HomeMy WebLinkAboutPVH HEALTH SYSTEMS, HARMONY CAMPUS, 4TH FILING, MOB (REDSTONE) - PDP - 32-98G - CORRESPONDENCE - (3)Number: 5 Created: 3/31/2004
[3/31/04] Landscaping needs to be shown on the east end of the parking lot
perimeter.
Number: 6 Created: 3/31/2004
[3/31/04] On the landscape plan, show plat counts and codes on the plan as well as
counts on the key
Number: 7 Created: 3/31/2004
[3/31/04] Show handicap ramps at HC spaces, crosswalks etc
Number: 8 Created: 3/31/2004
[3/31/04] Any trash/recyclable enclosures proposed??
Please return all of your redlined plans when you re -submit.
If you have any questions regarding these issues or any other issues related to this
project, please feel free to call me at (970) 221-6750.
Sincerely,
Cameron Gloss
Current Planning Director
Page 5
Number: 26 Created: 4/21/2004
[4/21/04] Will the drive aisle that goes in front of the new medical building be
extended to the east with future expansion?
Number: 27 Created: 4/21/2004
[4/21/04] To separate pedestrians from motor vehicles in the large parking lot
construct a walkway through the landscaped islands to the major walkway spine
(see redlines).
Department: Water Wastewater Issue Contact: Jeff Hill
Topic: General
Number: 17 Created: 4/21/2004
[4/21/04] Provide utility easements for all sanitary sewer mains and offsite utility
easements for sanitary sewer services which cross adjacent lots.
Number: 18 Created: 4/21/2004
[4/21/04] Include all appropriate water and sewer details with the final submittal.
Number: 19 Created: 4/21/2004
[4/21/04] Our records indicate that a 4-inch and 6-inch water lines were stubbed out
for this building. Clearly define the abandonment of the existing 4-inch water line
and installation of the proposed 1 1/2-inch water service.
Number: 20 Created: 4/21/2004
[4/21/04] See site, landscape and utility plans for other comments.
Department: Zoning Issue Contact: Jenny Nuckols
Topic: Zoning
Number: 1 Created: 3/31/2004
[3/31/04] The dashed areas, denoting existing parking, will there still be some
handicap spaces on the west side of the proposed building. Its unclear on the site
plan
Number: 2 Created: 3/31/2004
[3/31/04] Please remove topo lines from final site plan
Number: 3 Created: 3/31/2004
[3/31/04] It doesn't look like the building meets our commercial building standards,
there isn't any articulation, no apparent base or top treatments - its needs some
pizzazz
Number: 4 Created: 3/31/2004
[3/31/04] Building height needs to be shown on elevations as well as materials,
colors etc.
Page 4
Please discuss in the text of the report how water quality mitigation will be achieved.
This should be included in the report before the hearing.
Number: 29 Created: 4/21 /2004
Please provide a preliminary site -specific grading plan for the proposed site. This
should be included in the utility plan set before the hearing.
Number: 30 Created: 4/21/2004
At final plan review, all the coordination efforts between the various filings for the
construction of the drainage improvements needs to be documented with this
drainage report.
Topic: Erosion/Sediment Control
Number: 31 Created: 4/21 /2004
1. Plan will be reviewed when a complete sediment/erosion control plan is
submitted per City of Fort Collins specifications.
Department: Transfort Issue Contact: Garold Smith
Topic: Zoning
Number: 9 Created: 4/6/2004
No Comments
Department: Transportation Planning Issue Contact: Tom Reiff
Topic: Transportation
Number: 23 Created: 4/21 /2004
[4/21/04] Please provide a walkway connection from the walkway along the north
side of the drive aisle to the sidewalk/trail along Harmony Road. It should be
designed similar to the walkway connection to the west that connects the
sidewalk/trail to the hospital's main entrance. Also the crosswalk across the drive
aisle should be designed similar to the crosswalk design to t he west (see red lines).
