00 ASPHALT 0.00 ACRES 0.01 1.00 WETLAND 1.21 ACRES 0.00 0.00 C = 0.2080 P = 0.4900 EFF 89.81% t+frtttf+ttrffttt+xtr+x+frffrff+ftffxx+f xffffff tf tff+tt+rrtrrf tff tf tf tx+tt+rrrrrrrrffrfff+ SUB TOTAL AREA 27.51 ACRES EFFECTIVENESS = 92.14% TOTAL AREA = 39.31 ACRES OVERALL EFFECTIVENESS = 89.63% > 84.601, CONCLUDE: EROSION CONTROL PLAN IS EFFECTIVE EFFECTIVENESS CALCULATIONS PAGE 1 OF 2 STANDARD FORM B PROJECT: HEARTHFIRE P.U.D. SECOND PROJ. NO.1552-01-96 BY: MARK OBERSCHMIDT DATE 07/14/97 ------------------------------------------------------------------------------------------ EROSION CONTROL C-FACTOR P-FACTOR COMMENT METHOD VALUE VALUE ------------------------------------------------------------------------------------------ ROUGHENED GROUND 1.00 0.9 ROOF AREAS SILT FENCE 1.00 0.5 SUBBASINS 1-5 HAY BALES 1.00 0.8 SUBBASINS 1-5 ! ASPHALT 0.01 1.0 SUBBASINS 1-5 SOD 0.01 1.0 SUBBASINS 1-5 GRAVEL INLET FILTERS 1.00 0.8 SUBBASINS 1-5 ------------------------------------------------------------------------------------------ MAJOR PS SUB AREA CALCULATIONS BASIN % BASIN acre AREA C P ------------------------------------------------------------------------------------------ ALL 84.60% 1 0.78 ROOF 0.27 ACRES 1.00 0.90 SOD 0.18 ACRES 0.01 1.00 EQUATIONS ASPHALT 0.34 ACRES 0.01 1.00 C - WEIGHTED AVG OF C X AREA P- (WEIGHTED AVG OF P X AREA) X P C= 0.3528 EFF = (1 - P X C) X 100 P = 0.3130 ------------------------------------------------------------------------------------------ EFF 88.96% 2 0.90 ROOF 0.30 ACRES 1.00 0.90 SOD 0.20 ACRES 0.01 1.00 ASPHALT 0.40 ACRES 0.01 1.00 C = 0.3400 P = 0.3093 ------------------------------------------------------------------------------------------ Epp 89.48% 3 2.00 ROOF 0.82 ACRES 1.00 0.90 SOD 0.55 ACRES 0.01 1.00 ASPHALT 0.63 ACRES 0.01 1.00 C = 0.4159 P = 0.3069 ------------------------------------------------------------------------------------------ EFF 87.24% 4 8.12 ROOF 3.64 ACRES 1.00 0.90 SOD 2.42 ACRES 0.01 1.00 ASPHALT 0.85 ACRES 0.01 1.00 WETLAND 1.21 ACRES 0.00 0.00 C = 0.4523 P = 0.4031 EFP 81.77% f xtrxxxttttffffffffff tf txtxttttf tfffftxxxf xtx+ttf ttffxtttttftff xxxxtxxxfxxxxxf txx+xxttfff+ SUBTOTAL AREA = 11.8 ACRES EFFECTIVENESS = 83.76% RAINFALL PERFORMANCE STANDARD EVALUATION PROJECT: HEARTHFIRE PUD SEC STANDARD FORM A COMPLETED BY: MARK OBERSCHMIDT DATE: 07/14/97 xxxif++x+f ift+xxxxf r+rrf rtrxxxxxxxx*♦+++xxxi+itxxxixrirrrrr*+x+x+xxx+rift+xxx+++rift+xrxx+ DEVELOPED ERODIBILITY Aeb Lob Sob Lb Sb PS SUBBASIN ZONE (ac) (ft) (}) (feet) (}) (}) x Hfir+++ri+tt++iHe+rrii+rtttt+xi++r++x+if it+tirxrr+Hti+t*xxr ry xixi H tt+xxx+x Hirtxxrxxr 1 MODERATE 0.78 520.00 1.00 406 0.78 2 MODERATE 0.90 420.00 1.20 378 1.08 3 MODERATE 2.00 990.00 1.90 1980 3.80 4 MODERATE 8.12 1285.00 1.90 10434 15.43 5 MODERATE 2.71 955.00 0.90 2588 2.44 6 MODERATE 9.02 400 4.00 3608 36.08 7 MODERATE 10.47 1500 2.00 15705 20.94 8 MODERATE 5.31 200 4.00 1062 21.24 i xxxx**+t+rr+*xxx++++*+xixxxi+*ii+r+xxxx+r*++++x*rtxf rfirrr+rtxxxrirr+r+ 14.51 2492.13 7.01 LINEAR INTERPOLATION SLOPE LENGTH 7.00 7.01 8.00 2000 84.6 84.60 84.6 2492.13 84.60 2500 84.6 84.60 84.7 CONCLUDE:PERFORMANCE STANDARD = 84.60% EROSION CONTROL PLAN OVERALL EFFECTIVENESS MUST EXCEED THIS APPENDIX H ' Erosion Control Calculations. SHEAR ENGINEERING CORPORATION DEVELOPED PAGE 14 FLOW TO CONCENTRATION POINT E FROM SUBBASIN 5 PROJECT: HEARTHFIRE.PUD DATE 07/14/97 LOCATION:TOWN CENTER DRIVE - NORTH SIDE PROJ. N0.1552-01-96 FILE: STORM BY MEO AREA (A)= 2.71 ACRES i RUNOFF COEF.y,(C) 2 YEAR SO YEAR 100 YEAR C 0.74 0.74 0.93 REFER TO SUBBASIN BREAKDOWN ON PAGE 2 TIME OF CONCENTRATION (TO OVERLAND TRAVEL TIME (Ti) LENGTH 30 FEET SLOPE = 2.00 % 2 YEAR 10 YEAR 100 YEAR C = 0.20 0.20 0.25 Ti (min)- 7.33 7.33 6.93 TRAVEL TIME (Tt)=L/(60*V) FLOW TYPE L (ft) - 50 S (%) = 0.50 GUTTER V (fps) = 1.50 Tt(min)= 0.56 L (ft) = 105 S (%) 4.00 GUTTER V (fps) = 4.00 Tt(min)= 0.44 L (ft) - 770 S (%) = 0.50 GUTTER V (fps) = 1.50 Tt(min)= 8.56 L (ft) =7 S (%) _? ? V (fps) _? Tt(min)= 0.00 L (ft) =7 S (%) _? ? V (fps) _? Tt(min)= 0.00 -- L (ft) _? S (%) _? ? V (fps) _? Tt(min)= 0.00 L (ft) =7 S (%) _? ? V (fps) _? Tt(min)= 0.00 NOTE: ALL VELOCITIES TAKEN FROM FIGURE 3-2 TOTAL TRAVEL TIME (min) = 9.55 L = 955 L/180+10 15.31 < 16.47 CHOOSE LESSER Tc =Ti+TOTAL TRAVEL TIME 2 YEAR 10 YEAR 100 YEAR Tc (min)= 15.31 15.31 15.31 USE Tc - 15.5 15.5 15.5 INTENSITY (I) (iph) 2 YEAR 10 YEAR 100 YEAR I = 2.11 3.70 5.98 NOTE: INTENSITIES TAKEN FROM FIGURE 3-1 RUNOFF (Q= CIA) (cfs) 2 YEAR 10 YEAR 100 YEAR QINLET = 4.24 7.44 15.02 CONCLUDE:PIPE DIAM. = 2.00 FT. PIPE TYPE = ADS 0.012 SLOPE = 0.0235 FT/FT SLOPE _ 0.005 FT/FT CONVEYANCE FACTOR= 245.08 - REFER TO TABLE 4 ADS MANUAL CAPACITY = 37.57 CFS ' PIPE OVERSIZED FOR OVERFLOW FROM POND 2 SHEAR ENGINEERING CORPORATION DEVELOPED FLOW TO CONCENTRATION POINT E2 FROM SUBBASIN 5B PROJECT: HEARTHFIRE PUD DATE 07/14/97 LOCATION:TOWN CENTER DRIVE - SOUTH SIDE PROJ. NO.1552-01-96 FILE: STORM BY HBO AREA (A)= 0.77 ACRES PAGE RUNOFF COEF. (C) 2 YEAR 10 YEAR 100 YEAR C = 0.74 0.74 0.92 REFER TO SUBBASIN BREAKDOWN ON PAGE 2 TIME OF CONCENTRATION (Tc) OVERLAND TRAVEL TIME (Ti) LENGTH 50 FEET SLOPE = 1.00 $ 2 YEAR 10 YEAR 100 YEAR C = 0.20 0.20 0.25 Ti (min)= 11.90 11.90 11.24 TRAVEL TIME (TO =L/(60*V) FLOW TYPE L (ft) = 450 - S (6) = 0.50 GUTTER V (fps) = 1.50 Tt(min)= L'(ft) =? S (11) =? ? V (fps) =? Tt(min)= L (ft) =? S (%) =? ? V (fps) =? Tt(min)= L (ft) =? S (%) =? ? V (fps) =? Tt(min)= L (ft) =? S ('a) =? 7 V (fps) =? Tt(min)= L (ft) =? S (%) =? ? V (fps) =? Tt(min)= L (ft) =? S (4) =? 7 V (fps) =? Tt(min)= NOTE: ALL VELOCITIES TAKEN FROM, FIGURE 3-2. TOTAL TRAVEL TIME (min) _ L = 500 L/180+10 12.78 < 16.24 CHOOSE LESSER Tc =Ti+TOTAL TRAVEL TIME 2 YEAR 10 YEAR 100 YEAR Tc (min)= '12.78 12.78 12.78 USE Tc = 13 13 13 INTENSITY (I) (iph) 2 YEAR 10 YEAR I = 2.30 4.03 NOTE: INTENSITIES TAKEN FROM FIGURE 100 YEAR 6.49 3-1 RUNOFF (Q= CIA) (C£s) 2 YEAR 10 YEAR 100 YEAR Q = 1.30 2.28 4.60 QTOTAL = 4.72 8.10 16.69 FROM FILING 1 CALCULATIONS CONCLUDE:INSTALL 10 FOOT TYPE R INLET SUMP FOR 100 YEAR STORM CAPACITY PER FOOT (cfe/ft)= 2.45 BASED ON FLOW DEPTH OF 1 FOOT ABDUCTION FACTOR 90.004ACTUAL CAPACITY 22.05 CPS PIPE DIAM. = 2.00 FT. PIPE TYPE = ADS MANNINGS 0.012 SLOPE = 0.0235 FT/FT SLOPE _ 0.005 FT/FT CONVEYANCE FACTOR= 245.08 - REFER TO TABLE 4 ADS MANUAL CAPACITY = 37.57 CPS PIPS OVERSIZED FOR OVERFLOW FROM POND 2 INLET SIZED FROM FILING 1 13 5.00 0.00 0.00 0.00 0.00 0.00 0.00 5.00 SHEAR ENGINEERING CORPORATION DEVELOPED FLOW TO CONCENTRATION POINT E1 FROM SUBBASIN SA PROJECT: HEARTHFIRE PUD DATE 07/14/97 LOCATION:TOWN CENTER DRIVE - NORTH SIDE PROD. NO.1552-01-96 FILE: STORM BY MEO AREA (A)= 1.94 ACRES RUNOFF CORP. (C) 2 YEAR 10 YEAR 100 YEAR C = 0.75 0.75 0.93 REFER TO SUBBASIN BREAKDOWN ON PAGE 2 TIME OF CONCENTRATION (Tc) OVERLAND TRAVEL TIME (Ti) LENGTH = 30 FEET 2 YEAR C = 0.20 Ti (min)= 7.33 SLOPE 2.00 % 10 YEAR 100 YEAR 0.20 0.25 7.33 6.93 TRAVEL TIME.