HomeMy WebLinkAboutLEVON'S MINOR SUBDIVISION - H-C SITE PLAN REVIEW - 19-96 - CORRESPONDENCE -8. The proposed grading plan shows off -site grading on the property to the south. Off -site
grading will require an off -site grading easement from adjacent property owners.
Response:
9. Please provide calculations to check the capacity of the 4' inlet along Hickory Street.
The inlet must be sized for off -site runoff on Hickory Street.
Response:
Please refer to the redlined report and plans for additional review comments.
2. Please provide copies of the off -site drainage easement and the temporary construction
easement for the outfall swale through Salyer Open Space.
Response:
3. Please show details of the outfall for the existing storm sewer under Hickory. The
expansion of Hickory is adding impervious area to this drainage outfall. Where does the
drainage go? Is there an existing easement for the outfall? Or, is an easement needed?
Response:
4. Please show off -site contours on the west side of the site. The flows from this off -site
basin must be calculated and must pass through the site like historical conditions. The 6'
wall is shown to block off -site flows. Blocking off -site flows is only acceptable, if a
drainage easement is provided from the property to the west.
Response:
5. Please specify that maintenance of the off -site channel will be the responsibility of the
property owner of the proposed site. The erosion control measures must also be
maintained until the swale is fully vegetated.
Response:
6. The proposed on -site channel must not be within the dedicated right-of-way for Fourth
Street. The channel could be piped under the right-of-way. A drainage easement must be
dedicated for the on -site swale.
Response:
7. The time of concentration for the site was calculated assuming overland flow for the
entire travel time. The proposed swale through the site causes the runoff to become
channelized with a much smaller travel time. Please recalculate the peak runoff from the
site considering channelized flow for the time of concentration calculations.
Response:
PROTECT
COMMENT SHEET
City of Fort Collins
Current Planning
DATE: ? 10 DEPT: Stormwater
PROJECT: #!�- JG L(fvon s 11'1i1)cW' 50,6 /v✓ . -CA — l(/. 6211-gP S A? P/,-,/l �Pu;0w
PLANNER: IA,�, lre
All comments musf6e received by:
❑ No Problems
Problems or Concerns (see below or attached)
A written response for each of the following comments must be submitted, with the
redlined plans and report, at time of project resubmittal. The responses must note any
revisions or clarifications completed in result of these comments. If responses are not
submitted with the resubmittal, the project will be returned to the applicant without further
review. This procedure will help the review process become more efficient and effective.
Thank you.
Note: Further discussion between Stormwater and the Natural Resources Dept. is needed
regarding the outfall Swale. We plan to meet with Natural Resources to confirm the
location, intent, operation, and maintenance of the swale that is proposed in the Salyer
Open Space. This meeting will take place within the next week. At that time, additional
comments may be provided regarding the swale.
1. The drainage from this development is proposed to outlet into the Josh Ames Canal.
Drainage into the abandoned canal will not be allowed. Drainage from this development
must be diverted directly to the Poudre River.
Response:
17
Date: Signature:
CHECK IF YOU WISH TO RECEIVE ❑ PLAT hd
COPIES OF REVISIONS ❑ SITE mi ke Gods, i5
❑ TL�A+NDSCAPE 5)1ru ,J u and E, 9 .
0 V 1U= ` 0105
Levon's Warehouse and office building - plan review (page 2 of 2) July 11, 1996
Sheet 2
4. The new RCP pipe for drainage needs to be extended so that it goes past the ROW.
5. Label the 10 foot concrete path along the west edge of the property.
6. The block wall needs to be entirely on this property.
7. A type III barricade needs to be placed across the sidewalk and new pavement at the east edge
of this property where the road is being widened out. Need to make sure this stays out of the
railroad property.
8. Hickory street x-section: Indicate the amount of additional paving that will be done (what is
the flowline to flowline dimension?), this should be the same as Hickory Street to the east.
Indicate the existing slope of the road where the tie in is to occur and what the new pavement
slope is to be.