Number: 24 Created: 4/21 /2004
[4/21/04] Please consider increasing the widths of the 6 foot attached walkways
along the walkway spine through the parking lot to a minimum 7-foot width. Potential
users of the walkways accessing the medical building could be. people in
wheelchairs, in casts, using crutches, etc. and the extra width will increase their
mobility since two feet of the walkway will be taken up by cars overhanging into the
walkway. This would leave a minimum of a 5 foot clear space enough for two wheel
chairs to pass each other.
Number: 25 Created: 4/21 /2004
[4/21/041 Will the handicap parking stalls along the walkway spine be flush with the
walk and landscaping? Or will there be a raised curb with access ramps every 9
feet?
Page 3
J
walkway. System modification charges will apply to any electric system that needs
to be relocated.
Number: 12 Created: 4/19/2004
[4/19/04] On the Landscape Plan show the electric vault located on the north side of
the proposed building and remove landscaping from around the vault.
Number: 13 Created: 4/19/2004
[4/19/04] Submit Commercial Service Information Form (C-1) with building load
requirements.
Number: 14 Created: 4/19/2004
[4/19/04] On the Utility Plan show where electric meter and CT cabinet will be
located on the building and coordinate the transformer location with Light & Power.
Department: PFA Issue Contact: Ron Gonzales
Topic: fire
Number: 32 Created: 4/26/2004
[4/26/04] A fire sprinkler system shall be required. Submit plans for review as
required
Number: 33 Created: 4/26/2004
[4/26/04] the building address shall be visible from the street on which it fronts,
posted on a contrasting background, minimum 6 inch numerals
Number: 34
Created: 4/26/2004
[4/26/04] a fire lane shall be provided, and platted as an emergency access
easement. Please provide a fire lane plan for approval prior to installation.
Number: 35 Created: 4/26/2004
[4/26/04] fire hydrants are required on 600-ft. centers down the fire lane, and one
within 300 ft. of the building.
Number: 36 Created: 4/26/2004
[4/26/04] hazardous materials for this office bldg.shall be disclosed to the PFA.
Department: Police Issue Contact: Joseph Gerdom
Topic: General
Number: 16 Created: 4/20/2004
[4/20/04] Lighting levels at south end - drive/loading area - fall below required 1.Ofc.
Ornamentals along north side of building may block surveillance of parking lot from
building. Private/maintenance doors should have lighting and viewports.
Department: Stormwater Utility
Topic: Drainage
Number: 28
Issue Contact: Wes Lamarque
Created: 4/21 /2004
Page 2
6a �
City of Fort Collins
BHA DESIGN
ANGIE MILEWSKI
4803 INNOVATION DR
FT. COLLINS, CO 80525
Angie,
STAFF PROJECT REVIEW
Date:04/26/2004
Staff has reviewed your submittal for PVH HEALTH SYSTEMS, HARMONY
CAMPUS, 4TH FILING, MEDICAL OFFICE BUILDING II PDP - TYPE I, and we offer
the following comments:
ISSUES:
Department: Current Planning Issue Contact:. Cameron Gloss
Topic: General
Number: 21 Created: 4/21 /2004
[4/21/04] No information was provided regarding the proposed exterior building
materials and colors. Please add to the building elevations a summary list of all
building materials and the colors of each to ensure compatibility with the existing
medical office building.
Number: 22 Created: 4/21 /2004
[4/21/04] Please remove the word 'Preliminary" from the plat. Action taken by the
Hearings Officer on this application is based on this document being the final
version.
Department: Engineering Issue Contact: Dave Stringer
Topic: General
Number: 15 Created: 4/20/2004
[4/20/04] No comments on this PDP submittal. Will have comments on Final
Compliance Plan. Engineering okay for hearing
Department: Light & Power Issue Contact: Alan Rutz
Topic: General
Number: 10 Created: 4/19/2004
[4/19/04] Underground electric lines on the Utility Plan and other plans are not
shown in their correct location. Please locate and show the correct location of
electric lines, vaults and transformers on the Utility Plan. Final comments or
approval of the plans can not be made without this being corrected.
Number: 11 Created: 4/19/2004
[4/19/04] There is an existing electric line under the proposed walkway connecting
the two buildings. Please submit details of this part of building and its foundation.
Include plan and profile details of the existing electric line and proposed building
Page I