HomeMy WebLinkAboutHEARTHFIRE PUD, 2ND FILING - FINAL - 31-95E - CORRESPONDENCE - CITY STAFF (14)c. CUL-DE-SAC: A dead-end street cannot exceed 660' in length. The turn -around at
the end of the street must have an outside turning radius of 40' or more, and an inside
radius of 20'. Short fire lanes are permitted to facilitate a second point of access when
a street is greater than 660' in length. All structures beyond the 660' limit must be fire
sprinklered if a second point of access cannot be provided.
Again this comment continues to be addressed with each resubmittal. Hearthfire
Drive does exceed the 660' requirement but a short (250% 20' wide, all weather
surfaced EMERGENCY ACCESS DRIVE is provided for connecting Hearthfire
Drive to CR 13. This access is shown on the enclosed Final Site and Landscape
Plan as well as on the Final Utility Plans prepared by Shear Engineering
Corporation. This connection was discussed and approved by Mr. Ron Gonzalas
over a year ago when I discussed it with him at a meeting in Brian Shear's office.
d. STREET NAMES: Street names shall be reviewed and verified by L.E.T.A. prior to
being put into service.
Again, we have addressed this comment numerous times. In the many submittals
to the City, the street names have been reviewed, revisions made and we believe
all names have been approved.
Mike, hopefully this addresses all of your comments and concerns and we would request that you
send a letter to Mr. Steve Olt in the City's Current Planning Department stating the same.
If I can be of further assistance or should you have any additional comments or concerns, please
feel free to contact me at 226-1655.
Sincerely,
PineCrest Planning and Design LLC
Manager
Enclosure
Cc: Steve Olt, Ron Gonzalas, Tom Kennedy, Bill Yunker, Brian Shear
Hearthfire 2 Submittal
AIN0199 I = W
VINIECRIEST
February 1, 2001
Mr. Michael Chavez
Poudre Fire Authority
102 Remington
Fort Collins, Colorado 80524 .
RE: Hearthfire PUD, 2°d Filing
Comments related to your review of 11/15/00
Dear Mr. Chavez:
In response to your latest comments related to the Hearthfire PUD, 2"d Filing, we continue to
receive the same comments related to the plans. I have discussed these items with Mr. Ron
Gonzalas, and we believe all items have been previously addressed to meet your concerns. Please
note that your comments are as follows:
a. WATER SUPPLY: Fire hydrants are required at a maximum spacing of 600' along
an approved roadway. Each hydrant must be capable of delivering 1,5000 gallons of
water per minute at a residual pressure of 20 pounds per square inch. No commercial
building can be greater than 300' from a hydrant.
- A review of the Final Utility Plans from Shear Engineering shows that this
condition has been met. If you have additional concerns related to the hydrants
and/or pressures, please contact Mr. Brian Shear at 226-5334. Also note that
there are no commercial buildings located within this 2"d Filing of the Hearthfire
PUD.
b. ADDRESS NUMERALS: Address numerals shall be visible from the street fronting
the property and posted with a minimum of 6" high numerals on a contrasting
background (example: Bronze numerals on brown brick are not acceptable).
- This comment has continued to be addressed since the 2"d filing was first
submitted to the City in 1997. Since the first submittal there has been a note on
the Final Site and Landscape Plan that states: "House numbers within the
Hearthfire PUD shall be a minimum of 6 inch high numerals on a contrasting
background, shall be visible from the street facing the property and shall be
directly illuminated or back -illuminated by a light source of sufficient brightness
that numbers are visible from the adjacent street. Each light shall be downcast
type and controlled by a photocell. The Homebuilder shall install the light
fixtures, house numbers and photocell prior to the issuance of the certificate of
occupancy."
We believe thgt this note addresses your concern and have enclosed a copy of the
Final Site and Landscape Plan for your review.