(Tt) =L/(60-V) FLOW TYPE L (£t) = 50 S M = 0.50 GUTTER L (ft) = 105 S (%) = 4.00 GUTTER L (ft) = 770 S (%) = 0.50 GUTTER L (ft) _? S (%) _? ? L (ft) _? S (%) _? ? L (ft) _? S (%) _? ? NOTE: ALL VELOCITIES TAKEN FROM FIGURE 3-2 L = 955 L/180+10 15.31 < Tc =Ti+TOTAL TRAVEL TIME 2 YEAR 10 YEAR Tc (min)= 15.31 15.31 USE Tc = 15.5 15.5 INTENSITY (I) (iph) 2 YEAR 10 YEAR I = 2.11 3.70 NOTE: INTENSITIES TAKEN FROM FIGURE RUNOFF (Q= CIA) (cfs) 2 YEAR 10 YEAR QINLET = 3.05 5.34 PAGE 12 V (fps) = 1.50 Tt(min)= 0.56- V (fps) = 4.00 Tt(min)= 0.44 V (fps) = 1.50 Tt(min)= 8.56 V (fps) _? Tt(min)= 0.00 V (fps) _? Tt(min)=. 0.00 V (fps) _? Tt(min)= 0.00 V (fps) _? Tt(min)= 0.00 TOTAL TRAVEL TIME (min) = 9.55 16.47 CHOOSE LESSER 100 YEAR 15.31 15.5 100 YEAR 5.98 3-1 100 YEAR 10.79 CONCLUDE:INSTALL 10 FOOT TYPE R INLET SUMP FOR 100 YEAR STORM CAPACITY PER FOOT (cfs/ft)= 2.45 BASED ON FLOW DEPTH OF 1 FOOT REDUCTION FACTOR = 90.00%ACTUAL CAPACITY 22.05 CFS PIPE DIAM. = 2.00 FT. PIPE TYPE = RCP MANNINGS 0.013 SLOPE _ 0.0235 FT/FT SLOPE 0.005 FT/FT CONVEYANCE FACTOR= 226.22 - REFER TO TABLE 5 ADS MANUAL CAPACITY = 34.68 CFS PIPE OVERSIZED FOR OVERFLOW FROM POND 2 INLET SIZED FROM FILING 1 SHEAR ENGINEERING CORPORATION DEVELOPED FLOW TO CONCENTRATION POINT D FROM SUBBASIN 4 PROJECT: HEARTHFIRE PUD DATE 07/14/97 LOCATION:TOWN CENTER COURT PROJ. NO.1552-01-96 FILE: STORM BY MEO AREA (A)= 8.12 ACRES RUNOFF CORP. (C) 2 YEAR 10 YEAR 100 YEAR C = 0.61 0.61 0.77 REFER TO SUBBASIN BREAKDOWN ON PAGE 2 TIME OF CONCENTRATION (TO OVERLAND TRAVEL TIME (Ti) LENGTH = 250 FEET SLOPE = 4.00 4 2 YEAR 10 YEAR 100 YEAR C = 0.20 0.20 0.25 Ti (min)= 16.84 16.84 15.91 TRAVEL TIME (Tt)=L/(60*V) FLOW TYPE L (ft) = 150 S (6) = 4.00 SWALR L (ft) = 550 S (%) = 0.50 GUTTER L (ft) = 235 S 00 = 2.50 GUTTER L (ft) = 100 S 00 = 0.50 GUTTER L (ft) _? S 00 _? ? L (ft) _? S 00 _? ? L (ft) _? S ($) _? ? NOTE: ALL VELOCITIES TAKEN FROM FIGURE 3-2 L = 1285 L/180+10 17.14 < Tc =Ti+TOTAL TRAVEL TIME 2 YEAR 10 YEAR Tc (min). 17.14 17.14 USE Tc = 17 17 INTENSITY (I) (iph) 2 YEAR 10 YEAR I = 2.02 3.55 NOTE: INTENSITIES TAKEN FROM FIGURE PAGE 11 V (fps) = 3.00 Tt(min)= 0.83 V (fps) - 1.50 Tt(min)= 6.11 V (fps) = 3.10 Tt(min)= 1.26 V (fps) = 1.50 Tt(min)= 1.11 V (fps) _? Tt(min)= 0.00 V (fps) _? Tt(min)= 0.00 V (fps) _? Tt(min)= 0.00 TOTAL TRAVEL TIME (min) = 9.32 25.22 CHOOSE LESSER 100 YEAR 17.14 17 100 YEAR 5.72 3-1 RUNOFF (Q= CIA) (cfs) 2 YEAR 10 YEAR 100 YEAR Q = 10.10 17.71 35.67 QDP-El = 0.33 0.58 1.15 FLOW INTERCEPTED AT DP 81 QDP-E2 = 0.50 0.87 6.45 FLOW INTERCEPTED AT DP E2 QDP-E3 = 9.47 16.62 31.82 FLOW INTERCEPTED AT DP E3 QPIPB = 10.30 18.07 39.43 SIZE PIPE CONCLUDE:SIZE PIPE FROM DP E1 TO POND FOR 100 YEAR FLOW PIPE DIAM. = 2.50 FEET . ADS MANNINGS N = 0.012 CONVEYANCE FACTOR = 444.35 SLOPE = 0.0089 FT/FT CAPACITY = 41.92 CPS STREET CAPACITY FROM BACK OF WALK TO BACK OF WALK = 27.50 CPS FLOW DEPTH AT FLOWLINE UP TO BACK OF WALK = 0.57 FEET SHEAR ENGINEERING CORPORATION DEVELOPED PAGE 10 FLOW TO CONCENTRATION POINT D3 FROM SUBBASIN 4C PROJECT: HEARTHFIRB PUD DATE 07/14/97 LOCATION:WEST SIDS TOWN CENTER COURT PROJ. NO.1552-01-96 FILE: STORM BY MEO AREA (A)- 6.88 ACRES i RUNOFF COBF. (C) 2 YEAR 10 YEAR 100 YEAR C 0.68 0.68 0.85 REFER TO SUBBASIN BREAKDOWN ON PAGE 2 TIME OF CONCENTRATION (Tc) OVERLAND TRAVEL TIME (TO LENGTH 250 FEET SLOPE = 4.00 It 2 YEAR 10 YEAR 100 YEAR C = 0.20 0.20 0.25 Ti (min)= 16.84 16.84 15.91 TRAVEL TIME (TO-L/(60*V) FLOW TYPE .v L (£S) = 150 S (%) = 4.00 SWALB V (fps) = 3.00 Tt(min)- 0.83 L (ft) = 550 S (%) = 0.50 GUTTER V (fps) = 1.50 Tt(min)= 6.11 L (ft) = 235 S (%) - 2.50 GUTTER V (fps) = 3.10 Tt(min)= 1.26 L (ft) = 100 S (%) = 0.50 GUTTER V (fps) = 1.50 Tt(min)= 1.11 L (ft) _? S (%) _? ? V (fps) _? Tt(min)= 0.00 L (ft) _? S (%) _? ? V (fps) _? Tt(min)= 0.00 L (ft) _? S (%) _? ? V (fps) _? Tt(min)- 0.00 NOTE: ALL VELOCITIES TAKEN FROM FIGURE 3-2 TOTAL TRAVEL TIME (min) 9.32 L = 1285 L/180+10. 17.14 < 25.22 CHOOSE LESSER Tc =Ti+TOTAL TRAVEL TIME 2 YEAR 10 YEAR 100 YEAR Tc (min)= 17.14 17.14 17.14 USE Tc = 17 17 17 INTENSITY (I),(iph) 2 YEAR 10 YEAR 100 YEAR I = 2.02 3.55 5.72 NOTE: INTENSITIES TAKEN FROM FIGURE 3-1 RUNOFF (Q= CIA) (cfs) 2 YEAR 10 YEAR 100 YEAR Q = 9.47 16.62 33.47 DIRECT FLOW TO INLET QUP = 0.00 0.00 3.75 FLOW FROM DP D2 QTOTAL = 9.47 16.62 37.22 QINT = 9.47 16.62 31.82 INTERCEPTION QPASS 0.00 0.00 5.40 - CONCLUDB:DESIGN FOR 100 YEAR STORM FROM FIGURE 5-5 Q Sx T Dw n S 37.22 0.02 15 0.26 0.016 0.005 22 FOOT INLET REQUIRED FOR 100% INTERCEPTION INSTALL 15 FOOT INLET Qi/Q - 0.95 THEORETICAL INLET CAPACITY = 35.36 CFS REDUCTION FACTOR = 90.00%ACTUAL CAPACITY = 31.82 CPS SHEAR ENGINEERING CORPORATION DEVELOPED FLOW TO CONCENTRATION POINT D2 FROM SUBBASIN 4B PROJECT: HEARTHFIRE PUD DATE 07/14/97 LOCATION:WEST SIDE TOWN CENTER COURT PROS. NO.1552-01-96 FILE: STORM BY MEO AREA (A)= 1.04 ACRES RUNOFF CORP. (C) 2 YEAR 10 YEAR 100 YEAR C = 0.24 0.24 0.30 REFER TO SUBBASIN BREAKDOWN ON PAGE 2 TIME OF CONCENTRATION (TO OVERLAND TRAVEL TIME (Ti) LENGTH = 250 FEET SLOPE = 4.00 $ 2 YEAR 10 YEAR 100 YEAR C = 0.20 0.20 0.25 Ti (min)= 16.84 16.84 15.91 TRAVEL TIME (It) -L/(60+V) FLOW TYPE L (ft) = 150 S ($) = 4.00 SWALE L (ft) = 550 S ($) = 0.50 GUTTER L (£t) = 235 S ($) = 2.50 GUTTER L (ft) = 100 S ($) = 0.50 GUTTER L (ft) _? S ($) _? ? L (ft) _? S ($) _? ? L (ft) _? S ($) _? ? NOTE: ALL VELOCITIES TAKEN FROM FIGURE 3-2 L = 1285 L/180+10 17.14 < Tc =Ti+TOTAL TRAVEL TIME 2 YEAR 10 YEAR 100 YEAR Tc (min)= 17.14 17.14 17.14 USE Tc = 17 17 17 PAGE V (fpe) = 3.00 Tt(min)= V (fps) = 1.50 Tt(min)= V (fps) = 3.10 Tt(min)= V (fps) = 1.50 Tt(min)= V (fps) _? Tt(min)= V (fps) _? Tt(min)= V (fps) _? Tt(min)= TOTAL TRAVEL TIME (min) _ 25.22 CHOOSE LESSER INTENSITY (I) (iph) 2 YEAR SO YEAR 100 YEAR I = 2.02 3.55 5.72 NOTE: INTENSITIES TAKEN FROM FIGURE 3-1 RUNOFF (Q= CIA) (cfe) 2 YEAR 10 YEAR 100 YEAR QINLET = 0.50 0.87 1.76 QUP = 0.00 0.00 5.40 FLOW FROM DP E3 QTOTAL 0.50 0.87 7.15 TOTAL FLOW TO INLET QINT = 0.50 0.87 6.45 INTERCEPTION QPASS = 0.00 0.00- 0.70 CONCLUDE:DESIGN FOR 100 YEAR STORM FROM FIGURE 5-5 Q Sx T S Dw n 7.15 0.02 15 0.005 0.26 0.016 22 FOOT INLET REQUIRED FOR 100% INTERCEPTION INSTALL 20 FOOT INLET Qi/Q = 0.95 THEORETICAL INLET CAPACITY = 6.79 CPS REDUCTION FACTOR = 95.00$ACTUAL CAPACITY = 6.45 CPS 9 0.83 6.11 1.26 1.11 0.00 0.00 0.00 9.32 SHEAR ENGINEERING CORPORATION DEVELOPED FLOW TO CONCENTRATION POINT D1 FROM SUBBASIN 4A PROJECT: HEARTHFIRE PUD DATE 07/14/97 LOCATION:EAST SIDE TOWN CENTER COURT PROJ. NO.1552-01-96 FILE: STORM BY MEO AREA (A)= 0.20 ACRES RUNOFF CORP. (C) 2 YEAR 10 YEAR 100 YEAR C 0.81 0.81 1.00 REFER TO SUBBASIN BREAKDOWN ON PAGE 2 TIME OF CONCENTRATION (Tc) OVERLAND TRAVEL TIME (Ti) LENGTH 250 FEET SLOPE 4.00 t 2 YEAR 10 YEAR 100 YEAR C = 0.20 0.20 0.25 Ti (min)= 16.84 16.84 15.91 TRAVEL TIME (Tt) =L/(60*V) PLOW TYPE L (ft) 150 S (t) = 4.00 SWALE L (ft) = 550 S ($) = 0.50 GUTTER L (ft) = 235 S (%) = 2.50 GUTTER L (ft) = 100 S (t) = 0.50 GUTTER L (ft) _? S (t) _? ? L (ft) _? S (t) _? ? L (ft) _? S (t) _? ? NOTE: ALL VELOCITIES TAKEN FROM FIGURE 3-2 L = 1285 L/180+10 17.14 < Tc =Ti+TOTAL TRAVEL TIME 2 YEAR 10 YEAR 100 YEAR Tc (min)= 17.14 17.14 17.14 USE Tc = 17 17 17 PAGE V (fps) 3.00 Tt(min)= V (fps) 1.50 Tt(min)= V (fps) = 3.10 Tt(min)= V (fps) = 1.50 Tt(min)= V (fps) _? .Tt(min)= V (fps) _? Tt(min)= V (fps) _? Tt(min)= TOTAL TRAVEL TIME (min) _ 25.22 CHOOSE LESSER INTENSITY (I) (iph) 2 YEAR 10 YEAR 100 YEAR I 2.02 3.55 5.72 