HomeMy WebLinkAboutPVH HEALTH SYSTEMS, HARMONY CAMPUS, 4TH FILING, MOB (REDSTONE) - FDP - 32-98K - CORRESPONDENCE -[8/11/06] Provide easements on plat for all public water/sewer lines. Minimum widths:
Water 20 feet; Sewer 30 feet. Curb stop on water service must be within easement.
Topic: Water/WW
Number: 50 Created: 8/11 /2006
[8/11/06] Show curb stop and meter pit. Curb stop must be within easement and meter pit
must be within 2 feet of curb stop.
Number: 51 Created: 8/11 /2006
[8/11/061 Provide 0.2 ft drop (min.) where connecting to existing sewer MH.
Number: 52 Created: 8/11 /2006
[8/11/06] Include updated standard details for 1.5 and 2 inch meters.
Number: 53 Created: 8/11 /2006
[8/11/06] See plans for other comments.
Please return all of your redlined plans when you re -submit.
Should you have any questions regarding these issues or any other issues related to this
project, please feel free to call me at (970) 221-6750.
Sincerely,
C� Cameron Gloss
Current Planning Director
Page 4
Department: PFA Issue Contact: Carie Dann
Topic: fire
Number: 70 Created: 8/16/2006
[8/16/06] REQUIRED ACCESS: Comments from a project letter dated March 24, 2004,
regarding two access points were not addressed. The single access is from the private drive
to the north of the proposed structure. Connecting the proposed Emergency Access
Easement to the existing EAE to the west (in the parking lot) will help address this issue.
Department: Traffic Operations
Topic: Traffic
Number: 54
[8/11/06] No issues
Issue Contact: Eric Bracke
Created: 8/11 /2006
Department: Transportation Planning Issue Contact: David Averill
Topic: Transportation
Number: 67 Created: 8/15/2006
[8/15/06] Please dimension all walkways on overall utility plan.
Department: Stormwater-Water-Wastewater Issue Contact: Basil Hamdan
Topic: Easements
Number: 45 Created: 5/21 /2004
[8/15/06] A letter from the property owner agreeing to the work outside of the plat boundary
will be sufficient.
[5/21/04] Off -site easements should be provided for any work to be done outside of the
limits of this development proposal as is the case for some of the proposed storm sewer
improvements.
Department: Stormwater-Water-Wastewater Issue Contact: Roger Buffington
Topic: Easements
Number: 49 Created: 8/11/2006
[8/11/06] Provide offsite easement for public sanitary sewer and for 8-inch water main and
fire hydrant. Minimum width for sewer easements is 30 feet and for water is 20 feet.
Department: Stormwater-Water-Wastewater Issue Contact: Basil Harridan
Topic: Grading
Number: 68 Created: 8/15/2006
[8/15/06] Grading plan needs to be cleaned up. Too many overlapping labels.
Topic Inlet Overflow
Number: 75 Created: 8/17/2006
[8/17/06] Please provide erosion protection for the overflow path from the inlet at the east
end of the parking lot.
Topic: Landscape Plan
Number: 69 Created: 8/16/2006
[8/16/06] Please ghost the storm lines shown on the plan.
Department: Stormwater-Water-Wastewater Issue Contact: Roger Buffington
Topic: Plat
Number: 48 Created: 8/11 /2006
Page 3
Number: 59 Created: 8/11 /2006
[8/11/06] Please provide a letter from PVH for authorization to do offsite grading and
drainage work.
Topic: Plat
Number: 60 Created: 8/11 /2006
[8/11/06] Please make corrections to the Plat per our meeting on August 10. Correct the
title to read ... second filing and a portion of Lot 1 ...
Revise the easement note on the cover sheet regarding easement vacations shown on this
new Plat.
Number: 61 Created: 8/11 /2006
[8/11/06] All other easements not being dedicated by this Plat but required for the project
will need to be reviewed by the City prior to recordation. A review fee of $250 per easement
document will apply. We strongly recommend that the separate easements be submitted as
soon as possible to minimize any delay to the approval of the project and issuance of a
permit.
Topic: Technical Services
Number: 71 Created: 8/16/2006
[8/16/06] Boundary and legal close. Legal and Plat do not match. Please see redline
comments.
Number: 72 Created: 8/16/2006
[8/16/06] Do not use Block 1 in description, can just be Lot 1.
Number: 73 Created: 8/16/2006
[8/16/06] Several line over text, text overlap problems which will not scan well. Please see
redline comments.
Number: 74 Created: 8/16/2006
[8/16/06] Please correct all typographical errors in the legal description.
Department: Light & Power Issue Contact: Alan Rutz
Topic: General
Number: 62 Created: 8/14/2006
[8/14/06] Will an Access Easement be required to service the new transformer from the
existing property to the west?
Number: 63 Created: 8/14/2006
[8/14/06] The area east of the parking lot and east of the building is subject to Electric
Development Charges. The area north of the Private Drive is also subject to Electric
Development Charges. These areas need to be platted and billed prior to installation of the
electric system.
Department: Natural Resources
Topic: General
Number: 47
[8/3/06] No issues.
Issue Contact: Doug Moore
Created: 8/3/2006
Page 2
STAFF PROJECT REVIEW
City of Fort Collins
s�
BHA DESIGN Date: 08/18/2006
ANGIE MILEWSKI
4803 INNOVATION DR
FT. COLLINS, CO 80525
Staff has reviewed your submittal for PVH HEALTH SYSTEMS, HARMONY CAMPUS, 4TH
FILING, MOB (REDSTONE) - FINAL PLANS, and we offer the following comments:
ISSUES:
Department: Current Planning Issue Contact: Cameron Gloss
Topic: Landscape Plan
Number: 64 Created: 8/14/2006
[8/14/06] When proceeding to mylar drawings, please review and correct typographical
errors on the landscape plan.
Topic: Plat
Number: 65 Created: 8/14/2006
[8/14/06] Please remove the title "Preliminary Plat" from the plat document.
Topic: Post Office
Number: 66 Created: 8/15/2006
[8/15/06] Bonnie Ham from the USPS offered the following comment:
Developer must provide adequate mail receptacles for occupants. Number of potential
tenants is unknown at this time.
Department: Engineering Issue Contact: Randy Maiziand
Topic: Engineering
Number: 55 Created: 8/11 /2006
[8/11/06] Please submit the attached development agreement information sheet so that
staff can begin preparing the draft agreement.
Number: 56 Created: 8/11 /2006
[8/11/06] All easements not being recorded with the replat must be recorded by separate
instrument. Each easement document must be reviewd by the City prior to recordation.
Please submit all separate easement documents for review with a $250 review fee per
document. (sewer, parking lot, drainage etc... )
Number: 57 Created: 8/11 /2006
[8/11/06] A connecting walkway shall be provided from the proposed building site to the
public street system, Snow Mesa Drive. The walk shall be at least 4.5 feet wide and
contained within an easement outside the project boundary. You may also submit a
modification to the code as discussed at the staff review meeting to utilize the existing
concrete walk on the north side of the private drive.
Number: 58 Created: 8/11 /2006
[8/11/06] A small drainage easement will be needed for the rip rap pad outlet structure to
the existing pond to the east. Please show and label the drainage easement on the plans,
by separate document.
Page 1