45600ATL6. INC.
ELECTRICAL ENGINEERS
August 11, 2000
Louise Herbert
VF Ripley
401 W. Mountain Avenue
Suite 201
Ft. Collins, CO 80521
RE:, RegistryRidge 2nd,Filing
Job No. #0007
ZONAALP J McNuTT = P.E.
Dear Ms. Herbert:
Please see the following comments in reference to,y6ur,8/9/00 fax regarding the responses of the
planning department.
Lighting photometric calculations were not included under the gasoline canopy. of the proposed
development area as'ihis area.shall be considered'fhe future"tenants responsibility.
Calculations were completed for this filing as atypical ,coffimerci al area. Future tenants shall
provide, additional lighting under canopy maccordance with the City's standards, and include
lighting contributions from the current proposed filing.
The City of Ft. Collins requires that lighting levels shall not exceed 10 foot candles at any point.
Typically, gas stations propose 70 - 80 footcandles of light under their canopy for security
reasons and to make reading of pump instructions clear.: Special exceptions,,for items such as this
shall be requested by future tenant to the planning department.
`Respectfully,
Kate Hodgson
KH/slw
00071i.x-i i-ou.wlxl
C,2EELEY (970) 330-5266
5587 V. 19th STP-LLT "' •, DENVER (303) 654-1441
,CREELEY. COLORADO 80634 ` ` = FAX (970) 330-3667
e-mail: rjmcnutt@concentHc.net '"� FT. COLLIN-5 (970) 686-5678
Lighting Plan redlines:
a) Sheet 2 of 2 — C-store light levels under the pump canopy. Please
see attached letter from RJ McNutt and Associates, Inc.
Please call if you have any questions regarding the above. Thank you for your
consideration and we look forward to working with you during the development review
process.
Sincerely
VF Ripley Associates TST, Inc. Consulting Engineers
Louise Herbert Sharlene A. Shadowen, P.E. `
Eneineerine•
9) The circles at the end of the enhanced drives north and south of the recreational
open space area are pedestrian areas.
10) Emergency access drives removed
11) Parking to the c-store / retail area has been revised to accommodate the required
50' setback for parking spaces from streets.
12) See revised plat.
13) Coordinate with Fire and Engineering has resolved this issue.
14) See engineering response above under site plan item 6).
Stormwater Utility:
15) See revised plat.
16) A note has been added that all existing easements will be vacated with the plat.
17) Storm sewers have been revised too minimize conflicts with buildings and
clearances.
18) Developer is responsible for storm sewers within tracts. See note 2 on plat.
19) Point noted; however, we believe it would not be the best alternative for this site.
Natural Resources:
20) Grading plan does show drainage improvements (swales, pipes, inlets, etc.)
Plannine'
21) The emergency access drives north and south of the open space area will be
scored concrete. The pedestrian circles at the ends will be stamped tan colored
concrete.
22) The residential units will have some variation in materials and colors.
23) Additional red -line comments:
Site Plan redlines:
a) The `loading / parking areas' are for emergency vehicular maneuvering.
See engineering response above.
Plat:
1) Sight distance notes have been added to the sight plan.
2) Done
3) A note on the plat cover states that all existing easements are to be vacated
with this plat.
4) See #3
5) See #3
6) We have provided a blanket easement and have coordinated with utilities
to address all issues.
7) Building envelopes have been revised.
8) Have provided a blanket emergency access easement. This has been
accepted by the Fire Department and Engineering Department.
Site Plan:
1) The `loading zone' is an emergency access vehicle maneuvering area.
All emergency access areas will have painted curb and posted signs.
(see emergency access plan).
2) Drain water to driveways is shown as per the utility plans.
3) See comment #5 under utility plans above.
4) See comment #9 under utility plan above.
5) Revised. Site plan updated.
6) Plan labeling has been enlarged to make the plan more legible.
7) Storm water (separate comment sheet):
1) The overlap was corrected. The vacated easements were not shown per
Sheri (Engineering) and John VonNieda (TST). A note was added to the
plat indicating any easements not shown or specifically mentioned were
vacated with this plat.
2) Done.
3) Added discussion.
4) Same as A -A.
5) Detail was provided on Sheet 12.
8) Technical Services ( Mapping / Drafting Department):
a) Storm Water Department requesting specific easement for Storm Drainage
purposes.
b) Noted.
5) Zoning Department:
a) Handicapped ramps are shown where sidewalks meet the
enhanced crosswalk
b) Residential trash enclosures 10' x 12' are sized to
accommodate 2 dumpsters ( for trash and recyclables).
c) Plant note # 4 wording has been changed to read " value of
landscaping and installation".
d) Acknowledged. Note # 14 has been adjusted. The site plan note on trash
enclosure gates has been changed to say "all trash enclosures will be
gated'.
e) Elevation sheets have been identified as residential elevation on sheet 4 of
8.
6) Engineering (separate comment sheet): 11
Utility Plans:
1) Done
2) Done
3) All utility stubs shown as existing are being installed as part of phase 1 &
3, prior to final lift of paving being laid. A revised utility plan is being
coordinated with the FCLWD & SFCSD.
4) Done
5) Parking to the c-store / retail area has been revised to the required
50' setback for parking spaces from streets.
6) Done
7) Done
8) Done
9) Removed driveway cuts at emergency access drives.
10) Done
11) Driveway Revised.
12) Done
13) Done
14) Done
- .G
September 5, 2000
Steve Olt
Fort Collins Planning Department
281 North College Avenue
Fort Collins, CO 80524
Be: Response to staff letter
Registry Ridge PUD, Second Filing — Preliminary and Final
Dear Steve:
We have reviewed the staff letter dated July 10,2000 and have the following comments:
1) Public Service Company (New Century Energies):
a) See revised utility plan regarding revised utility layouts including shallow
utilities.
b) All trees have been checked with utilities. See revised landscape plan.
c) See revised utility plan.
d) See revised utility plan.
e) The water meter pits are located with a min 4' clearance from gas lines.
See revised utility plan.
2) Fort Collins- Loveland Water District and South Fort Collins
Sanitation District: See separate response letter.
3) Thompson School District R2-J:
Acknowledged.
4) Traffic Operations:
All crosswalks are shown as painted, striped crosswalks.