Sheet 3
9. Show how the new flowline location is to meet existing grade. Looks like some grading/ fill
may be needed. In addition what is to be done where the sidewalk ends next to the concrete path,
this sidewalk will sit 6 inches higher than the flowline which appears to be higher than the adjacent
path.
10. Indicate what the driveway width is to be and the location of the drive from the property line.
PROJECT
COMMENT SHEET
City of Fort Collins
Current Planning
DATE: June 14, 1996 DEPT: Engineering - Ping
PROJECT: # 19-96 Levon's Minor Subdivision - North
College Site Plan Review
PLANNER: Mike Ludwig
All comments must be received by: June 28, 1996
Levon's Warehouse and office building - plan review July 11, 1996
Plat -
1. A nine foot utility easement should be provided along the Hickory street frontage.
2. Any easements needed for drainage should also be dedicated on this plat at this time.
Site Plan/ Landscape plan
1. Make sure the block wall remains entirely on your property.
2. The ivy to be planted on the west side of the block wall does not appear to be on this property.
Need permission from neighbor to plant on there property. In addition who is to maintain and
water these plants.
Utility plans
1. General note 1 should be modified to reference the Director of Engineering not the City
Engineer.
2.The last note under the general notes (number 1) says that this plan does not meet the
`customary 2% minimum standard' and that the developer is responsible for requesting a variance.
What does this apply to? Drainage, streets?
3. All off site easements are needed prior to going to the Planning and zoning board for approval
and /or the signing of the mylars.
(Continued on next pa e)
Date: / Signa m'
CHECK IF YOU WISH TO RECEIVE ❑ PLAT
COPIES OF REVISIONS ❑ SITE
❑ LANDSCAPE
0 UTILITY
Please provide a written response to each of the above stated comments with the submittal
of plan revisions. An administrative hearing will be scheduled with the Director of Planning
after each of the issues have been addressed/resolved.
Please contact me at 221-6206 if you have any questions or concerns related to these
comments. I would like to schedule a meeting with you as soon as possible, if necessary,
to discuss these comments.
Sincerely,
Michael Ludwig
Project Planner
xc: Sheri Wamhoff
Stormwater Utility
file/Project Planner
1! Please provide dimensions for the drive lane and typical parking stalls.
M. There should be a landscaped island at approximately the mid -point of the
row of parking stalls. Also, there should be a landscaped island at each end
of the row of parking stalls to provide separation from the trash enclosures.
This will prevent cars from hitting the enclosures.
On- The Building Envelope may need to be increased as no awnings or building
projections may extend outside of the building envelope.
o
An east/west sidewalk extension is needed from the entrance drive to the
building.
pe'� Please delete General Notes 3,5,6,7,8,9,10, and 11 from the Landscape
Plan as they have no relevance to this development request.
9 Please choose different symbols for Peking Cotoneaster, English Ivy, and
Gold Drop Potentella as they are difficult to differentiate on the Landscape
Plan.
Ir� Please label the species and diameter of any existing trees, etc. and
designate which are to remain and those which are to be removed.
S. Landscaping is needed along the eastern edge of the parking lot (shrubs
and trees).
t. Additional landscaping is needed along the north side of the proposed
building.
Please designate building materials and colors on the building elevations.
Additional architectural features are needed on the north elevation in
accordance with H-C Standard #19 which states: "No blank wall that faces
a public street shall exceed 50 feet in length.'
Additional architectural features may be needed along the west elevation.
l/ Please discuss this with the Current Planning staff.
Please provide elevations of the proposed trash dumpsters.
This completes the review comments at this time. Additional comments may be
forthcoming as the various departments and reviewing agencies continue to review this
request.
b. Please add a note to the Landscape Plan which states: "AII shrubs must be
separated a minimum of4teet from all water and sewer mains and services."
There appear to be conflicts on the north side of the proposed building.
10. The Mapping Department requests that all easements be shown on the Plat.
11. Comments from the Engineering Department are attached.
12. Comments from the Stormwater Utility are attached.
13. The Current Planning Department offers the following comments:
a% Please label the Site Plan as "Sheet 1 of 3'; the Landscape Plan as "Sheet
2 of 3'; and the Building Elevations as "Sheet 3 of 3".
b,,,/ Please provide a scale and north arrow for the vicinity map on the Site Plan.
c. /The Site Statistics and General Notes should be moved to another location
on the Site Plan as they conflict with notes designating surrounding land
uses.
id. Please add a note to the Site Plan which states that "AII roof -top mechanical
equipment is to be fully screened from public view."
