Mr. Todd Rand
TST Inc.
748 Whalers Way, Building D
Fort Collins, Colorado 80525
Re: East Ridge Utility Plans: 2nd Review
Dear Mr. Rand:
Plans for the East Ridge development were received at Boxelder Sanitation District (District). District
staff have reviewed and redlined the drawings. The following comments are to further clarify redlines.
Note that comments below are not included for all redlines on the drawings.
Sheet #
Comment
All
Use updated signature block — updated version emailed to Keith Sheaffer on 19
Sheets
May 2008.
Plat
Add the plat language for sewer easements — emailed version to Keith Sheaffer
she 1
on 19 May 2008.
of 10
51
See redlines, need to revise location of MH NMI0010 so that it is more
accessible.
64
Easement for sewer is called out as 25-ft, plat shows 30-ft. District requires 30-ft
as called out on plat.
Please return these redlines with future submittals to aid in our back -checking of the revised drawings.
I hope these comments and the redlines are clear enough to be easily addressed in a revision to these
plans. If there are questions, please contact me at 970-498-0604.
S:\DEVELOPMEN1\Basins\West Basin\Cooper_Slough_Interceptor_Subbasin\East Ridge\Design Review\2008-5-22-2nd-
review.doc
3201 East Mulberry, Unit Q - P.O. Box 1518 • Fort Collins, Colorado 80522
Phone (970) 498-0604 • Fax (970) 498-0701 • Email bsdQverinet.com
Ca
22 May 2008
Jim Sell Design, Inc.
153 West Mountain Avenue
Fort Collins, Colorado 80524
Re: East Ridge Utility Plans: 2nd Review - Landscape
Jim Sell Design:
MAY 2 3 20000
Plans for the East Ridge development were received at Boxelder Sanitation District (District). District
staff have reviewed and redlined the landscaping drawings.
The District is concerned with the close proximity to the sanitary sewer line of some trees as shown on
drawings L6 and L7. The District has redlined those drawings indicating trees it believes are
problematic. The driplines of large trees (e.g. cottonwood, hackberry, etc.) must not overlap that of the
sanitary sewer so that the potential from root intrusion into the sewer is minimized. Root intrusion
leads to more frequent maintenance by the District and even with increased maintenance, can result in
sanitary sewer backups.
Please return these redlines with future submittals for our use in back -checking the revised drawings.
Please review the redlines. If there are questions, please contact me at 970-498-0604.
ngineer