HomeMy WebLinkAbout4406 SENECA ST. GROUP HOME - PDP - PDP170024 - CORRESPONDENCE -the threshold of needing a TIS. Based on section 4.2.3.1) of LCUASS, the
Traffic Impact Study requirement can be waived.
be the yard between the street abutting the lot and an imaginary line running
along the front edge of the building closest to the street and extending to the
side property lines. With the addition of the pavers to allow parking on the north
side of the lot, what percentage of the front yard is dedicated to parking? This
may push you above 40%, which would not be permitted. If the existing driveway
exceeds 40%, you will not be able to go further into non-conformance by
dedicating more of the front yard to parking. Please provide an analysis of the
percentage of front yard dedicated to parking.
Department: Stormwater Engineering
Contact: Jesse Schlam, 970-218-2932, ischiam@fcgov.com
Topic: Erosion Control
Comment Number: 1 Comment Originated: 07/20/2017
07/20/2017: No Comment from erosion control.
Contact: Wes Lamarque, 970-416-2418, wlamargue@fcgov.com
Topic: General
Comment Number: 2 Comment Originated: 08/02/2017
08/02/2017: Please provide a grading plan for the area of improvements near
the northeast corner of the lot.
Department: Technical Services
Contact: Jeff County, 970-221-6588, *county@fcgov.com
Topic: Building Elevations
Comment Number: 4 Comment Originated: 07/26/2017
07/26/2017: Please revise the legal description as marked. See redlines.
Comment Number: 5 Comment Originated: 07/26/2017
07/26/2017: There is text that needs to be masked. Mask all text in hatched
areas. See redlines.
Comment Number: 6 Comment Originated: 07/26/2017
07/26/2017: There are line over text issues. See redlines.
Topic: Site Plan
Comment Number: 1 Comment Originated: 07/26/2017
07/26/2017: Please revise the legal description as marked. See redlines.
Comment Number: 2 Comment Originated: 07/26/2017
07/26/2017: There are line over text issues. See redlines.
Comment Number: 3 Comment Originated: 07/26/2017
07/26/2017: There is text that needs to be masked. Mask all text in hatched
areas. See redlines.
Department: Traffic Operation
Contact: Nicole Hahn, 970-221-6820, nhahn@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 08/01/2017
08/01/2017: The anticipated change in traffic volume is not expected to rise to
Applicants of new projects should email scarter@fcgov.com to schedule a
pre -submittal meeting. Applicants should be prepared to present site plans,
floor plans, and elevations and be able to discuss code issues of occupancy,
square footage, and type of construction being proposed.
Department: PFA
Contact: Jim Lynxwiler, 970-416-2869, wlynxwiler@poudre-fire.org
Topic: General
Comment Number: 1 Comment Originated: 08/01/2017
08/01/2017: GROUP R-4, CONDITION-2 OCCUPANCIES
> IFC 903.2.8.3: PFA notes the building will be equipped with a fire sprinkler
system as required by IFC 903.3.1.2 for Condition 2, Group R-4 occupancies.
Attics shall be protected in accordance with Section 903.2.8.3.2.
Please contact Assistant Fire Marshal, Joe Jaramillo with any fire sprinkler
related questions at 970-416-2868.
Comment Number: 2 Comment Originated: 08/01/2017
08/01/2017: FIRE ALARM & DETECTION
> IFC 907.2.10: Fire alarms systems and smoke alarms shall be installed n
Group R-4 occupancies as required in Sections 907.2.10.1 through 907.2.10.3.
Comment Number: 3
Comment Originated: 08/01/2017
08/01/2017: Other fire department comments pertaining to exiting
requirements may apply at time of building permit.
Department: Planning Services
Contact: Clay Frickey, 970-224-6045, cfrickey@fcqov.com
Topic: General
Comment Number: 1
Comment Originated: 08/01/2017
08/01/2017: How many parking spaces are included as part of this project?
Please add a table that details how you are meeting the parking requirement
and show the parking spaces clearly on the site plan. Since the parking
requirement is based on the number of employees, you will need to indicate this
in the parking table as well.