NOTE: INTENSITIES TAKEN FROM FIGURE 3-1 RUNOFF (Q= CIA) (cfs) 2 YEAR 10 YEAR 100 YEAR Q 0.33 0.58 1.15 QINT 0.33 0.58 1.04 INTERCEPTED FLOW QPASS = 0.00 0.00 0.12 CONCLUDE:DESIGN FOR 100 YEAR STORM FROM FIGURE 5-5 Q Sx T S Dw n 1.15 0.02 7.5 0.005 0.11 0.016 10 FOOT.INLRT REQUIRED FOR 100% INTERCEPTION INSTALL 20 FOOT INLET Qi/Q = 1 INLET CAPACITY = 1.15 REDUCTION FACTOR = 90.00t ACTUAL CAPACITY = 1.04 CPS PIPE MATL n SLOPE C CAPACITY 2.5 ADS 0.012 0.0089 444.35 41.92 PIPS AND INLET ARE OVERSIZED FOR UPSTREAM FLOWS 8 0.83 6.11 1.26 1.11 0.00 0.00 0.00 9.32 SHEAR ENGINERING DEVELOPED FLOW TO CONCENTRATION POINT FROM SUBBASIN 3 PROJECT: HEARTHFIRE PUD SECOND FILING LOCATION:TOWN CENTER COURT FILE: STORM AREA (A)= 2.00 ACRES RUNOFF COEF. (C) 2 YEAR 10 YEAR 100 YEAR C = 0.74 0.74 0.93 REFER TO SUBBASIN BREAKDOWN ON PAGE 2 TIME OF CONCENTRATION (TO OVERLAND TRAVEL TIME (TO LENGTH = 40 FEET SLOPE 1.00 6 2 YEAR 10 YEAR 100 YEAR C = 0.20 0.20 0.25 Ti (min)= 10.64 10.64 10.05 TRAVEL TIME (TO =L/(60*V) FLOW TYPE L (ft) = 520 S M = 0.50 GUTTER L (ft) = 230 S (4) - 4.00 GUTTER L (ft) 100 S (M) = 2.00 GUTTER L (ft) = 100 S (i) = 5.00 GUTTER L (£t) _? S (!) _? ? L (ft) _? S (4) _? ? L (ft) _? S (6) _? ? NOTE: ALL VELOCITIES TAKEN FROM FIGURE 3-2 L = 990 L/180+10 15.50 < Tc -Ti+TOTAL TRAVEL TIME 2 YEAR SO YEAR 100 YEAR Tc (min)= 15.50 15.50 15.50 USE Tc - 15.5 15.5 15.5 DATE 07/14/97 PROD. NO.1552-02-97 BY MEO PAGE V (fps) = 1.50 Tt(min)= V (fps) = 4.00 Tt(min)= V (fps) - 2.83 Tt(min)= V (fps) 4.45 Tt(min)= V (fps) _? Tt(min)= V (fps) _? Tt(min)= V (fp0) _? Tt(min)= TOTAL TRAVEL TIME (min) _ 17.75 CHOOSE LESSER INTENSITY (I) (iph) 2 YEAR 10 YEAR 100 YEAR I = 2.11 3.70 5.98 NOTE: INTENSITIES TAKEN FROM FIGURE 3-1 RUNOFF (Q= CIA) (cfo) 2 YEAR 10 YEAR 100 YEAR QTOTAL 3.14 5.50 11.10 QDPD1 = 0.67 1.18 1.83 FLOW INTERCEPTED AT DP QDPD2 2.46 4.32 4.97 FLOW INTERCEPTED AT DP QINT 3.14 5.50 6.80 TOTAL INTERCEPT QPASS = 0.00 0.00 4.30 CONCLUDS:SIZE PIPE FROM DP D1 FOR 100 YEAR STORM = PIPE DIAM. = 1.50 FEET ADS MANNINGS N = 0.012 CONVEYANCE FACTOR = 113.8 SLOPS = 0.010 FT/FT CAPACITY = 11.38 CPS STREET CAPACITY FROM BACK OF WALK TO BACK OF WALK = 86.99 CPS FLOW DEPTH AT FLOWLINE UP TO BACK OF WALK = 0.57 FEET DI D2 6.80 CFS 7 5.78 0.96 0.59 0.37 0.00 0.00 0.00 7.70 SHEAR ENGINEERING CORPORATION DEVELOPED PLOW TO CONCENTRATION POINT C2 FROM SUBBASIN 3B PROJECT: HEARTHFIRE PUD SECOND PILING DATE 07/14/97 LOCATION:WEST SIDE TOWN CENTER COURT PROJ. NO.1552-02-97 FILE: STORM BY MBO AREA.(A)= 1.616 ACRES RUNOFF COBF. (C) 2 YEAR 10 YEAR 100 YEAR C = 0.72 0.72 0.90 REFER TO SUBBASIN BREAKDOWN ON PAGE 2 TIME OF CONCENTRATION (Tc) OVERLAND TRAVEL TIME (Ti) LENGTH = 40 FEET SLOPE = 1.00 i 2 YEAR 10 YEAR 100 YEAR C = 0.20 0.20 0.25 Ti (min)= 10.64 10.64 10.05 TRAVEL TIME (Tt)=L/(60*V) FLOW TYPE L (ft) = 520 S (%) = 0.50 GUTTER L (ft) = 230 S (%) = 4.00 GUTTER L (ft) _ 100 S (14) = 2.00 GUTTER L (ft) = 100 S M = 5.00 GUTTER L (ft) _? S (14) _? 7 L (ft) _? S (1k) _? ? L (ft) _? S (t) _? ? NOTE: ALL VELOCITIES TAKEN FROM PIGURE 3-2 L = 990 L/180+10 15.50 < Tc =Ti+TOTAL TRAVEL TIME 2 YEAR 10 YEAR Tc (min)= 15.50 15.50 USE Tc = 15.5 15.5 INTENSITY (I) (iph) 2 YEAR 10 YEAR I 2.11 3.70 NOTE: INTENSITIES TAKEN FROM FIGURE RUNOFF (Q= CIA) (Cfs) 2 YEAR QINLET 2.46 QINT 2.46 QPASS = 0.00 CONCLUDE:DRSIGN FOR Q Sx 8.72 0.02 PAGE V (fps) = 1.50 Tt(min)= V (fps) = 4.00 Tt(min)= V (fps) = 2.83 Tt(min)= V (fps) = 4.45 Tt(min)= V (fps) _? Tt(min)= V (fps) _? Tt(min)= V (fps) _? Tt(min)= TOTAL TRAVEL TIME (min) _ 17.75 CHOOSE LESSER 100 YEAR 15.50 15.5 100 YEAR 5.96 3-1 10 YEAR 100 YEAR 4.32 8.72 4.32 4.97 INTERCEPTED FLOW 0.00 3.75 BYPASS FLOW TO DP E3 100 YEAR STORM FROM FIGURE 5-5 T S Dw n 13.5 0.05 0.23 6 5.78 0.96 0.69 0.37 0.00 0:00 0.00 7.70 SHEAR ENGINEERING CORPORATION DEVELOPED FLOW TO CONCENTRATION POINT C1 FROM SUBBASIN 3A PROJECT: HEARTHFIRE PUD SECOND FILING DATE 07/14/97 LOCATION:EAST SIDE TOWN CENTER COURT PROJ. NO.1552-02-97 FILE: STORM BY MHO AREA (A)= 0.38 ACRES RUNOFF COEF. (C) 2 YEAR 10 YEAR 100 YEAR C = 0.84 0.84 1.00 REFER TO SUBBASIN BREAKDOWN ON PAGE 2 TIME OF CONCENTRATION (TO OVERLAND TRAVEL TIME (Ti) LENGTH = 40 FEET SLOPE = 1.00 4 2 YEAR 10 YEAR 100 YEAR C = 0.20 0.20 0.25 Ti (min)= 10.64 10.64 10.05 TRAVEL TIME (TO=L/(60+V) FLOW TYPE L (ft) = 520 S (4) - 0.50 GUTTER L (ft) = 230 S = 4.00 GUTTER L (ft) = 100 S (%) = 2.00 GUTTER L (ft) = 100 S ($) = 5.00 GUTTER L (ft) _? S _? ? L (ft) _? S (4) _? ? L (ft) _? S (t) _? ? NOTE: ALL VELOCITIES TAKEN FROM FIGURE 3-2 L = 990 L/180+10 15.50 < Tc =Ti+TOTAL TRAVEL TIME 2 YEAR 10 YEAR Tc (min)= 15.50 15.50 USE Tc = 15.5 15.5 INTENSITY (I) (iph) 2 YEAR 10 YEAR I = 2.11 3.70 NOTE: INTENSITIES TAKEN FROM FIGURE PAGE V (fps) = 1.50 Tt(min)= V (fps) = 4.00 Tt(min)= V (fps) = 2.83 Tt(min)= V (fps) = 4.45 Tt(min)= V (fps) _? Tt(min)= V (fps) _? Tt(min)= V (fps) _? Tt(min)= TOTAL TRAVEL TIME (min) _ 17.75 CHOOSE LESSER 100 YEAR 15.50 15.5 100 YEAR 5.98 3-1 RUNOFF (Q= CIA) (cfa) 2 YEAR 10 YEAR 100 YEAR QINLRT = 0.67 1.18 2.27 QINT = 0.67 1.18 1.83 INTERCEPTED FLOW QPASS 0.00 0.00 0.44 BYPASS FLOW TO DP B CONCLUDE:DESIGN FOR 100 YEAR STORM FROM FIGURE 5-5 Q Sx T S Dw n 2.27 0.02 7.5 0.05 0.11 0.016 30 FOOT INLET REQUIRED FOR 100% INTERCEPTION INSTALL 20 FOOT INLET Qi/Q = 0.85 INLET CAPACITY = 1.93 REDUCTION FACTOR = 95.00%ACTUAL CAPACITY = PIPE MAIL n SLOPE C CAPACITY 1.5 ADS 0.012 0.0100 113.8 11.38 FEET 5 5.78 0.96 0.59 0.37 0.00 0.00 0.00 7.70 1.83 SHEAR ENGINEERING CORPORATION PAGE 4 A CHANNEL CAPACITY -AT EAST END OF BUNTWING PROJECT NAME: HEARTHFIRE PUD 2ND FILING DATE: 07/14/97 PROJECT NO. : 1552-02-97 BY : MEO SWALB DESCRIPTION:BUNTWING COURT FILE: STORM CAPACITY OF TRIANGULAR OR TRAPEZOIDAL CHANNEL CHANNEL CONFIGURATION: TRAPEZOIDAL Q100 (cfe) = 0.57 CHANNEL LINING: GRASS 1.33*Q100 (cfe) 0.76 Da Db Dc Sc n W I (ft) (ft) (ft) (t) (ft) (ft) ---- ---- ---- ----- ---- ---- 2.00 2.00 0.50 2.00 0.0320 2.00 6.20 0.25 FT/FT = LEFT BANK SLOPE 4.00 :11(H:V) 0.25 FT/FT = RIGHT BANK SLOPE 4.00 :1 (H:V) DEPTH WIDTH AREA PERIM R 2/3 Sc 1/2 Q V (s.f.) (ft) (s.f.) (ft) (A/P) (cfe) (ft/eec) ------------------------------------------------- ------- 0.50' 6.00 2.00 6.12 0.47 0.14 6.23 3.11 0.30 4.40 0.96 4.47 0.36 0.14 2.26 2.35 0.10 2.80 0.24 2.82 0.19 0.14 0.30 1.27 0.00 2.00 0.00 2.00 0.00 0.14 0.00 0.00 0.00 2.00 0.00 2.00 0.00 0.14 0.00 0.00 0.00 2.00 0.00 2.00 0.00 0.14 0.00 0.00 0.17 3.36 0.46 3.40 0.26 0.14 0.76 1.72 r rrx+rxrrxtr+rrrrrrrr+xx+rr+rrrrrr rrrrrrrx+r+rr+rr+rx+x+r++rx++++++rr++r DEPTH WIDTH AREA PERIM R 2/3 Sc 1/2 Q V (s.f.) (ft) (s.f.) (ft) (A/P) (cfe) (ft/sec) FLOW DEPTH FOR THE DESIGN FLOW IS APPROXIMATELY 0.17 FEET FREEBOARD IN CHANNEL - 0.33 FEET CONCLUDE:CHANNEL WILL BE ADEQUATE SHEAR ENGINEERING CORPORATION DEVELOPED FLOW TO CONCENTRATION POINT B FROM SUBBASIN 2 PROJECT: HEARTHPIRE PUD SECOND FILING DATE 07/14/97 LOCATION:BUNTWING COURT PROJ. NO.1552-02-97 FILE: STORM BY HBO AREA (A)= 0.90 ACRES RUNOFF CORP. (C) 2 YEAR 10 YEAR 100 YEAR C = 0.78 0.78 0.98 REFER TO SUBBASIN BREAKDOWN ON PAGE 2 TIME OF CONCENTRATION (TO OVERLAND TRAVEL TIME (TO LENGTH = 40 FEET SLOPE = 1.00 ft 2 YEAR 10 YEAR 100 YEAR C = 0.20 0.20 0.25 Ti (min). 