HomeMy WebLinkAbout431 E. LAUREL STREET REPLAT (ROLLINS SUB.) - PDP - 30-10 - CORRESPONDENCE -Please note: There is a hydrant in the northwest corner of Laurel and Whedbee and the
southeast corner of Laurel and Whedbee.
2006 International Fire Code 508.1 and Appendix B
Number: 11 Created: 12/1 /2010
ADDRESS NUMERALS
Address numerals shall be visible from the street fronting the property, and posted with a
minimum six-inch high numerals on a contrasting background. (Bronze numerals on brown
brick are not acceptable). If the numerals are mounted on a side of the building other than
the side off of which it is addressed, the street name is required to be posted along with the
numerals.
PLEASE NOTE: The new residence shall be addressed off Whedbee Street.
2006 International Fire Code 505.1
Department: Technical Services
Topic: Subdivision Plat
Number: 1
[11/17/10] The boundary closes.
Issue Contact: Jeff County
Created: 11 /17/2010
Number: 2 Created: 11 /17/2010
(11/17/10] Please change the Subdivision title, to something other than an address. We
suggest "Rollins Subdivision".
Number: 3 Created: 11 /17/2010
[11/17/10] Please move the bearing & distance, as shown on the Subdivision Plat. See
redlines.
Number: 4 Created: 11/17/2010
[11/17/10] Please add Right of Way widths for streets, and alley information
Page 2
n
STAFF PROJECT REVIEW
City of Fort Collins
Date: 12/1 /2010
Staff has reviewed your submittal for 431 E. LAUREL STREET REPLAT PDP - TYPE I
(re:Galligan's Sub.), and we offer the following comments:
ISSUES:
Department: Engineering Issue Contact: Andrew Carney
Topic: General
Number: 7 Created: 11 /29/2010
[11/29/10] Since there is not one currently in place, a Development Agreement will need to
be exicuted with this replat. I have provided the Information for Development Agreement
sheet with this round of review and I will begin to draft a DA once it is returned.
Number: 8 Created: 11 /29/2010
[11/29/10] Please add the existing ROW widths for Laurel St, Whedbee St, and for the
alley.
Topic: Subdivision Plat
Number: 12 Created: 12/1/2010
[12/l/10] Please remove survey note #3. All recorded ROW and easements must be
shown on the plat regardless of clients wishes.
Department: Light & Power Issue Contact: Doug Martine
Topic: Light & Power
Number: 6 Created: 11 /18/2010
[11/18/10] This comment is to expand on and clarify the Conceptual Review minutes
relative to Light & Power. The electric development charges relative to front footage along
dedicated streets and to total square feet of property area are considered paid ONLY for the
lot #1 are considered paid. Full Light & Power development charges and system
modification charges will apply for lot #2. Please contact Light & Power Engineering with
any questions.
Department: PFA Issue Contact: Carie Dann
Topic: Fire
Number: 10 Created: 12/1 /2010
WATER SUPPLY
Fire hydrants, where required, must be the type approved by the water district having
jurisdiction and the Fire Department. Hydrant spacing and water flow must meet minimum
requirements based on type of occupancy. Minimum flow and spacing requirements include:
• Commercial and multi -family dwellings 1,500 gpm at 20 psi residual pressure, spaced
not further than 300 feet to the building, on 600-foot centers thereafter
•. Residential within Urban Growth Area, 1,000 gpm at 20 psi residual pressure, spaced
not further than 400 feet to the building, on 800-foot centers thereafter
• Residential outside Urban Growth Area, 500 gpm at 20 psi residual pressure, spaced
not further than 400 feet to the building, on 800-foot centers thereafter.
These requirements may be modified if buildings are equipped with automatic fire sprinkler
systems.