HomeMy WebLinkAbout2620 W. ELIZABETH ST., SINGLE-FAMILY DETACHED - PDP - PDP160037 - CORRESPONDENCE -line. Comment Number: 4 Comment Originated: 12/08/2016 12/08/2016: Please label size of existing water mains. Comment Number: 5 Comment Originated: 12/08/2016 12/08/2016: A thrust block is required for the water main connection in Elizabeth Street. Department: Zoning Contact: Ali van Deutekom, 970416-2743, avandeutekom@fcgov.com Topic: General Comment Number: 1 Comment Originated: 12/07/2016 12/07/2016: In addition to the 6,000 minimum lot square footage there is also a minimum lot width of 60 feet. Several of these lots are under 60 feet wide. On the corner lots which require a 15 foot side setback, 15 foot rear setback and 20 foot front setback you are left with a very restricted buildable area. Comment Number: 12 Comment Originated: 12/06/2016 12/06/2016: Please add bearings as marked. See redlines. Comment Number: 13 Comment Originated: 12/06/2016 12/06/2016: Please add angle breaks to the right of way lines to match the section line. See redlines. Comment Number: 14 Comment Originated: 12/06/2016 12/06/2016: Per a 11/29/16 phone call, please call John Von Nieda to discuss the pins in Detail A. See redlines. Topic: Site Plan Comment Number: 15 Comment Originated: 12/06/2016 12/06/2016: Please remove the address from the plans. With the project being replatted, the address could change. Comment Number: 16 Comment Originated: 12/06/2016 12/06/2016: Some of the sheet titles in the sheet index do not match the sheet titles on the noted sheets. See redlines. Comment Number: 17 Comment Originated: 12/06/2016 12/06/2016: Some of the easement descriptions shown are incorrect. If they are going to stay on the plan, they should match what is shown on the Subdivision Plat. Comment Number: 18 Comment Originated: 12/06/2016 12/06/2016: There is text that needs to be rotated 1800. See redlines. Comment Number: 19 Comment Originated: 12/06/2016 12/06/2016: Please revise the legal description to match the legal description on the Subdivision Plat. See redlines. Department: Water Conservation Contact: Eric Olson, 970-221-6704, eolson@fcgov.com Topic: General Comment Number: 1 Comment Originated: 11/29/2016 11/29/2016: Irrigation plans are required no later than at the time of building permit. The irrigation plans must comply with the provisions outlined in Section 3.2.1(J) of the Land Use Code. Direct questions concerning irrigation requirements to Eric Olson, at 221-6704 or eolson @fcgov.com Department: Water -Wastewater Engineering Contact: Wes Lamarque, 970-416-2418, waamargue@fcgov.com Topic: General Comment Number: 1 Comment Originated: 12/08/2016 12/08/2016: The main trunk of the new water main needs to be 8-inches in diameter. The water main serving lots 7 & 8 can remain 6 inches. Comment Number: 2 Comment Originated: 12/08/2016 12/08/2016: Please show all water and sewer services. Comment Number: 3 Comment Originated: 12/08/2016 12/08/2016: Please include water main restraint for the dead end fire hydrant 12/06/2016: There are text over text issues. See redlines. Comment Number: 29 12/06/2016: There are line over text issues. See redlines. Topic: Landscape Plans Comment Originated: 12/06/2016 Comment Number: 20 Comment Originated: 12/06/2016 12/06/2016: Please remove the address from the plans. With the project being replatted, the address could change. Topic: Lighting Plan Comment Number: 21 Comment Originated: 12/06/2016 12/06/2016: Please correct the project name in the title block. See redlines. Topic: Plat Comment Number: 1 Comment Originated: 12/06/2016 12/06/2016: There is plat language missing. See redlines. Comment Number: 2 Comment Originated: 12/06/2016 12/06/2016: Are there any Lienholders for this property? If so, please add a signature block. If not, please add a note stating there are none, and include response in written comments. Comment Number: 3 Comment Originated: 12/06/2016 12/06/2016: There are spelling issues. See redlines. Comment Number: 4 Comment Originated: 12/06/2016 12/06/2016: Please add title commitment information as available. Comment Number: 5 Comment Originated: 12/06/2016 12/06/2016: Please provide current acceptable monument records for the aliquot corners shown. These should be emailed directly to Jeff at jcounty@fcgov.com Comment Number: 6 Comment Originated: 12/06/2016 12/06/2016: Please label all surrounding properties with "Unplatted" or the subdivision name. This includes properties across right of ways. See