10.64 10.64 10.05 TRAVEL TIME (Tt) =L/(60*V) FLOW TYPE L (ft) = 50 S (t) = 5.00 GUTTER L (ft) = 30 S 00 = 2.50 GUTTER L (ft) = 140 S 00 = 1.00 GUTTER L (ft) = 160 S ($) = 0.50 GUTTER L (ft) _? S (6) _? ? L (ft) _? S (%) _? ? L (ft) _? S M _? ? NOTE: ALL VELOCITIES TAKEN FROM FIGURE 3-2 .L - 420 L/180+10 12.33 < Tc -Ti+TOTAL TRAVEL TIME 2 YEAR 10 YEAR 100 YEAR Tc (min)= 12.33 12.33 12.33 USE Tc = 12.5 12.5 12.5 PAGE V (fps) = 4.45 Tt(min)= V (fps) = 3.10 Tt(min)= V (fps) = 2.00 Tt(min)= V (fps) = 1.50 Tt(min)= V (fps) _? Tt(min)= V (fps) _? Tt(min)= V (fps) _? Tt(min)= TOTAL TRAVEL TIME (min) _ 13 .35 CHOOSE LESSER INTENSITY (I) (iph) 2 YEAR 10 YEAR 100 YEAR I 2.34 4.10 6.60 NOTE: INTENSITIES TAKEN FROM FIGURE 3-1 4 0.19 0.16 1.17 1.78 0.00 0.00 0.00 3.29 RUNOFF (Q= CIA) (cfs) 2 YEAR 10 YEAR 100 YEAR Q = 1.65 2.90 5.83 QUP = 0.00 0.00 0.44 FLOW FROM DP D1 QTOTAL = 1.65 2.90 6.27 QOVER = 0.00 0.00 0.57 OVERFLOW SWALE CONCLUDE:DESIGN FOR 10 YEAR STORM INSTALL 5 FOOT TYPE R INLET IN SUMP CONDITION CAPACITY PER FOOT (cfs/ft)= 1.34 BASED ON FLOW DEPTH OF 0.57 FOOT ABDUCTION FACTOR = 85.00}ACIUAL CAPACITY = 5.70 CPS PIPE DIAM. = 1.50 FT. PIPE TYPE = ADS SLOPS = 0.010 PT/FT MANNINGS n = 0.012 CONVEYANCE FACTOR= 113.8 - REFER TO TABLE 4 ADS MANUAL - CAPACITY = 11.38 CPS SEE PAGE 4 A FOR OVERFLOW CHANNEL SHEAR ENGINEERING CORPORATION PAGE 3 A CHANNEL CAPACITY -AT SOUTH END OF PONDVIEW PROJECT NAME: HEARTHFIRE PUD 2ND FILING DATE: 01/00/00 PROJECT NO. : 1552-02-97 BY : MEO SWALE DESCRIPTION: PONDVIEW COURT FILE: STORM CAPACITY OF TRIANGULAR OR TRAPEZOIDAL CHANNEL CHANNEL CONFIGURATION: TRAPEZOIDAL Q100 (cfe) = 0.12 CHANNEL LINING: GRASS 1.33rQ100 (cfe) = 0.16 Da Db Dc Sc n W I (ft) (ft) (ft) (11) (ft) (ft) ---- ---- ---- ---- ----- ---- ---- 2.00 2.00 0.50 2.00 0.0320 2.00 0.10 0.25 FT/FT = LEFT BANK SLOPE 4.00 :1 (H:V) 0.25 FT/FT = RIGHT BANK SLOPE 4.00 :1 (H:V) DEPTH WIDTH AREA PERIM R 2/3 Sc 1/2 Q V (e.f.) (ft) (s.f.) (ft) (A/P) (cfe) (ft/sec) -------------- ----------------------------------- ------- 0.50 6.00 2.00 6.12 0.47 0.14 6.23 3.11 0.40 5.20 1.44 5.30 0.42 0.14 3.97 2.76 0.30 4.40 0.96 4.47 0.36 0.14 2.26 2.35 0.20 3.60 0.56 3.65 0.29 0.14 1.05 1.88 0.10 2.80 0.24 2.82 0.19 0.14 0.30 1.27 0.00 2.00 0.00 2.00 0.00 0.14 0.00 0.00 0.07 2.56 0.16 2.58 0.16 0.14 0.16 1.03 xtx+++++++++++rr+r+rt+ttrtrtrtrrtrrr+rrtxrtrrrtrtertxrtr+rxr+++++++++r+rrr+r++rr DEPTH WIDTH AREA PERIM R 2/3 Sc 1/2 Q V (e.f.) (ft) (a.f.) (ft) (A/P) (cfe) (ft/sec) FLOW DEPTH FOR THE DESIGN FLOW IS APPROXIMATELY 0.07 FEET FREEBOARD IN CHANNEL = 0.43 FEET CONCLUDE: CHANNEL WILL BE ADEQUATE SHEAR ENGINEERING CORPORATION PAGE 2 SUBBASIN BREAKDOWN PROJECT: HEARTHFIRE PUD 2ND FILING DATE: 07/14/97 PROJECT NO 1552-02-97 BY MHO FILE: STORM OPEN SPACE TRACTS TRACT AREA AREA PLAITED AREA SF ACRES HEARTHFIRE 39.31 ACRES A 66265 1.52 i OPEN SPACE* 8.28 ACRES B 120913 2.78 C 22193 0.51 ASSUME SINGLE FAMILY LOTS ON THE SITE ARE D 112866 2.59 60.00%IMPERVIOUS - ROOF AND DRIVES B 38523 0.88 40.00%PERVIOUS - LAWN 360760 8.28 1 SQ INCH 65 SCALE: 1 INCH 100 IM- PERVIOUS PERVIOUS PLANI OPEN ROADS ROOF/ LAWN C2 C100 SUB- METER SF ACRES SPACE DRIVES BASIN READING 0.20 0.95 0.95 0.20 ACRES ACRES ACRES ACRES t+r+rrr+xxrrxr++rrr+rrrxrrrrrrrrrrrrr+r++rrxrxrrrrar+rrt+rx+rrxxr+r+rxrxrxrrrrrttr r+rr+rrr 1 222 34154 0.78 0.00 0.34 0.27 0.18 0.78 0.98 2 255.5 39308 0.90 0.00 0.40 0.30 0.20 0.78 0.98 3 565 86923 2.00 0.00 0.63 0.82 0.55 0.74 0.93 4 2299 353692 8.12 1.21 0.85 3.64 2.42 0.61 0.77 5 766 117846 2.71 0.00 0.84 1.12 0.75 0.74 0.93 6 2554 392923 9.02 3.30 0.00 3.77 1.95 0.51 0.64 7 2964 456000 10.47 3.78 0.03 4.38 2.28 0.52 0.64 e 1503 231231 5.31 0.00 0.00 1.06 4.25 0.35 0.44 rr+rrrxrxxxrrr+rrrrrr+rrrtr++r++r+rrxxrxxrx++x++r+rr+rrrrrr++rrrrr+rxr++xxrxr+rrr+rrr+rr+r SUBTOTAL 1712077 39.30 8.29 3.09 15.35 12.57 0.55 0.69 IM- PERVIOUS PERVIOUS PLANI OPEN ROADS ROOF/ LAWN C2 C100 MINOR METER SF ACRES SPACE DRIVES BASIN READING 0.20 0.95 0.95 0.20 ACRES ACRES ACRES ACRES r+rxxxxr++r+++r++rr+rxxxx+r++r++rr++xr+xrxrrx+rr+rr+r+++rxrr+rr+rrr+rrr+xxrxr+ree+xrr+xx+x 3A 107.5 16538 0.38 0.00 0.24 0.08 0.06 0.84 1.00 3B 457.50 70385 1.62 0.00 0.39 0.74 0.49 0.72 0.90 4A 57 8769 0.20 0.00 0.11 0.05 0.04 0.81 1.00 4B 294 45231 1.04 0.99 0.05 0.00 0.00 0.24 0.30 4C 1949 299846 6.88 0.00 0.69 3.72 2.48 0.68 0.85 SA 548 84308 1.94 0.00 0.62 0.79 0.53 0.75 0.93 SE 218 33538 0.77 0.00 0.22 0.33 0.22 0.74 0.92 FLOW SUMMARY FOR STORM SEWER DESIGN IN PAGE 1 HEARTHFIRE PUD SECOND FILING DATE 07/14/97 DESIGN CONTRIBUTING AREA C2 C10 C100 Tc Tc I2 I10 I100 Q2 Q10 Q100 DESIGN PAGE POINT SUB 2,10 100 BASIN(S) ac. min. min iph iph iph cfe cfs cfs r rrrrr+rr+r++r+r+r+rrrrrrrrrtrxrxxxtxrxxxrrxxxrrrrr+r+rx+xtx+r+rrxxr+rr rrrr++++++rrrrrrrrrrrrrrrrrrrrr DEVELOPED FLOWS FOR STORM SEWER IN SUB -BASIN 1 TO POND 2 A 1 0.78 0.78 0.78 0.98 13.00 13.00 2.30 4.03 6.49 1.41 2.46 4.96 I/P 3 DEVELOPED FLOWS FOR STORM SEWER IN SUB -BASIN 2 B 2 0.90 0.78 0.78 0.98 12.50 12.50 2.34 4.10 6.60 1.65 2.90 5.83 I/P 4 DEVELOPED FLOWS FOR STORM SEWER IN SUB -BASIN 4 TO POND 2 CI 3A 0.38 0.84 0.84 1.00 15.50 15.50 2.11 3.70 5.98 0.67 1.18 2.27 I/P 5 C2 3B 1.62 0.72 0.72 0.90 15.50 15.50 2.11 3.70 5.98 2.46 4.32 8.72 I/P 6 C 3 2.00 0.74 0.74 0.93 15.50 15.50 2.11 3.70 5.98 3.14 5.50 11.10 PIPE 7 DEVELOPED FLOWS FOR STORM SEWER IN SUB -BASIN 5 TO POND 2 D1 4A 0.20 0.81 0.81 1.00 17.00 17.00 2.02 3.55 5.72 0.33 0.58 1.15 I/P 8 D2 4B 1.04 0.24 0.24 0.30 17.00 17.00 2.02 3.55 5.72 0.50 0.87 1.76 I/P 9 D3 4C 6.88 0.68 0.68 0.85 17.00 17.00 2.02 3.55 5.72 9.47 16.62 33.47 I/P 10 D 4 8.12 0.61 0.61 0.77 17.00 17.00 2.02 3.55 5.72 10.10 17.71 35.67 PIPE' 11 DEVELOPED FLOWS FOR STORM SEWER IN SUB -BASIN 6 TO RICHARDS LAKE E1 5A 1.94 0.75 0.75 0.93 15.50 15.50 2.11 3.70 5.98 3.05 5.34 3.05 I/P 12 82 5B 0.77 0.74 0.74 0.92 13.00 13.00 2.30 4.03 6.49 1.30 2.28 4.60 I 13 E 5 2.71 0.74 0.74 0.93. 15.50 15.50 2.11 3.70 5.98 4.24 7.44 15.02 PIPE 14 DESIGN DESIGN STORM PIPE DESIGNINLET OG CAPA- PIPE RCP/ SLOPE CAPA- POINT INLET Q SIZE CITY DIAM ADS CITY year BOTH cfe ft SUMP cfe ft ft/ft cfe rrr+r+rrrr+rtrtrtrrt+trrrrrr++rt++++++rrr+++++r+r++r+++++r+rrrrr+++++rr+++++++rrrrrx+rrrrrttx+. .. PROFILE A PONDVIEW COURT A 10 BOTH 4.96 5 SUMP 4.85 1.50 ADS 0.060 27.88 PROFILE B BUNTWING COURT B 10 BOTH 6.27 5 SUMP 5.70 1.50 ADS 0.010 11.38 PROFILE C TOWN CENTER DRIVE @ TRACTS E & C Cl 100 INLET 2.27 20 OG 1.83 C2 100 BOTH 8.72 20 OG 4.97 1.50 RCP 0.010 10.50 C 100 PIPE 6.80 1.50 ADS 0.010 11.38 PROFILE D TOWN CENTER DRIVE i4 TRACT A & C D1 100 INLET 1.15 20 OG 1.04 D2 100 INLET 7.15 20 OG 6.45 D2 100 PIPE 38.27 2.50 RCP 0.009 38.70 D3 100 BOTH 37.22 15 OG 31.82 2.50 RCP 0.009 38.70 D 100 PIPE 39.43 2.50 ADS 0.009 41.92 PROFILE E TOWN CENTER DRIVE - FILING 1 E1 100 INLET 10.79 10 SUMP 22.05 2.00 RCP 0.024 34.68 E2 100 INLET 16.69 10 SUMP 22.05 2.00 ADS 0.024 37.57 Storm Sewer Design Flows APPENDIX I Drainage Calculations Page 11 Final Drainage and Erosion Control Report Hearthfire P.U.D., Second Filing VII. VARIANCE FROM CITY STANDARDS A. Variance from City of Fort Collins requirements 1. There will be no requests for variances from City of Fort Collins Stormwater Utility Standards. VIH. CONCLUSIONS A. Compliance With Standards 1. The grading and drainage design for Hearthfire P.U.D., Second Filing is in compliance with the City of Fort Collins storm drainage design criteria. 