Plartrti"S S DesiS" LLC
4225 Westshore Way Fort Collins, CO 80525
(970) 226-1655 • (970) 226-1635 fax
Sincerely,
and Design LLC
Manager
Enclosures
cc: Steve Olt, Tom Kennedy, Bill Yunker, Lucia Liley, Brian Shear, Fred Walker, Hearthfire 2 Submittal
r1N�C1tEsr
February 1, 2001
Ms. Kim Kreimeyer
Mr. Doug Moore
City of Fort Collins Planning Department
P.O. Box 580
281 N. College Ave
Fort Collins, Colorado 80522-0580
RE: Hearthtire P.U.D., 2od Filing, Final, #31795E
Resubmittal - Response Letter
Dear Kim and Doug:
As per Steve Olt's letter of November, 15, 2000, there were still several issues and concerns that
you had related to the Final Site and Landscape Plan for the Hearthfire PUD, Second Filing. The
first was related to the Showy Prairie Gentian that was found offsite along Richard's Lake. Doug,
Ted Boss and myself met onsite on December 7, 2000 to try to locate the plant. Although we did
find several specimens, because of the time of year, the exact and complete locations could not
be delineated and mapped. Therefore these locations cannot be shown on the plans. Based upon
our discussions with Doug, and because the plant is located offsite, he did not feel the delineation
was required at this time and requested that signage be installed along the existing trail. We have
added a note to the Site and Landscape Plan that states: Install sign that states: "There is a rare
Colorado Plant located in this area. Please remain on trail and all pets must be kept on leashes."
This sign will be installed when the development of the 2°d filing occurs. A copy of this plan is
enclosed for your review.
An additional item on your referral had to do with the relocation of the trail. Within the 2A filing,
there are no trails that connect to this area. There is an existing trail that was constructed with the
V filing just to the east of the 2°d filing that may be a concern. This trail and open space parcel
has been dedicated to the Homeowner's Association. If there is a concern with it's location, we
will work with you and the Association on the possibility of removing and/or relocating the trail.
The final item of concern that still remains is the connection of Town Center Way with the
property to the south. This item has been discussed many times and although the property may or
may not be developable under the City's Land Use Code, we have agreed with the Engineering
Department and Water Supply and Storage to plat the ROW and not construct this road until
development occurs to the south. The developer feels that we must provide access to the property
owner to the south and if it is determined in the future that this property cannot be developed, the
ROW can be vacated and turned over to the HOA as additional open space.
I believe this addresses all of the comments since the last submittal. Please review the enclosed
information and should you have any questions, feel free to give me a call.
PlAwii"S & Desig" LLC
4225 Westshore Way Fort Collins, CO 80525
(970) 226-1655 • (970) 226-1635 fax
Sincerely,
PineCrest Planning and Design LLC
Th as J. D n
Manager
Enclosure
Cc: Steve Olt, Brian Shear, Tom Kennedy
Hearthfire 2"d Submittal
AoTP1AlIECREST
February 1, 2001
Mr. Ward Stanford
City of Fort Collins Traffic Operations
P.O. Box 580
Fort Collins, Colorado 80522-0580
RE: Hearthfire PUD, 2"d Filing
Comments of November 15, 2000
Dear Ward:
In response to your letter and comments of November 15d' related to the Hearthfire PUD, 2"d
Filing, please note the following:
a. The Douglas Road/County Road 11 improvements issue needs to be resolved prior to
this project going to the Planning and Zoning Board for a decision.
- As discussed in my previous letter to Steve Olt of October 16, 2000, the
developer has been working with Cam McNair and Sherri Wamhoff to try to
resolve the issues and concerns with the Douglas Road improvements. He
has met again as early as two weeks ago to discuss the design for the
Douglas Road improvements to the east of Hearthfire Way.
Because there is currently a restriction in the development agreement for the
I' filing related to the required improvements, we do not understand why the
2"d filing plans cannot be signed off until the Douglas Road plans are
approved because there are already restrictions in place to prohibit more than
90 permits being issued for the development until the Douglas Road
improvements are completed.
b. The County Road 13 improvements should terminate a safe distance either before or
after the curve. Improvements should not terminate in the middle of the curve.
- Shear Engineering has designed CR 13 as per direction from the City. If the
location of the termination of the pavement has changed (based upon your
comment), please direct Shear Engineering and let them know where you
would now like the pavement to terminate. Note that Shear will be
resubmitting revised Utility Plans within the next week.
Ward, as requested in your Project Comment Sheet, I have enclosed a copy of the latest, revised
Site and Landscape Plan for your review. If you should have any addition comments or
questions, feel free to give me a call at 226-1655.
P1aH1hitiS & Design LLC
4225 Westshore Way Fort Collins, CO 80525
(970)226-1655 • (970) 226-1635 fax
believe that the developer should be required to add this crosswalk in a dedicated
and constructed City street. I believe this item was deleted from your written
comments.
Mark and Kathleen, hopefully this addresses all of your comments and concerns and we would
request that you send a letter to Mr. Steve Olt in the City's Current Planning Department stating
the same.