redlines. Comment Number: 7 Comment Originated: 12/06/2016 12/06/2016: Please add Private Drive name. Comment Number: 8 Comment Originated: 12/06/2016 12/06/2016: Private Drive may need to be in a Tract. Please refer to comments by other departments. Comment Number: 9 Comment Originated: 12/06/2016 12/06/2016: The easements along Elizabeth self extinguish with dedication of right of way. See redlines. Comment Number: 10 Comment Originated: 12/06/2016 12/06/2016: Please explain why the found monuments were not accepted per Board Rule 6.5.4.1. See redlines. Comment Number: 11 Comment Originated: 12/06/2016 12/06/2016: Please add "See Note #6" to the labels as marked. See redlines. 12/08/2016: Please add detention pond and LID summary tables to the Drainage Plan. Comment Number: 9 Comment Originated: 12/08/2016 12/08/2016: The detention pond needs to meet the City's Detention Pond Landscape Standards. This includes more natural grading patterns. Comment Number: 10 Comment Originated: 12/08/2016 12/08/2016: Drainage easements are required for detention ponds, LID facilities, and conveyance elements for the 100-year storm. Department: Technical Services Contact: Jeff County, 970-221-6588, (county@fcgov.com Topic: Construction Drawings Comment Number: 22 Comment Originated: 12/06/2016 12/06/2016: Please provide the following information for the Benchmark Statement in the EXACT format shown below. PROJECT DATUM: NAVD88 BENCHMARK # w/ DESCRIPTION ELEVATION: BENCHMARK # w/ DESCRIPTION ELEVATION: PLEASE NOTE: THIS PLAN SET IS USING NAVD88 FOR A VERTICAL DATUM. SURROUNDING DEVELOPMENTS HAVE USED NGVD29 UNADJUSTED FOR THEIR VERTICAL DATUMS. IF NGVD29 UNADJUSTED DATUM IS REQUIRED FOR ANY PURPOSE, THE FOLLOWING EQUATION SHOULD BE USED: NGVD29 UNADJUSTED = NAVD88 - X.XX�. Comment Number: 23 Comment Originated: 12/06/2016 12/06/2016: Please remove the address from the plans. With the project being replatted, the address could change. Comment Number: 24 Comment Originated: 12/06/2016 12/06/2016: There are line over text issues. See redlines. Comment Number: 25 Comment Originated: 12/06/2016 12/06/2016: There is text that needs to be rotated 180°. See redlines. Comment Number: 26 Comment Originated: 12/06/2016 12/06/2016: There are cut off text issues. See redlines. Comment Number: 27 Comment Originated: 12/06/2016 12/06/2016: Some of the easement descriptions shown are incorrect. If they are going to stay on the plan, they should match what is shown on the Subdivision Plat. Comment Number: 28 Comment Originated: 12/06/2016 depth of at least 150' per Land Use Code section 3.6.2(G). Please submit a modification request to this standard. Comment Number: 2 Comment Originated: 12/02/2016 12/02/2016: You are not allowed to count portions of the lot encumbered by access easements/a private drive towards your minimum lot size as outlined in Land Use Code section 3.8.8(A). Due to this, none of the lots meet the minimum lot size in section 4.4(D)(1). You must get a modification to both of these standards to proceed with your current site plan. Staff will not support these modification requests. Department: Stormwater Engineering Contact: Jesse Schlam, 970-218-29329 ischiam@fcqov.com Topic: Erosion Control Comment Number: 1 Comment Originated: 11/23/2016 11/23/2016: Current Erosion Control Materials Submitted do not meet requirements. Please submit; an Erosion Control Plan (Based upon redlines), an Erosion Control Report (was not received in packet or was not submitted) , and an Escrow / Security Calculation (was not received in packet or was not submitted). Also, based upon the area of disturbance State permits for storm water will be required since the site is over an acre. If you need clarification concerning the erosion control section, or if there are any questions please contact Jesse Schlam 970-218-2932 or email @ jschlam@fcgov.com Contact: Wes Lamarque, 970-416-2418, wlamargue@fcqov.com Topic: General Comment Number: 2 Comment Originated: 12/08/2016 12/08/2016: The City's Low Impact Development standards are required for the development with 50% of the site's proposed impervious surface treated. Comment Number: 3 Comment Originated: 12/08/2016 12/08/2016: The City's water quality requirements are required for the development. Comment Number: 4 Comment Originated: 12/08/2016 12/08/2016: The limits of the proposed quantity detention must be in a tract within a drainage easement and not located on individual lots. Comment Number: 5 Comment Originated: 12/08/2016 12/08/2016: Lot drainage can not travel across more than 3 additional lots. The drainage conveyance must be in a tract & drainage easement. Comment Number: 6 Comment Originated: 12/08/2016 12/08/2016: The release rate for the detention pond is not the 2-year existing rate. Please revise. Comment Number: 7 Comment Originated: 12/08/2016 12/08/2016: Basin E1 does not get routed into the detention pond. This 100-year flows from this basin need to be subtracted from the release rate of the pond or routed into the pond. The overall release rate from the site needs to equal the 2-year existing flow. Comment Number: 8 Comment Originated: 12/08/2016 the design criteria already contained in relevant standards and policies, any new fire lane must meet the following general requirements: > Shall be designated on the plat as an Emergency Access Easement. > Maintain the required 20 foot minimum unobstructed width & 14 foot minimum overhead clearance. > Be designed as a flat, hard, all-weather driving surface capable of supporting 40 tons. > Dead-end fire access roads in excess of 150 feet in length shall be provided with an approved area for turning around fire apparatus. > The required turning radii of a fire apparatus access road shall be a minimum of 25 feet inside and 50 feet outside. Turning radii shall be detailed on submitted plans. > Be visible by painting and/or signage, and maintained unobstructed at all times. Sign locations or red curbing should be labeled and detailed on final plans. > Additional access requirements exist for buildings greater than 30' in height. Refer to Appendix D of the 2012 IFC or contact PFA for details. International Fire Code 503.2.3, 503.2.4, 503.2.5, 503.3, 503.4 and Appendix D; FCLUC 3.6.2(B)2006 and Local Amendments. Comment Number: 7 Comment Originated: 12/09/2016 12/09/2016: AUTOTURN EXHIBIT The fire marshal has requested that all projects provide turning templates to indicate fire apparatus movement along private drives and throughout Emergency Access Easements within the development site. This is particularly needed as proposed turning radii are described at less than 25' on the hammerhead. Comment Number: 8 Comment Originated: 12/09/2016 12/09/2016: FIRE LANE DEDICATION The proposed EAE is shown to be 28.75' wide while the width of the private drive is shown to be 30'. For clarity, the width of the EAE should be described as flow line to flow line (i.e. also 30' in width). On the other hand, if the intent of the project is to allow on -street parking in the area, further redesign will be required as parking cannot overlap with a dedicated fire lane. Department: Planning Services Contact: Clay Frickey, 970-224-6045, cfrickey@fcgov.com Topic: General Comment Number: 3 Comment Originated: 12/09/2016 12/09/2016: If you are looking to seek approval for the site plan submitted for first round of PDP, you will be required to seek modifications to the following standards. Staff would not support this group of modification requests: 3.6.2(G) - Lot depth along an arterial street 3.8.8(A) - Lots - Area and Dimension 4.4(D)(1) - Density (minimum lot size of 6,000 sq. ft. in the RL) 4.4(D)(2)(a) - Minimum lot width of 60' Topic: Site Plan Comment Number: 1 Comment Originated: 12/02/2016 12/02/2016: Lots with rear or front yard lines on arterial streets must have a lot roads shall be marked with permanent NO PARKING - FIRE LANE signs complying with Figure D103.6. Signs shall have a minimum dimension of 12 inches wide by 18 inches high and have red letters on a white reflective background. Signs shall be posted on one or both sides of the fire apparatus road as required by Section D103.6.1 or D103.6.2. Comment Number: 5 Comment Originated: 12/09/2016 12/09/2016: GATING As indicated in comment #1 above, should the "fire only" drive lane be required to have access control, an approved plan needs to be submitted for review and approval by the fire authority. Code language provided below. > IFC 503.6: The installation of security gates across a fire apparatus access road shall be approved by the fire chief. Where security gates are installed, they shall have an approved means of emergency operation. The security gates and the emergency operation shall be maintained operational at all times. > IFC D103.5: Gates securing fire apparatus access roads shall comply with all of the following criteria: 1. The minimum gate width for vehicle access shall be 20 feet. 2. Gates shall be of the swinging or sliding type. 3. Construction of gates shall be of materials that allow manual operation by one person. 