2. The erosion control measures shown on the erosion control plan comply with the City of Fort Collins standards and generally accepted erosion control practices. B. Drainage Concept 1. The proposed drainage design for Hearthfire P.U.D., Second Filing is effective for the control of storm runoff with a considerable reduction in potential downstream effects." IX REFERENCES 1. City of Fort Collins "Storm Drainage Design Criteria and Construction Standards'; May, 1984, revised May, 1997 2. City of Fort Collins "Erosion Control Reference Manual"; January, 1991 3. Preliminary Drainage and Erosion Control Report for Hearthfire at Richards Lake; Prepared by Merrick & Company; Project No. 15011782; Dated July 10,1996 4. Urban Runoff Mitigation for Hearthfire PUD, TR Boss Environmental and Biological Consulting; Dated November 1996 5. Wetland Mitigation Report for Hearthfire P.U.D.; TR Boss Environmental and Biological Consulting; Dated November 1996 Page 10 Final Drainage and Erosion Control Report Hearthfire P.U.D., Second Filing V. WATER QUALITY B. Specific Details 2. The water quality diffuser will intercept the initial flush and divert to the gravel drains on either side of the drain basin. When the capacity of the gravel drain is reached the remaining stormwater will flow through the drain basin to pond 2 where the wetlands will filter much of the remaining nutrients in the stormwater. VI. EROSION CONTROL: A. General Concept 1. Erosion control measures are specified on the Drainage and Erosion Control Plan. a. Maintenance of erosion control devices. will remain. the responsibility of the contractor and the owner until the project is complete. B. Specific Details 1. The following temporary measures are specified on the Drainage and Erosion Control plan: a. Area inlet filters composed of haybales around all area inlets . b. Silt fence along the downstream property lines. c. Gravel inlet filters at all storm sewer inlets. d. Haybale dikes within all swales. 2. The following permanent measures are specified on the Drainage and Erosion Control plan: a. Buried riprap aprons at all storm sewer outfalls b. Riprap to have a Dso of 12" c. Minimum length of riprap apron is 40 feet d. Minimum width of the riprap apron will be 5.0 feet for 18" pipe and 6.0 feet for 24" pipe. Page 9 Final Drainage and Erosion Control Report Hearthfire P.U.D., Second Filing IV DRAINAGE FACILITY DESIGN B. Specific Details -Swales 1. Overflow swales are provided at the end of the Pondview and Buntwing Courts. The swale is designed to convey the overflow generated by the 100-year storm at the inlets. The design flow is 1.33 x the Q100. The following table summarizes the design of the overflow swales. DP Q100 Depth Bottom SS Mannings Swale Section Width (H:V) n Capacity cfs ft. ft. ft:ft cfs A 0.12 0.5 2 4:1 0.032 6.23 A -A B 0.57 0.5 2.0 4:1 0.032 6.23 B-B V. WATER QUALITY A. General Concept 1. Water quality measures are specified in the Water Quality and Wetland Mitigation Report prepared by Ted Boss, PH.D. A copy of this report is on file in the office of Stormwater Utility a. Maintenance of water quality will be the responsibility of the contractor and the owner until the project is complete. The Homeowners Association will be responsible upon completion of the construction. B. Specific Details 1. A water quality diffuser will be installed at all storm sewer outfalls into the pond 2. The diffuser will consist of the following; a. An 18" or 24" ADS Drain Basin will be installed just before the Flared End Section (FES) of the outfall. A different detail is provided with larger pipes. b. Forty (40) lineal feet of 6" perforated ADS pipe will be extended out of either side of the drain basin. The invert of the 6" pipe will be one (1.0') foot lower than the invert of the storm sewer. c. The 6" pipe will be surrounded by 6" of 3/4" clean gravel with Mirafi Filter Fabric or equivalent on the top and the two (2) sides of the 6" pipe. d. The FES will be attached to the downstream end of the drain basin. e. 40 lineal feet of buried riprap with a D,o of 12" will be installed at each outfall. f.. Riprap aprons will be 5.0 feet for 18" pipe and 6.0 feet for larger pipes. Page 7 Final Drainage and Erosion Control Report Hearthfire P.U.D., Second Filing IV DRAINAGE FACILITY DESIGN B. Specific Details - Storm Sewer 3. Storm sewer B located on Town Center Drive north of Buntwing Court will consist of the following; a. 1 - 20' Type R inlet in continuous grade condition on the west side of Town Center Drive. b. 31.33 LF of 18 " RCP pipe. c. 1 - 20' Type R inlet in continuous grade condition on the east side of Town Center Drive. d. 300 LF of 18 " HDPE pipe ( ADS N-12 or approved equal) with FES. e. An 18 "ADS N-12 Drain Basin for Water Quality 4. Storm sewer C located at the low point on Buntwing Court will consist of the following; a. 5' Type R inlet in sump condition b. 140 LF of 18 " HDPE pipe ( ADS N-12 or approved equal) with FES. c. An 18 "ADS N-12 Drain Basin for Water Quality d. Overflow Swale 5. Storm sewer D located on Town Center Drive south of Buntwing Court will consist of the following; a. 1 - 15' Type R inlet in continuous grade condition on the west side of Town Center Drive. b. 65 LF of 30 " RCP pipe. c. 2 - 20' Type R inlets in continuous grade condition on the east and west side of Town Center Drive. d. 31.33 LF of 30 " RCP pipe. e. 500 LF of 30 " HDPE pipe ( ADS N-12 or approved equal) with FES. Page 6 Final Drainage and Erosion Control Report Hearthfire P.U.D., Second Filing IV DRAINAGE FACILITY DESIGN A. General Concept 1. The majority of the site (sub -basins 1-4) will be contributing stormwater to the wetland / pond areas (Pond 2) via a combination of a. overland flow b. gutter flow c. storm sewer flow The grading of the site attempts to divert as much of the runoff into the wetland areas as possible. 2. Sub -basins 5-7 will contribute stormwater directly to Richard Lake or Douglas Road via the same methods of conveyance mentioned previously. Sub-basin:8 contributes stormwater to pond 1. 3. Water quality is addressed in the design of the outfalls of the storm sewer into Richards Lake. Refer to the Wetlands Mitigation Report prepared by TR. Boss . Associates. Water Quality details coincide with the recommendations of the report. 4. Emergency overflow structures were designed with Filing 1 to pass any stormwater that exceeds the storage capacity of the wetland/ pond areas safely to Richards Lake. 5. Any swales that have slopes less than 2.0 percent will have 3' valley pans installed at the flow line of the swale. B. Specific Details - Storm Sewer 1. Storm sewer A located at the low point on Pondview Court will consist of the following; a. 5' Type R inlet in sump condition b. 140 LF of 18 " HDPE pipe ( ADS N-12 or approved equal) with FES. . c. 1 - shallow manhole d. An 18 "ADS N-12 Drain Basin for Water Quality e. Overflow Swale Page 5 Final Drainage and Erosion Control Report Hearthfire P.U.D., Second Filing III DRAINAGE DESIGN CRITERIA A. Regulations 1. This final report and the Master Grading, Drainage and Erosion Control Plans for Hearthfire P.U.D., Second Filing were prepared in accordance with the requirements of the current City of Fort Collins Storm Drainage Design Criteria and Erosion Control Criteria. B. Development Criteria Reference and Constraints 1. County Road 13 will be widened with this project and the proposed grading along the west property line will have to match the proposed design of the road. 2. The existing wetland areas retain much of the stormwater that flows to them. Emergency overflow structures were necessary to convey the stormwater which exceeds the capacity of the wetlands out of the wetland areas to Richards Lake. These were designed with Hearthfire P.U.D., First Filing. 