Comment Number: 2 Comment Originated: 08/01/2017
08/01/2017: The City of Fort Collins requires standard site plan notes on all
plans submitted. I will send you these notes to include on your next submittal. In
addition to these notes, we will need a couple of additional notes specific to this
project:
1. Indicate the number of residents you are seeking to allow.
2. Indicate that residents of the group home will not be allowed to own a car.
Comment Number: 3 Comment Originated: 08/01/2017
08/01/2017: Municipal Code section 20-105(d) requires that no more than 40%
of the front yard may be used for parking. The front yard shall be considered to
Department: Environmental Planning
Contact: Rebecca Everette, 970-416-26259 rverette@fc_qov.com
Topic: General
Comment Number: 1 Comment Originated: 07/12/2017
07/12/2017: Will the existing trees and shrubs on the property be protected
during construction? If so, please add the existing trees on the site plan and add
a note clarifying that existing landscaping will remain and be protected.
Department: Forestry
Contact: Molly Roche, mroche@fcgov.com
Topic: Landscape Plans
Comment Number: 1
08/03/2017:
Retain and protect all existing landscaping.
Department: Internal Services
Contact: Sarah Carter, 970-416-2748, scarter@fcgov.com
Topic: Building Insp Plan Review
Comment Number: 2
Comment Originated: 08/03/2017
Comment Originated: 08/01/2017
08/01/2017: Construction shall comply with adopted codes as amended.
Current adopted codes are:
2015 International Building Code (IBC)
2015 International Energy Conservation Code (IECC)
2015 International Mechanical Code (IMC)
2015 International Fuel Gas Code (IFGC)
2015 International Plumbing Code (IPC) as amended by the State of Colorado
2017 National Electrical Code (NEC) as amended by the State of Colorado
Fort Collins has amendments to most of the codes listed above. See the
fcgov.com/building web page to view them.
Accessibility: State Law CRS 9-5 & ICC/ANSI Al17.1-2009.
Snow Load Live Load: 30 PSF / Ground Snow Load 30 PSF.
Frost Depth: 30 inches.
Wind Load: 100- MPH 3 Second Gust Exposure B.
Seismic Design: Category B.
Climate Zone: Zone 5
Energy Code Use: 2015 IECC residential chapter.
Comment Number: 1
Comment Originated: 08/01/2017
08/01/2017: This is a change of occupancy from an R3 single family dwelling to
an R4 assisted living facility.
Comment Number: 3
Comment Originated: 08/01/2017
08/01/2017: Please schedule a pre -submittal meeting with Building Services
for this project. Pre -Submittal meetings assist the designer/builder by assuring,
early on in the design, that the new projects are on track to complying with all of
the adopted City codes and Standards listed below. The proposed project
should be in the early to mid -design stage for this meeting to be effective.
Fort Collins
Community Development and
Neighborhood Services
281 North College Avenue
PO Box 580
Fort Collins, CO 80522
970.221.6750
970.224.6134 - fax
kgov. com/developmentreview
August 07, 2017
38844 CR 31
Eaton, CO 3035701169
RE: 4406 Seneca St Group Home, PDP170024, Round Number 1
Please see the following summary of comments from City staff and outside reviewing
agencies for your submittal of the above referenced project. If you have questions about
any comments, you may contact the individual commenter or direct your questions through
the Project Planner, Clay Frickey, at 970-224-6045 or cfrickey@fcgov.com.
Comment Summary:
Department: Engineering Development Review
Contact: Katie Andrews, 970-221-65015 kandrews@fcqov.com
Topic: General
Comment Number: 1
Comment Originated: 07/31/2017
07/31/2017: Prior to CO, any damaged or non-ADA-compliant public curb,
gutter, sidewalk, or asphalt along the property's frontage will need to be
repaired or replaced. This work will require a sidewalk permit and this permit
will need to be obtained prior to building permit. More information about the
permit can be found at: https://www.fcgov.com/engineering/inspection.php. A
City construction inspector may help scope the required work if requested.
Comment Number: 2
Comment Originated: 07/31/2017
07/31/2017: Please provide a 9 foot utility easement along Seneca St.
adjacent to the ROW and please reflect this on the site plan. More information
about the easement dedication process can be found here:
http://www.fcgov.com/engineering/devrev.php
Comment Number: 3
Comment Originated: 08/02/2017
07/31/2017: Please add the following note to the site plan: Any damaged curb,
gutter and sidewalk existing prior to construction, as well as streets, sidewalks,
curbs and gutters, destroyed, damaged or removed due to construction of this
project, shall be replaced or restored to City of Fort Collins standards at the
Developer's expense prior to the acceptance of completed improvements
and/or prior to the issuance of the first Certificate of Occupancy.