7. On the H-5's, are these wall -mounts or pole -mounts? The photometric appears to
indicate wall -mounts and the table says "wall mount bracket" but the schedule
says poles at 16 feet. Please clarify.
8. On the goosenecks, there is supposed to be16 poles but I only count 15 and 20
walls, but I only count 18. Please double check me to make sure the plan and
schedule match.
So far, the plan looks very good and complies with the L.D.G.S. I am going to do one
more run through with our contact in Light and Power to verify that the types of
distribution are appropriate for the fixtures in their particular locations. I plan on doing
this early next week. As always, call if you have any questions.
Sincerely:
Ted Shepard
Chief Planner
Corn; airy Planning and Environmem-Jervices
Current Planning
City of Fort Collins
October 29, 1999
Mr. Kurt Prinslow
CLC Associates, Inc.
8480 East Orchard Road
Englewood, CO 80111
Dear Kurt:
I have reviewed the Lighting Plan for Mulberry and Lemay Crossings, Filing One. The
following comments are offered:
1. The light source and wattages per fixture are exactly what we are looking for.
2. The average footcandle of 2.3 is acceptable.
3. The gooseneck fixture is very attractive and therefore acceptable.
4. There is one area where the footcandles get rather high for being so close to
Buffalo Run. This the area on the northwest comer of the site, where there is one
H-3 abutting the 12 parking spaces that face north.. It appears that two footcandle
readings of 5.0 and 4.3 are on the north side of the parking lot. Perhaps these
readings could be reduced in this area due to sensitivity with Buffalo Run.
5. The schedule needs to specify that for H1 — H5 luminaires that the catalog number
reflects the Magnusquare "arm -mount," "flat -lens" luminaire. I don't see in the
catalog number where there is a distinction between this preferred luminaire and
the drop -lens luminarie.
6. Not sure about the suffix of the MSM series. For example, for the H-1, the suffix
of 3Px does not tie back to a catalog description. What does this mean? Please
specify or clarify what the following suffixes refer to: .
H-1: 3Px
H-2: x-xWx
H-3: 3Px
H-4: x-xWx
H-5: 3Px