3. The design intent is to divert as much of the runoff as possible to Ponds 1 and 2 for the purpose of water quality. C. Hydrologic Criteria 1. Runoff calculations at various design points are based on the 'Rational" method. The 2, 10, and 100-year storms have been analyzed. 2. No detention is proposed with this subdivision because the existing wetland areas will act as temporary retention ponds. 3. Emergency overflow structures were designed to convey flows that exceed the capacity of the retention areas with Filing 1. D. Hydraulic Criteria 1. Storm sewer inlet design is based on the inlet curves provided in the City of Fort Collins Drainage Criteria Manual. All the storm sewer is designed for at least the 10- year storm. This exceeds the City Requirement of the 2-year design storm. 2. Storm sewer design is based on Mannings Equation with Mannings coefficients as suggested in the City of Fort Collins Drainage Criteria Manual. Page 4 Final Drainage and Erosion Control Report Hearthfire P.U.D., Second Filing II DRAINAGE BASINS AND SUB -BASINS D. Developed Conditions 1 The developed site increases the contributing area to ponds 1 & 2 for the purpose of water quality. The table below summarizes the sub -basins within the limits of the Second Filing, their total area and the immediate destination of the flow from them. Area Sub -basin acres Flow Destination Notes 1 0.78 Pond 2 Storm Sewer 2 0.90 Pond 2 Storm Sewer 3 2.00 Pond 2 Storm Sewer 4 8.12 Pond 2 /Richards Lake Storm Sewer 5 2.71 Richards Lake Storm Sewer 6 9.02 Richards Lake 7 10.47 Richards Lake 8 5.31 Pond 1 The total area of the sub -basins is 39.31 acres. 2. The table below summarizes the peak flows from the developed sub -basins which contribute to the storm sewer infrastructure. Sub -basin Q2 Q100 Notes cfs cfs 1 1.41 4.96 Storm sewer Profile A 2 1.68 5.83 Storm Sewer Profile B 3 3.14 11.10 Storm Sewer Profile C 4 10.10 35.67 Storm Sewer Profile D 5 4.24 15.02 Overland Flow Page 2 Final Drainage and Erosion Control Report Hearthfire P.U.D., Second Filing II DRAINAGE BASINS AND SUB -BASINS A. Major Basin Description 1. The site is located in the Dry Creek Basin as delineated on the City of Fort Collins Stormwater Basin Map. 2. This portion of the Dry Creek Basin is partially developed with large single family lots and medium sized ranches. B. Sub -Basin Description 1. The site topography is best described as rolling. There are several ridges on the site which create several sub -basins. The site generally slopes from the northeast to the southwest at an average rate of 0.04 ft/ft (4.0%). 2. The basin is defined by Douglas Road to the north, County Road 13 to the west and Richards Lake to the south. The eastern property line of the entire site is the eastern boundary of the basin. 3. There are two (2) existing wetlands / ponding areas east of the site which intercept much of the runoff from the site and retain it. Grading proposed in these areas with Hearthfire P.U.D., Fast Filing created permanent water features. They are designated Pond 1 and Pond 2 on the Drainage and Erosion Control Plan. a. Pond 1 is crossed by the proposed access road (Hearthfire Way) to the First Filing from Douglas Road which was designed with Hearthfire P.U.D., First Filing. b. Pond 2 is the wetland area that is within the limits of Hearthfire P.U.D., First Filing. The stormwater that is intercepted by the wetlands either percolates into the soil or evaporates. An exception to this occurs when storm events exceed the storage capacity of the low areas. The stormwater eventually overflows into Richards Lake when this occurs. 4. Richards Lake is the ultimate destination of all runoff from the site including any water that exceeds the storage capacity of the wetland / pond areas. Page 1 Final Drainage and Erosion Control Report Hearthfire P.U.D., Second Filing I. GENERAL LOCATION AND DESCRIPTION A. Property Location 1. Hearthfire P.U.D., Second Filing is located in the West one-half (1/2) of Section 30, Township 8 North, Range 68 West of the 6th P.M., Latimer County, Colorado. 2. More specifically, it is located on the south side of Douglas Road (County Road 54), approximately 1.5 miles east of the intersection of Douglas Road and State Highway 1. 3. The site is bounded on the west by County Road 13, on the north by Douglas Road and Cherrywood Acres, on the east by Hearthfire P.U.D., First Filing and on the south by Richards Lake. 4. Richards Lake is located immediately south of Hearthfire P.U.D., Second Filing. Storm runoff from the site has historically entered Richards Lake and will continue with the development of Hearthfire P.U.D., Second Filing. a. Richard Lake is owned and operated by The Water Supply and Storage Company. b. The Water Supply and Storage Company has indicated that they will accept undetained flows from Hearthfire P.U.D., Second Filing in a manner similar to historic acceptance. i. A statement has been provided with the Hearthfire P.U.D, Second Filing Utility Plans and Final Plat indicating the reservoir company's acceptance of undetained flows to Richards Lake. ii. The Water Supply and Storage Company has provided a letter indicating their intent to accept undetained flows to Richards Lake. A signed copy of this letter is attached to this report and is located in Appendix IV. B. Description of the Property 1. Hearthfire P.U.D., Second Filing is a proposed residential subdivision in the City of Fort Collins, Colorado. The overall subdivision consists of approximately 146 single family homes. There are a total of 57 lots proposed with this filing. 2. Hearthfire P.U.D., Second Filing has a platted area of approximately 39.31 acres. 3. The site is currently vacant and is covered with native vegetation. 