HomeMy WebLinkAboutRAMADA LIMITED SUITES PUD - PRELIMINARY/FINAL - 16-96 - CORRESPONDENCE -12. A traffic impact study will be required. The traffic study should incorporate potential
traffic from lots 3-5. It will be necessary to obtain an access easement from the
owner of Lot 3 for the shared access. Sidewalks along Mason Street must be at
least five feet in width and detached from the curb. For more information, regarding
these comments, please contact Sheri Wamhoff at 221-6750.
13. The site is located in the McClellands/Mail Creek Drainage Basin. The Storm
Drainage Fee in this basin is $3,717 per acre subject to the runoff coefficient
reduction. A standard drainage and erosion control report is required, with the
exception of the release rate of 0.5 cfs/acre. The Stormwater Utility would prefer for
this site to drain to the existing storm sewer at Boardwalk and Mason; however, if
this would be a hardship, the detained release may be allowed into the curb and
gutter of Mason Street. There is an S.I.D. (Special Improvement District) payment
due on this property for the storm sewer improvements. The fee due will be roughly
equal to $2,751.47 per acre, plus the Handy -Whitman Utility Cost Index (see
handout example done for lots 4 and 5). Drainage cannot flow into the railroad
right-of-way without an easement; most sites along the railroad R.O.W. have been
bringing the railroad drainage through their sites. The site may be next to an existing
wetland; if so, any impacts to said wetland must be addressed/mitigated. For
further information, please contact Glen Schlueter, 221-6589.
4. If a kitchen will be part of the proposal, the City's Water and Wastewater Department
will require a grease interceptor on the sanitary sewer line.
There is an eight (8") inch sanitary sewer line and an eight (8") inch water line which
runs in/along Mason Street. There are existing stubs into the site; if these stubs are
of adequate size, they must be utilized. On the other hand, if it is found that these
stubs are not large enough to service the site and the proposed use, they will have
to be abandoned. Taps into these lines are subject to specific spacing
requirements, and fire water and domestic water taps must be separate. Water
conservation standards for landscaping and irrigation will apply. Plant Investment
and Water Acquisition Fees will be due at the time of building permit issuance.
There may be repay agreements on taps into the water and sewer lines serving this
site. For further information on water and sewer issues, please contact Roger
Buffington, 221-6681. For further information on plant investment fees and raw
water requirements, please contact Mary Young at Water and Wastewater Utility,
221-6681.
6. The property is zoned HB, Highway Business. As the proposed use is not
specifically allowed in this zone, the project must be processed as a Planned Unit
Development (P.U.D.), subject to the standards of the Land Development Guidance
System (LDGS), for consideration by the Planning and Zoning Board.
7. It will be necessary to include bicycle racks as part of the site plan. These racks
should be conveniently and safely located, permanently anchored to the ground, and
should not obstruct any walkways.
8. The twenty -foot drive lane on the north side of the proposed building would have to
be striped as a "Fire Lane" with no parking allowed. All turns must be designed such
that there is a minimum of a twenty foot (20') radius on the inside of the turn and a
forty (40') foot radius on the outside of the turn. The third story of the structure
would have to be equipped with an automatic fire suppression system (sprinklers).
The Poudre fire Authority would like there to be an addressable fire alarm system.
It would be necessary to provide a fire hydrant at either side (north or south) of the
Mason Street access. If you have any questions regarding the Poudre Fire
Authority's requirements or comments, please contact Roger Frasco at 221-6570.
9. Please provide recycling facilities/opportunities within the trash enclosures. Trash
enclosures must be visually screened from public view, as must all roof -top
mechanical equipment.
10. It will be necessary to provide handicap accessible parking spaces. Handicap
accessible routes of travel cannot have 'slopes exceeding ADA requirements.
Similarly, a minimum of one out of every seven rooms/units will have to be handicap
accessible. A 13-R system is allowable in guest rooms. For information regarding
these comments, please contact Sharon Getz at 221-6760.
11. The proposed land uses will be assessed a Street Oversizing Fee of $14,005 per
acre of developed land, payable at the time of building permit issuance. For further
information on an estimate of these fees, please contact Matt Baker, 221-6605.
IN
CONCEPTUAL REVIEW STAFF COMMENTS
MEETING DATE: April 29, 1996
ITEM: Ramada Suites Hotel on west side of Mason Street, at
Boardwalk Drive (Lots 1 and 2 of Garth Subdivision).
APPLICANT: Terence C. Hoaglund
Cityscape Urban Design, Inc.
3555 Stanford Road, Suite 105,
Fort Collins, CO 80525
LAND USE DATA: Request for a three-story, sixty-six room hotel on approximately
1.26 acres located on the west side of Mason Street at the
intersection of Boardwalk Drive. The hotel would share access
with the lot to the south (Lot 3). The roof of the building would
be pitched and would have an average height of forty-two (42')
feet with a peak height of forty-four (44') feet. The back/west
side of the lot borders the Colorado and Southern Railroad
right-of-way.
COMMENTS:
1. Electrical power will be supplied by City of Fort Collins Light and Power Utility which
has a conduit along/in Mason Street; all services must be underground.
Underground installation must be placed within an easement meeting the
specifications of the utility. Buildings must not encroach onto this easement.
2. The electrical transformer must be within eight feet of hard surface for emergency
change -out. The transformer must not be located by or visible from the adjoining
arterial street, Mason Street. The transformer must be screened by a solid
enclosure meeting the clearance specifications of the Utility or by landscape
materials. The location of the transformer will affect the development charges
associated with the project. You will need to complete a commercial (C-1) loading
form. Streetlight locations may need to be changed and, thus, will need to be
coordinated. For further information regarding electrical service, please contact
Doug Martine at 221-6700.
3. It was highly recommended that you make use of the lighting consultation services
offered by the Light and Power Department. The Department will review your
lighting needs, efficiency, design, and costs for no charge (free). For more
information regarding this service, please contact Jon McHugh at 221-6700.
COMMUNITY PLANNING &
ENVIRONMENTAL SERVICES 281 NORTH COLLEGE P.O.BOX 580 FORT COLLINS, COLORADO80522-0580 (303)221-6750
PLANNING DEPARTMENT
Comn ity Planning and Environment: ervices
Current Planning
City of Fort Collins
April 29, 1996
Terence C. Hoaglund
Cityscape Urban Design, Inc.
3555 Stanford Road, Suite 105
Fort Collins, CO 80525
Dear Mr. Hoaglund:
For your information, attached is a copy of the Staffs comments concerning Ramada
Suites Hotel on the west side of Mason at Boardwalk Drive (Lots 1 and 2 of Garth
Subdivision presented before the Conceptual Review Team on April 29, 1996.
The comments are offered informally by Staff to assist you in preparing the detailed
components of the project application. Modifications and additions to these comments
may be made at the time of formal review of this project.
If you should have any questions regarding these comments or the next steps in the
review process, please feel free to call me at 221-6750.
Sincerely,
Mitch Haas
City Planner
MH/gjd
cc: Eric Bracke, Streets Department
Stormwater Department
Project Planner
File
281 North College Avenue • P.O. Box 580 • Fort Collins, CO 80522-0580 • (970) 221-6750
FAX (970) 221-6378 • TDD (970) 224-6002