Oe In the "Site Statistics", please show provide a breakdown for the number of
square feet of the proposed building, parking and drives, and landscaped
area.
f / Please delete the "Site Statistic" which references developed gross density.
Density refers to residential development, not warehouse and office uses.
Please correct the spelling of the word "Collins" in General Note 1.
Please add a note to the Site Plan which states: "All trash dumpsters are to
be fully enclosed and gated. Enclosures are to be constructed with materials
and colors similar to the warehouse/office building."
Please delete General Note 5 and replace it with a note which states: "All
signage to comply with the City Sign Code."
Please delete General Note 6.
Please revise the existing Planning and Zoning Board Certification to state
"Planning Certification: Approved by the Director of Planning of the City of
Fort Collins, Coloorra'd�o on this day of , 1996."
d. The developer needs to coordinate a transformer location and development
charges with the Light and Power Engineering Department.
3. The Right -of -Way Agent requests that the City owned 20' strip be shown on the
plat as Parcel 2.
4. The Parks Department offers the following comments:
a. / The area adjacent to Legacy Park may receive overflow foot traffic and
equipment placement during the New West Festival.
b. Please prepare an easement request with legal description, etc. for any
necessary easement(s) needed from the City's Parks Department.
5. The Poudre Fire Authority offers the following comments:
a. This building exceeds five thousand (5,000) square feet and must be fire
contained or fire sprinklered. If fire containment is used, a fire access
roadway must be provided around the building with turning radii of 20 feet
inside, and 40 feet outside. The road must be constructed of road base or
better construction and maintained year around.
b. If the building is fully fire sprinklered, the access as shown will meet fire
department concerns.
C. A fire hydrant is required within 400 feet of the building capable of 1,000
gallons per minute at a residual of 20 pounds pressure. We recommend a
hydrant at the entrance to the property.
6. Public Service Company stated that a minimum 10 foot wide utility easement is
needed adjacent to the Hickory Street right-of-way or Fourth Street (south property
line).
7. The Pavement Management Division of the Engineering Department stated that
all projects initiated after April 12, 1996 shall follow the new Pavement Design and
Technical Criteria guidelines.
8. TCI of Fort Collins states that they have a cable running east/west on the south
side of Hickory Street.
9. The Water and Wastewater Utility offers the following comments:
a. Please add a note to the Landscape Plan which states: "All trees must be
separated a minimum of 10 feet from all water and sewer mains and
services."
Commt y Planning and Environmental ,rvices
Current Planning
City of Fort Collins
July 22, 1996
Charlie Meserlian
c/o Joe Marcisofsky
318 E. Oak Street
Structured Engineering
Fort Collins, CO 80524
Dear Joe,
Staff has reviewed your documents for the Levon's Warehouse and Office Building that
were submitted on June 24, 1996, and would like to offer the following comments:
1. The Building Inspections Department offers the following comments:
a. A minimum 6% of the interior of the parking lot must be landscaped. Please
refer to the Parking Lot Development Guide for further information.
tb. Please add a note to the landscape plan which states: "AII landscaping shall
be installed or secured with an irrevocable letter of credit, performance bond,
or escrow account for 125% of the valuation of the materials and installation
prior to the issuance of a Certificate of Occupancy."
C. 10 foot wide landscape strips are required along Hickory Street in front of the
paved driveway/parking. It is unclear what width is currently shown. Please
revise and/or clarify.
2. The Light and Power Utility offers the following comments:
a. An eight foot wide utility easement is needed along the north, south, and
west property lines.
b. There is an existing fiberglass electric vault near the northeast corner of the
site (not shown on the utility plan). If this vault needs to be relocated, or
have the grade adjusted, it will be at the developer's expense.
C. There will also be costs to the developer to relocate the overhead line to
underground in addition to normal electric development charges.