If I can be of further assistance or should you have any additional comments or concerns, please
feel free to contact me at 226-1655.
Sincerely,
PineCrest Planning and Design LLC
Thomas J.
Manager
Enclosure
Cc: Steve Olt, Tom Kennedy, Bill Yunker, Brian Shear
Hearthfire 2
r1N£CR�ST
February 1, 2001
Mr. Mark Jackson
Ms. Kathleen Reavis
City of Fort Collins Transportation Planning Dept.
P.O. Box 580
Fort Collins, Colorado 80522-0580
RE: Hearthfire PUD, 2"d Filing
Comments related to your review of 11/6/00
Dear Mark and Kathleen:
In response to your letter and redlined prints of November 6, 2000 related to the Hearthfire PUD,
2"d Filing, please note the following:
I . Interim improvements to Douglas Road (east or west) need to be at least 36' wide.
- This item is noted and the final design for Douglas Road will be per the required
City specifications.
2. Ultimate improvements to Douglas Road to be made to Minor Arterial design
standard as per the City Master Street Plan.
- This item is noted but there is not a requirement for this Developer to construct
the ultimate improvements Douglas Road to the Minor Arterial standard.
3. Improvements to County Road 13 to be made to Collector design standards as per the
City Master Street Plan. Agreement to build curb, gutter, and detached sidewalk (5'-
0" wide), and a bicycle lane on their side of the road.
- Although the Final Utility Plans have not been completely approved by the
Engineering Department, these improvements to CR 13 are shown on the Final
Utility Plans as prepared by Shear Engineering Corporation.
4. Should the pedestrian street crossings be painted or enhanced?
- The Final Site and Landscape Plan as well as the Final Utility Plans show the
crosswalks as painted. If it is the desire of the City to do something different,
please give us the appropriate direction and this will be done.
5. Will Town Center Way work for bicycle and pedestrian access to the south?
- As discussed in the past, the developer will be dedicating the ROW for Town
Center Way with this development to provide access and transportation
connectivity to the property to the south. There is some concern on the part of the
engineering and natural resources departments as to the developability of this
property, therefore the ROW will only be dedicated at this time and if the
property to the south ever develops, this road will be constructed. At that time,
the road will provide bicycle and pedestrian access to the south.
6. Red -lined- Final Site and Landscape Plan
- Although there are many red marked notations on the plan, we do not believe that
there are any comments that are needed to be addressed related to the 2"d Filing.
One note does state "Add painted crosswalk marking" This area is part of the I"
Filing which was approved and constructed several years ago and we do not
P1awNirtg Fr Desig" LLC
4225 Westshore Way Fort Collins, CO 80525
(970) 226-1655 • (970) 226-1635 fax
MoTP1NIECR£ST
rebruary 1, 2UU1
City of Fort Collins Technical Services Department
P.O. Box 580
Fort Collins, Colorado 80522-0580
RE: Hearthfire PUD, 2ad Filing
Comments related to your review of 11/6/00
Dear Technical Services Department:
In response to your letter and redlined prints of November 8, 2000 related to the Hearthfire PUD,
tad Filing, please note the following:
a. Some text on the subdivision plat, Site plan, Landscape Plan, utility plans, etc.) is not
reproducible (text sizes, line weight, etc.) It is too small and dense.
- Text on the Final Site and Landscape Plan has been revised with much of the
notes being enlarged and moved to the second sheet. A copy of this plan is
enclosed for your review and approval.
b. The plat boundary closes and the legal description matches the plat.
- This item is noted and we do not believe any revisions are needed base upon your
comment.
Hopefully this addresses all of your comments and concerns and we would request that you send
a letter to Mr. Steve Olt in the City's Current Planning Department stating the same.
If I can be of further assistance or should you have any additional comments or concerns, please
feel free to contact me at 226-1655.
Sincerely,
PineCrest Planning and Design LLC
Thoeas J:
Manager
Enclosure
Cc: Steve Olt, Tom Kennedy, Bill Yunker, Brian Shear, Bryan Short
Hearthfire 2
PJA "Nii"g Fr DcsiS" LLC
4225 Westshore Way Fort Collins, CO 80525
(970)226-1655 • (970) 226-1635 fax
T'14 NIECREST
February 1, 2001
Mr. Basil Hamdan
City of Fort Collins Stormwater Utility Department
P.O. Box 580
Fort Collins, Colorado 80522-0580 ,.