4. Gate components shall be maintained in an operative condition at all times and replaced or repaired when defective. 5. Electric gates shall be equipped with a means of opening the gate by fire department personnel for emergency access. Emergency opening devices shall be approved by the fire code official. 6. Manual opening gates shall not be locked with an unapproved padlock, or chain and padlock, unless they are capable of being opened by means of forcible entry tools or when a key box containing the key(s) to the lock is installed at the gate location. 7. Gate design and locking device specifications shall be submitted for approval by the fire code official prior to installation. 8. Electric gate operators, where provided, shall be listed in accordance with UL 325. 9. Gates intended for automatic operation shall be designed, constructed and installed to comply with the requirements of ASTM F 2200. Comment Number: 6 Comment Originated: 12/09/2016 12/09/2016: "FIRE ONLY" ACCESS LANE TOW ELIZABETH > The fire access connection to W Elizabeth does not appear to meet minimum fire lane standards. Minimum turning radii is 25' and the plan describes an abrupt turn with a 7' radius. > The surface for the connection to W Elizabeth is required to be a hard surface. Compacted road base would require approval of the fire marshal. Fire lane standards provided below. > Roll over curb is allowable at the connection to W Elizabeth, however vertical curbing is not allowable and further discussion is required. FIRE LANE SPECIFICATIONS A fire lane plan shall be submitted for approval prior to installation. In addition to 12/07/2016: Comments from GIS: 1. Bartlett Dr has been added to the street name reservation list at larimer.org/streets 2. Pear St (Private Drive) should be marked on the subdivision plat in place of Drive A. Comment Number: 4 Comment Originated: 12/09/2016 12/09/2016: Comment from Comcast: Developer needs to open trench - rear lot. See image attached to the comment letter. Department: PFA Contact: Jim Lynxwiler, 970-416-2869, iynxwiler@goudre-fire.org Topic: General Comment Number: 1 Comment Originated: 11/21/2016 11/21/2016: FIRE ACCESS (NR) PFA will need to see a plan as to how the project team will keep the Emergency Access from Elizabeth open to emergency apparatus while simultaneously keeping it clear of private vehicles and obstructions. Comment Number: 2 Comment Originated: 12/09/2016 12/09/2016: WATER SUPPLY Relocation of the existing hydrant to the dead-end, private drive with hammerhead turnaround will dramatically delay access to water supply for the exiting homes on Pear St that are south of W Plum. The existing hydrant on the cul-de-sac will need to be relocated so as to remain available in it's current location. Comment Number: 3 Comment Originated: 12/09/2016 12/09/2016: STREET NAMING Where possible, the naming of private drives is typically recommended to aid in wayfinding. Addresses shall be posted on each structure and where otherwise needed to aid in wayfinding. If the street is not named, monument signage may be required to facilitate wayfinding. Code language provided below. > IFC 505.1: New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible, visible from the street or road fronting the property, and posted with a minimum of six-inch numerals on a contrasting background. Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure. Comment Number: 4 Comment Originated: 12/09/2016 12/09/2016: FIRE LANE SIGNS The limits of the fire lane shall be fully defined. Fire lane sign locations should be indicated on future plan sets. Signage will also be required at both entrances to the "fire only" drive lane. Code language provided below. > IFC D103.6: Where required by the fire code official, fire apparatus access Please adjust location to keep trees 4-5 feet off fence. Comment Number: 7 Comment Originated 12/07/2016: For street tree planting in front of lots, it doesn't appear feasible to place them in the parkway because of the proposed swale. In lieu of placing the trees in the parkway, please show canopy shade trees behind walk as directed in Land Use Code 3.2.1 2(b). It may be necessary to use an upright ornamental tree, such as Chanticleer Pear and Red Barron Crabapple, if the face of the building and sidewalk are too close. Explore locations of a suitable tree behind the walk. Department: Outside Agencies Contact: Clay Frickey, 970-224-6045, cfrickey@fcgov.com Topic: General Comment Number: 1 12/07/2016 Comment Originated: 12/02/2016 12/02/2016: Comment from Real Estate Services: "In reviewing the plat note 6 identifying the overlap it might be a good idea to add to the language in the note that the East line of the new plat of Elizabeth Street Farms is being revised by this plat to remove the overlap or some such language so it is clear in the language that the overlap is being corrected on the plat." Comment Number: 2 Comment Originated: 12/06/2016 12/06/2016: Comments from property owners that use the irrigation lateral on the north side of the property: 1. It is our understanding Bartlett Drive will be a private road and not be maintained or repaired by the City? Therefor, we are requesting a legal binding agreement be initiated prior to any development which clearly stipulates the HOA and/or all lot owners will be responsible for all expenses incurred by the lateral users, including any attorney fees, for any efforts to unplug and/or repair the lateral should problems arise. This agreement will be binding for as long a time period s the lateral is in use. 2. The concrete pipe used to line the lateral will be a minimum of 14 inches in all segments and sealed according to the same standards as stipulated for the City's storm sewers. 3. Three (3) "clean outs" be installed in the lateral; two spaced out from the existing west clean out and the third at the east boundary where the lateral exists the development. 4. We will be running water in the lateral from the first part of May until the end of September. Our use of the lateral cannot be interrupted or interfered with in any manner during this time period. We believe it may be beneficial for all parties involved to meet and discuss re -locating the lateral any potential problems which may become occur. Comment Number: 3 Comment Originated: 12/07/2016 Comment Number: 3 Comment Originated: 11/23/2016: It does not appear that the proposed street light fixture is offered in a "warm white" option (color temperature of 3000K or less). This fixture meets the City's standards as proposed. However, if a new fixture is selected at any point in the process, staff encourages the applicant to select a version with a warmer (lower) color temperature to reduce glare and light pollution. Department: Forestry Contact: Molly Roche, mroche@fcgov.com Topic: Landscape Plans Comment Number: 1 11 /23/2016 Comment Originated: 12/07/2016 12/07/2016: It appears that there are existing trees within the property lines. Please contact the City Forester for an onsite meeting to obtain tree inventory and mitigation information for landscape plans. Existing significant trees should be retained to the extent reasonably feasible. Comment Number: 2 Comment Originated: 12/07/2016 12/07/2016: Please use the City of Fort Collins General Landscape Notes, Street Tree Notes, and Tree Protection Notes. Also, please include the Tree Permit note in the bolded box on all landscape sheets. The Street Tree Notes and the Tree Permit box that are currently on the plans are not the right versions. The correct notes are available through the project planner or the City Forester. Comment Number: 3 Comment Originated: 12/07/2016 12/07/2016: Please confirm that the extension of Pear Street and Bartlett Drive will be private roads. Comment Number: 4 Comment Originated: 12/07/2016 12/07/2016: Street Tree Comments: Northern Red Oak is not expected to survive long-term in Fort Collins soils. Please replace with a species on the Fort Collins Street Tree list, such as Bur Oak. Arterial roads, such as Elizabeth St, are heavily treated with deicing salts. Lindens do not survive or thrive well under these conditions, so we typically do not recommend their placement in such proposed locations. Please replace with a species on the Fort Collins Street Tree list, such as Hackberry. Comment Number: 5 Comment Originated: 12/07/2016 12/07/2016: Will proposed street trees along Elizabeth be impacted by future widening of W. Elizabeth? It would be helpful to show sidewalk location to determine if trees will be impacted by future widening of the road. Please review tree placement with City of Fort Collins Transportation Planner, Amy Lewin. Comment Number: 6 Comment Originated: 12/07/2016 12/07/2016: The proposed street tree appear to be very close (3 feet) to the privacy fence. Comment Number: 5 Comment Originated: 12/06/2016 12/06/2016: A 15 foot utility easement will need to be dedicated behind the ROW along Elizabeth