4. There are some existing oil wells on the site. July 16, 1997 Project No: 1552-02-97 Basil Hamdan City of Ft. Collins Storm Water Utility P.O. Box 580 Ft. Collins, Colorado 80524 Re: Hearthfire P.U.D., Second Filing; Ft. Collins, Colorado Dear Basil, Enclosed please find the Final Drainage and Erosion Report and Plans for Hearthfire P.U.D., Second Filing. The hydrology data and the hydraulic analysis presented in this report complies with the requirements of the City of Fort Collins Storm Drainage Criteria Manual; dated March, 1984, revised May, 1997 and the Erosion Control Reference Manual. If you have any questions or comments, please call me at 226-5334. Sincerely, Brian W. Shear Shear Engineering Corporation BW S / meo cc: Richards Lake Development Company a A 4836 S. College, Suite 12 Ft. Collins, CO 80525 (970) 226.5334 FAX (970) 282-0311 FINAL DRAINAGE AND EROSION CONTROL REPORT for HEARTHFIRE P.U.D., SECOND FILING Ft. Collins, Colorado Prepared for: RICHARDS LAKE DEVELOPMENT COMPANY 5319 Paradise Lane Fort Collins, Colorado 80526 r, e r r" "nn-TAL dale. `�I'�4Q------- Prepared By: SHEAR ENGINEERING CORPORATION Project No: 1552-02-97 Date: July, 1997 4836 S. College, Suite 12 Ft. Collins, CO 80525 (970) 226.5334 FAX (970) 282-0311 SHEAR ENGINEERING CORPORATION DEVELOPED FLOW TO CONCENTRATION POINT A FROM SUBBASIN 1 PROJECT: HEARTHFIRE PUD SECOND FILING DATE 07/14/97 LOCATION:POND VIEW COURT PROD. NO.1552-02-97 FILE: STORM BY HBO AREA (A)= 0.78 ACRES PAGE i RUNOFF COBF. (C) 2 YEAR 10 YEAR 100 YEAR C 0.78 0.78 0.98 REFER TO SUBBASIN BREAKDOWN ON PAGE 2 TIME OF CONCENTRATION (Tc) OVERLAND TRAVEL TIME (Ti) LENGTH = 40 FEET SLOPE = 1.00 i 2 YEAR 10 YEAR 100 YEAR C = 0.20 0.20 0.25 Ti (min)= 10.64 10.64 10.05 TRAVEL TIME (It) =L/(60*V) FLOW TYPE L (ft) = 480 S (%) = 1.00 GUTTER V (fps) = 2.00 Tt(min)= L (ft) _? S M _? ? V (fps) _? Tt(min)= L (ft) _? S (6) _? ? V (fps) _? Tt(min)= L (ft) _? S (e) _? ? V (fps) _? Tt(min)= L (ft) _? S (6) _? ? V (fps) _? Tt(min)= L (ft) _? S (t) _? ? V (fps) _? Tt(min)= L (ft) _? S (6) _? ? V (fps) _? Tt(min)= NOTE: ALL VELOCITIES TAKEN FROM FIGURE 3-2 TOTAL TRAVEL TIME (min) _ L = 520 L/180+10 12.89 c 14.05 CHOOSE LESSER Tc -Ti+TOTAL TRAVEL TIME 2 YEAR 10 YEAR 100 YEAR Tc (min)= 12.89 12.89 12.89 USE Tc = 13 13 13 INTENSITY (I) (iph) 2 YEAR 10 YEAR 100 YEAR I = 2.30 4.03 6.49 NOTE: INTENSITIES TAKEN FROM FIGURE 3-1 RUNOFF (Q= CIA) (cfe) 2 YEAR 10 YEAR 100 YEAR QTOTAL - 1.41 2.46 4.96 QINLBT = 1.41 2.46 4.85 QOVRR = 0.00 0.00 0.12 OVERFLOW SWALE CONCLUDE:DESIGN FOR 10 YEAR STORM INSTALL 5 FOOT TYPE R INLET IN SUMP CONDITION CAPACITY PER FOOT (cfe/ft)= 1.14 BASED ON FLOW DEPTH OF REDUCTION FACTOR = 85.006ACTUAL CAPACITY = 4.85 CPS PIPE DIAM. = 1.50 FT. PIPE TYPE = ADS 0.5 FOOT 3 4.00 0.00 0.00 0.00 0.00 0.00 0.00 4.00 SLOPE = 0.0600 FT/FT MANNINGS n = 0.012 CONVEYANCE FACTOR= 113.8 - REFER TO TABLE 4 ADS MANUAL CAPACITY = 27.88 CPS SEE PAGE 3 A FOR OVERFLOW CHANNEL Page 8 Final Drainage and Erosion Control Report Hearthfire P.U.D., Second Filing IV DRAINAGE FACILITY DESIGN B. Specific Details - Storm Sewer 6. Storm sewer E located on Town Center Drive east of Ingle Court will consist of the following; a. 2 - 10' Type R inlet in sump condition designed with Filing 1 b. The overflow storm sewer from Pond 2 to Richards Lake designed with Filing 1. 7. The following table summarizes the design of the storm sewers. Flow depth only applies to inlets in sump condition. Profile Design Design Inlet Flow Inlet Point Storm Q Size Depth Capacity yr. cfs ft. ft. cfs A A 10 2.46 5 0.57 5.70 B B 10 2.95 5 0.57 5.70 C Cl 100 2.27 20 NA 1.83 C C2 100 8.72 20 NA 4.97 D D1 100 1.15 20 NA 1.04 D D2 100 7.15 20 NA 6.45 D D3 100 38.27 15 NA 31.82 E E1 100 10.79 10 1.0 22.05 E E2 100 16.69 10 1.0 22.05 Profile From To Pipe Pipe Pipe Mannings Pipe DP DP Diameter Slope Type n Cap. ft.. ft./ft. cfs A A Pond 1.5 0.06 ADS N-12 0.012 27.88 B B Pond 1.5 0.01 ADS N-12 0.012 11.38 C C2 Cl 1.5 0.01 RCP 0.013 10.50 C C1 Pond 1.5 0.01 ADS N-12 0.012 11.38 D D3 D2 2.5 0.0089 RCP 0.013 38.70 D D2 D1 2.5 0.0089 RCP 0.013 38.70 D D1 Pond 2.5 0.0089 ADS N-12 0.010 41.92 E E2 E1 2.0 0.024 RCP 0.013 34.68 E E1 Lake 2.0 0.024 ADS 0.012 37.57 Page 3 Final Drainage and Erosion Control Report Hearthfire P.U.D., Second Filing II DRAINAGE BASINS AND SUB -BASINS C. Historic Conditions The overall site which includes filing 1 and 2 can be divided into 6 historic sub -basins designated A-F. These basins are undeveloped with a few active oil wells located on them as well as some wetland areas. We are utilizing the "C" factor for sandy soils with an average slope because of the wetlands present for most of the basin. We have assumed a "C" factor of 0.45 for Sub -basin F which consists of large estate lots in Cherrywood Acres. The table below summarizes the sub -basins, their total area and the immediate destination of the flow from them. Area Sub -basin acres Flow Destination A 50.53 Pond 1 B 57.59 Pond 2 a: C 40.50 Richards Lake D 10.64 Richards Lake via Richards Lake PUD E 13.75 Serramonte Highlands F 12.16 Douglas Road and east The total area of the sub -basins is 185.17 acres. Sub -basins A-E contribute stormwater to Richards Lake. There is also an additional 91.8 acres on the north side of Douglas Road which contributes runoff to pond 1. 2. The table below summarizes the peak flows from the historic sub -basins. Q2 Q100 Sub -basin cfs cfs Notes A 30.5 59.8 Retained in Pond 1 B 9.5 35.1 Retained in Pond 2 C 7.7 28.6 Richards Lake D 1.9 7.4 Richards Lake E 3.4 12.4 Serramonte Highlands F 8.3 30.5 Douglas Road a APPENDIX V Grading and Drainage and Erosion Control Plan (3 Sheets) THE WATER SUPPLY AND STORAGE COMPANY 231-9 EAST MULBERRY PHONE (303) 482-3433 P.O. BOX 1584 FORT COLLINS, COLORADO 80522 July 8, 1997 To whom it may concern Re: Hearthfire P.U.D., Second Filing; Ft. Collins, Colorado This note Is provided in order to indicate the intent of The Water Supply and Storage Company to agree to accept developed undetained stormwater runoff from the Hearthfire P.U.D. project to Richards Lake in a pattern similar to historic flows which entered Richards Lake. Our ur.derstanding is that water quality will be addressed. We also understand that an approval block will be provided on the final utility plans for Hearthfire P.U.D., Second Filing Ndnich will be as follows: Water Supply and Storage UTILITY PLAN APPROVAL The undersigned on behalf of THE WATER SUPPLY AND STORAGE COMPANY, the owner of Richards Lake, does hereby agree to accept all runoff from Hearthfire P.U.D. in a pattern similar to historic flows which entered this irrigation reservoir. President Date We also understand that the final plat •will be provided with the folio%vino: IRRIGATION COMPANY APPROVAL The undersigned on behalf of THE WATER SUPPLY AND STORAGE COMPANY, the owner of Richards Lake, does hereby agree to accept all runoff from Hearthfire P.U.D, in a pattern similar to historic flows which entered this irrigation reservoir. President Date ifyoe hate any question or comments, please call us at (970) 482-3433. Sincerely, Torn 1 ogre, esrdent The Water Supply and Storage Company cc: Richards Lake Development Company APPENDIX IV Water Supply and Storage Letter accepting stormwater from Hearthfire Second Filing TABLE 5 CIRCULAR PIPE FLAW CAPACITY Full Flow (cubic feet per second) Mannings "n"= 0.013 Dia. *Cony. % Slope (feet per 100 feet) (in.) Factor 0.02 0.05 0.10 0.20 0.35 0.50 0.75 1.00 1.25 1.50 1.75 2.0 2.5 5.0 10.0 20.