RE: Hearthfire PUD, 2°d Filing
Comments related to your review of 11/8/00
Dear Basil:
In response to your letter and redlined prints of November 8, 2000 related to the Hearthfire PUD,
2"d Filing, please note the following (as related to the Final Site and Landscape Plan):
Item 4: Please remember that the pending easements included with this submittal must be
in final form and signed before a final hearing on this project can be given.
- This item has been noted and the developer continues to be working with the
City Attorney's office, Glen Schlutter, the Water Supply and Storage
Company and their attorney as well as the Developer's attorney to resolve this
issue and create an easement that is acceptable to all parties.
Note that your redlined copy of the Final Site and Landscape Plan does not have any notations on
it. (This is being returned to Steve Olt).
Please note that Shear Engineering Corporation will be sending you revised copies of the Final
Utility Plans addressing the remainder of your comments.
Hopefully this addresses all of your comments and concerns and we would request that you send
a letter to Mr. Steve Olt in the City's Current Planning Department stating the same.
If I can be of further assistance or should you have any additional comments or concerns, please
feel free to contact me at 226-1655.
Sincerely,
Planning and Design LLC
�kr6trial; J:
Manager
Enclosure
Cc: Steve Olt, Tom Kennedy, Bill Yunker, Brian Shear, Lucia Liley, Fred Walker
Hearthfire 2
Pimi"iNg & Design LLC
4225 Westshore Way Fort Collins, CO 80525
(970) 226-1655 • (970) 226-1635 fax
The walls have been shown on the revised Final Site and Landscape Plan
and as we discussed, I will contact Steve Olt and ask him to determine if a
Minor Amendment is required for the I" Filing.
The other comment on the redlined plan is "Bollard detail provided is not the
drive over type."
Shear Engineering has received the details of the drive over bollard from the
manufacturer of the bollard and should be including them on their revised
Final Utility Plans. These plans will be resubmitted to you within the next
week.
Note that I will return your red -lined plan to Steve Olt with our resubmittal next week.
Sherri, as requested in your Project Comment Sheet, I have enclosed a copy of the latest, revised
Site and Landscape Plan for your review. Hopefully this addresses all of your comments and
concerns and we would request that you send a letter to Mr. Steve Olt in the City's Current
Planning Department stating the same.
Sincerely,
LLC
rnciosure
Cc: Steve Olt, Brian Shear, Tom Kennedy, Lucia Liley
Hearthfire 2nd Submittal
rIv�cn�sr
February 1, 2001
Ms. Sherry Wamhoff
City of Fort Collins Engineering Department
P.O. Box 580
Fort Collins, Colorado 80522-0580
RE: Hearthfire PUD, 2"d Filing
Comments of November 15, 2000
Dear Ward:
In response to your letter and red -lined comments of November 15`h related to the Hearthfire
PUD, 2"d Filing, Final Site and Landscape Plan, please note the following:
a. The applicant and developer must resolve the necessary improvements to Douglas
Road before this project goes to the Planning and Zoning Board for a decision. This
has somewhat stalled and plans are still needed.
- As discussed in my previous letter to Steve Olt of October 16, 2000, the
developer has been working with Cam McNair and yourself to try to resolve
the issues and concerns with the Douglas Road improvements. He has met
with you again as early as two weeks ago to discuss the design for the
Douglas Road improvements to the east of Hearthfire Way.
Because there is currently a restriction in the development agreement for the
I" filing related to the required improvements, we do not understand why the
2"d filing plans cannot be signed off until the Douglas Road plans are
approved because there are already restrictions in place to prohibit more than
90 permits being issued for the development until the Douglas Road
improvements are completed.
b. The applicant and developer must address the piece of "old" road right-of-way
(ROW) going south from the road bend at Inverness Street and County Road 13.
This ROW does affect the Hearthfire PUD, Second Filing property. Has the ROW
been vacated?
- This issued was discussed with the City Attorney and the developer's
attorney. It was determined that the ROW was never legally granted and/or
recorded in this area and therefore no vacation is needed. I believe you have
received the correspondence from both attorneys as to that fact.
c. There are also several comments on your red -lined Final Site and Landscape Plan.
The first is "Need to show retaining wall (s). Were not shown on the 151 filing. May
need to do a minor amend. to V filing plan."
Plat i "i"5 & Design LLC
4225 Westshore Way Fort Collins, CO 80525
(970) 226-1655 • (970) 226-1635 fax