Street. Comment Number: 6 Comment Originated: 12/06/2016 12/06/2016: Elizabeth Street cross section on cover sheet will need to be updated to reflect WEETC plan cross section. Comment Number: 7 Comment Originated: 12/06/2016 12/06/2016: Residential private drive cross section on cover shows parking - this entire drive is within an emergency access easement and parking may not be permitted on the easement - work with PFA to determine if this is OK. Comment Number: 8 Comment Originated: 12/06/2016 12/06/2016: The WEETC plan shows a bus pullout adjacent to the property. Please coordinate with Transfort to determine bus pullout location and design. Comment Number: 9 Comment Originated: 12/06/2016 12/06/2016: The public street is not being continued; therefore, the driveway into the subdivision will need to be constructed as LCUASS 707.2 driveway standard — pedestrian ramps and concrete to the back of the walk. Comment Number: 10 Comment Originated: 12/06/2016 12/06/2016: Please add a spot for the ditch company to sign the plat/accept the ditch easement. Contact: Sheri Langenberger, 970-221-65739 slangenberger@fcgov.com Topic: General Comment Number: 1 Comment Originated: 11/18/2016 11/18/2016: The project owes an additional $516.25 for the PDP TDRFees. The acreage was not included in the fee calculation submitted. Department: Environmental Planning Contact: Rebecca Everette, 970-416-2625, reverette@fcqov.com Topic: General Comment Number: 1 Comment Originated: 11/23/2016 11/23/2016: Thank you for submitting an Ecological Characterization Study for this site. Per the ECS, the only significant natural features on the site are mature trees, which provide habitat for songbird and other avian species. An on -site meeting with the City Forester still needs to occur to determine mitigation requirements for the trees proposed to be removed. Please include Environmental Planning staff (Stephanie Blochowiak or myself) in that meeting. A tree mitigation plan should be included with the next submittal. For any native trees that will be removed (cottonwood and boxelder), please mitigate with other native tree species to account for the habitat value that will be lost. Comment Number: 2 Comment Originated: 11/23/2016 11/23/2016: Please include a water budget chart with the next submittal that identifies all hydrozones and total annual water use on the site, per LUC section 3.2.1(E)(3). Total annual water use should not exceed 15 gallons/square foot over the site, including all hydrozones used on the landscape plan. Fort Collins Community Development and Neighborhood Services 281 North College Avenue PO Box 580 Fort Collins, CO 80522 970.221.6750 970.224.6134 - fax fcgov. com/developmentre view December 09, 2016 Mike Walker TB GROUP 444 MOUNTAIN AVE Fort Collins, CO 80513 RE: 2620 W Elizabeth St - Single-family Detached, PDP160037, Round Number 1 Please see the following summary of comments from City staff and outside reviewing agencies for your submittal of the above referenced project. If you have questions about any comments, you may contact the individual commenter or direct your questions through the Project Planner, Clay Frickey, at 970-224-6045 or cfrickey@fcgov.com. Comment Summary: Department: Engineering Development Review Contact: Katie Andrews, 970-221-65015 kandrews@fcgov.com Topic: General Comment Number: 2 Comment Originated: 12/06/2016 12/06/2016: Section 3.8.8 (A) of the Land Use Code states: "No part of an area or dimension required for a lot to comply with the provisions of this code shall be included as an area or dimension required another lot, nor shall such required area or dimension be burdened by any easement for an abutting private street or private drive that provides access to the lot or to any other lot." This requirement may change the layout of the site and should be addressed as soon as possible. Comment Number: 3 Comment Originated: 12/06/2016 12/06/2016: Please review the 'West Elizabeth Enhanced Travel Corridor Plan" which was adopted in 10/16. The ultimate cross section in the plan (including detached walk) should be implemented with this development. Interim and ultimate striping plans should be included with development plans. Comment Number: 4 Comment Originated: 12/06/2016 12/06/2016: ROW will only need to be dedicated to the back of the ultimate sidewalk (ultimate cross section found in above referenced plan). The 30' noted on the PUD was back when the street was master -planned as a 4 lane arterial and is no longer planned as such.