( (c.f.s.) 3 0.884 0.012 0.020 0.028 0.040 0.052 0.062 0.077 0.088 0.099 0.11 0.12 0.12 0.14 0.20 0.28 0.4( 4 1.903 0.027 0.043 0.060 0.085 0.113 0.135 0.165 0.190 0.213 0.23 0.25 0.27 0.30 0.43 0.60 0.8E 5 3.451 0.049 0.077 0.109 0.154 0.204 0.244 0.299 0.345 0.386 0.42 0.46 0.49 0.55 0.77 1.09 1.54 6 5.611 0.079 0.125 0.177 0.251 0.332 0.397 0.486 0.561 0.627 0.69 0.74 0.79 0.89 1.25 1.77 2.51 8 12.084 0.171 0.270 0.382 0.540 0.715 0.854 1.047 1.208 1.351 1.48 1.60 1.71 1.91 2.70 3.82 5.4( 10 21.91 0.31 0.49 0.69 0.98 1.30 1.55 1.90 2.19 2.45 2.68 2.90 3.10 3.46 4.90 6.93 9.8( 12 35.63 0.50 0.80 1.13 1.59 2.11 2.52 3.09 3.56 3.98 4.36 4.71 5.04 5.63 7.97 11.27 15.9; 15 64.60 0.91 1.44 2.04 2.89 3.82 4.57 5.59 6.46 7.22 7.91 8.55 9.14 10.21 14.44 20.43 28.8E 18 105.04 1.49 2.35 3.32 4.70 6.21 7.43 9.10 10.50 11.74 12.87 13.90 14.86 16.61 23.49 33.22 46.9E 21 158.45 2.24 3.54 5.01 •7.09 9.37 11.20 13.72 15.85 17.72 19.41 20.96 22.41 25.05 35.43 50.11 70.8E 24 226.22 3.20 5.06 7.15 10.12 13.38 16.00 19.59 22.62 25.29 27.71 29.93 31.99 35.77 50.59 71.54 101.17 27 309.70 4.38 6.93 9.79 13.85 18.32 21.90 26.82 30.97 34.63 37.93 40.97 43.80 48.97 69.3 97.9 138.5 30 410.17 5.80 9.17 12.97 18.34 24.27 29.00 35.52 41.02 45.86 50.24 54.26 58.01 64.85 91.7 129.7 183.4 36 666.98 9.43 14.91 21.09 29.83 39.46 47.16 57.76 66.70 74.57 81.69 88.23 94.33 105.46 149.1 210.9 298.3 42 1006.1 14.23 22.50 31.82 44.99 59.5 71.1 87.1 100.6 112.5 123.2 133.1 142.3 159.1 225.0 318.2 449.E 48 1436.4 20.31 32.12 45.42 64.24 85.0 101.6 124.4 143.6 160.6 175.9 190.0 203.1 227.1 321.2 454.2 642.4 * Conveyance Factor = (1.486 x R2/3 x A) / n TABLE 4 CIRCULAR PIPE FLOW CAPACITY Full Flow (cubic feet per second) Mannings "n"= 0.012 Dia. *Conv. % Slope (feet per 100 feet) (in.) Factor 0.02 0.05 0.10 0.20 0.35 0.50 0.75 1.00 1.25 1.50 1.75 2.0 2.5 5.0 10.0 21 (c.f.s.) 3 0.957 0.014 0.021 0.030 0.043 0.057 0.068 0.083 0.096 0.107 0.12 0.13 0.14 0.15 0.21 0.30 0 4 2.062 0.029 0.046 0.065 0.092 0.122 0.146 0.179 0.206 0.231 0.25 0.27 0.29 0.33 0.46 0.65 0 5 3.738 0.053 0.084 0.118 0.167 0.221 0.264 0.324 0.374 0.418 0.46 0.49 0.53 0.59 0.84 1.18 1 6 6.079 0.086 0.136 0.192 0.272 0.360 0.430 0.526 0.608 0.680 0.74 0.80 0.86 0.96 1.36 1.92 2 8 13.091 0.185 0.293 0.414 0.585 0.774 0.926 1.134 1.309 1.464 1.60 1.73 1.85 2.07 2.93 4.14 5 10 23.74 0.34 0.53 0.75 1.06 1.40 1.68 2.06 2.37 2.65 2.91 3.14 3.36 3.75 5.31 7.51 10 12 38.60 0.55 0.86 1.22 1.73 2.28 2.73 3.34 3.86 4.32 4.73 5.11 5.46 6.10 8.63 12.21 17 15 69.98 0.99 1.56 2.21 3.13 4.14 4.95 6.06 7.00 7.82 8.57 9.26 9.90 11.06 15.65 22.13 31 18 113.80 1.61 2.54 3.60 5.09 6.73 8.05 9.86 11.38 12.72 13.94 15.05 16.09 17.99 25.45 35.99 50 21 171.65 2.43 3.84 5.43 7.68 10.16 12.14 14.87 17.17 19.19 21.02 22.71 24.28 27.14 38.38 54.28 76 24 245.08 3.47 5.48 7.75 10.96 14.50 17.33 21.22 24.51 27.40 30.02 32.42 34.66 38.75 54.80 77.50 109 27 335.51 4.74 7.50 10.61 15.00 19.85 23.72 29.06 33.55 37.51 41.09 44.38 47.45 53.05 75.0 106.1 15' 30 4440 35 6.28 9.94 14.05 19.87 26.29 31.42 38.48 44.44 49.68 54.42 58.78 62.84 70.26 99.4 140.5 19 .57 10.22 16.16 22.35 32.31 42.75 51.09 62.58 72.26 80.79 88.50 95.59 102.19 114.25 161.6 228.5 32 36 722 42 1089.9 15.41 24.37 34.47 48.74 64.5 77.1 94.4 109.0 121.9 133.5 144.2 154.1 172.3 243.7 344.7 48 48 1556.1 22.01 34.80 49.21 69.59 92.1 110.0 134.8 155.6 174.0 190.6 205.9 220.1 246.0 348.0 492.1 69 * Conveyance Factor = (1.486 x R2/3 x A) / n a A 0.7 U- 0.6 F- IAJ Z 0.5 w > 0.4 0 2 F CL 0.3 w o. z 0.2 0 z 0 m EXAMPLE • FLOW INTO INLET PER SO. FT. OF OPEN AREA (CFS/FT Figure 5-3 CAPACITY OF GRATED INLET IN SUMP (From: Wright -McLaughlin Engineers, 1969) Z. MAY 1984 5-11 DESIGN CRITERIA No Text 1.0 .9 .8 7 RM ».1 f- w w 0 .25 F- c� w .2 15 12 10 II 8 10 6 9 0 0 4 �U- i ' 8 x 3 w z - a of 7 , ��2' v P°t1� Ex°mp`e�' i z m 6 _ . Exaple, Part a_ J I'8- z z w 5.5 a a_ 0 U w .6 1L 0 5 z Z z .4 w = - 4.5 z 0o .3 c� w U. = 4 = _ .2 z co z 0 �^ 3.5 w w Q. w I 0 w wo .08 w 3 0E- o .06 = c� 0 w z - w = ac .04 or 2.5 w ° w ~ .03 r a 3 F, a .02 p 2 a F- U a.. w .01 L w 0 0 _ yo a - 1.5 5 4 3 2 1.5 1.0 8 .7 .6 119 1.1 .3 .25 2 15 IN Figure 5-2 NOMOGRPAH FOR CAPACITY OF CURB OPENING INLETS IN SUMPS, DEPRESSION DEPTH 2" Adapted from Bureau of Public Roads Nomograph MAY 1984 5-10 DESIGN CRITERIA 'S.4 'S.3.5 Grates for Pipes Where a clear and present danger exists such as a siphon, a drop in elevation adjacent to a sidewalk or road, a long pipe with one or more manholes, or at pipes which are near play- grounds, parks; and residential areas, a grate may be required. For most culverts through embankments and crossing streets, grates will not be required. When called for on the plans, grates shall meet the following requirements: a. Grating shall be constructed of steel bars with a minimum diameter of 5/8". Reinforcing bars shall not be used. b. Welded connections shall be 1/4" minimum. c. Spacing between bars shall normally be 6" unless site conditions are prohibitive. d. All exposed steel shall be galvanized in accordance with AASHTO M 111. e. Welded joints shall be galvanized with a rust preventive paint. I. Grates shall be secured to the headwall or end section by removable devices such as bolts or hinges to allow maintenance access, prevent vandalism, and prohibit entrance by children. Inlets Storm inlets shall be installed where sump (low -spot) conditions exist or street runoff -carrying capacities are exceeded. The curb inlets shown in the Standard Details, pages D-7, 8, 12 & 13, shall be used in all City Streets. If larger inlets are required, the Colorado Department of Highways Type R Curb Inlet, Standard M-604- 12, shall be used. For drainageways other than streets (for example, parking lots, medians, sump basins) an Area Inlet similar to the detail on page D-9 shall be used. The outlet pipe of the storm inlet shall be sized on the basis of the theoretical capacity of the inlet, with a minimum diameter of 15 inches, or 12 inches if elliptical or arch pipe is used. All curb openings shall be installed with the opening at least 2 inches below the flow line elevation. The minimum transition length shall be 3'6" as shown on the standard details previously listed. Because of debris plugging, pavement overlaying, parked vehicles, and other factors which decrease inlet capacity, the reduction factors listed in Table 5-4 shall be utilized. Table 5-4 INLET CAPACITY REDUCTION FACTORS Percentage of Drainage Condition Inlet Type Theoretical Capacity Sump or Continuous Grade ........................................... CDOH Type R-Curb Opening 5' 80% 10, 85% 15' 90% Street— Sump.............................................................. 4' Curb Opening 80% Street — Continuous Grade .......................................... 4' Curb Opening 80% Parking Lots, Medians ................................................... Area Inlet 80% The theoretical capacity of inlets in a low point or sump shall be determined from Figures 5-2 and 5-3. The theoretical capacity of curb openings on a continuous grade shall be determined from Figures 5-4, 5-5 and 5-6. The standard curb -opening is illustrated by Figure 5-4 and is defined as having a gutter depression apron W feet wide at the inlet opening which extends W feet upstream and downstream from the open- ing, has a depression depth (a) equal to W/12 feet at the curb face, and a curb opening height (h) of at least 0.5 feet. The graph as presented by Figure 5.5 is based on a depression apron width (W) equal to 2 feet and depression width (a) equal to 2 inches. The pavement cross-section is straight to the curb MAY 1984 5-8 DESIGN CRITERIA