HomeMy WebLinkAboutFAITH FAMILY HOSPITALITY TRANSITIONAL HOUSE - PDP - PDP160044 - CORRESPONDENCE - REVISIONS01/04/2017: There is text that needs to be masked. Mask all text in hatched
areas. See redlines.
Response: All text masked. See sheet A1.1
Department: Water -Wastewater Engineering
Contact: Dan Mogen, 970-224-6192, dmogen@fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 12/30/2016
12/30/2016: It does not appear that there are any proposed changes to water
or sewer services. Please advise if this changes.
Response: Noted, this is correct.
Comment Number: 2 Comment Originated: 12/30/2016
12/30/2016: Has the sewer service(s) been located? There may not be
proposed changes; however, its location may have impacts on the proposed
pavers and dry well, and the service(s) need to be located.
It is likely that the service(s) tie to the sanitary main in the alley. There is a
manhole behind 321 and it is shown to be relatively shallow at 4.4' deep.
The TV report for this main shows a tap in the direction of this property 87.8' north of
the manhole. It also shows capped wyes at 4.6' and 83.1'.
It is also possible that the service(s) tie to the sanitary main in Sherwood. From
the manhole in front of these lots, the TV report shows there is a tap in the
direction of this property 50.4' north of the manhole.
Hopefully this information will be helpful in located the service(s); please let me
know if I can assist with any additional information.
If the existing service(s) are clay, it is recommended to update the service(s) to
PVC as a part of this project. This would replace the clay services that are
susceptible to more issues than PVC prior to the paving of the alley and
placement of the paver parking lot and save from potential future repairs that
would be made more difficult and costly by the addition of pavements.
If the service(s) are to be under the paver parking lot, it is worth considering
insulation in this area due to the shallow depth beneath the paver cross section.
Response: A 4" PVC sanitary sewer service was located and there is no conflict with the paver system.
See utility plan for location.
Department: Zoning
Contact: Ryan Boehle, 970-416-24019 rboehle@fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 12/30/2016
12/30/2016: One parking space needs to be designated for handicap use and
be designated as a van accessible space, and must be 8' wide and have an 8'
wide access aisle.
Response: Southeast parking stall updated to meet these standards. See sheet A1.1
Comment Number: 2 Comment Originated: 12/30/2016
12/30/2016: A trash enclosure needs to be designated on the drawings, and
be designed to allow a walk-in access separate from the main service gates.
Response: Trash enclosure coordinated with Gallegos Sanitation and shown on Site Plan, see sheet A1.1.
ELEVATION:
PLEASE NOTE: THIS PLAN SET IS USING NAVD88 FOR A VERTICAL
DATUM. SURROUNDING DEVELOPMENTS HAVE USED NGVD29
UNADJUSTED FOR THEIR VERTICAL DATUMS.
IF NGVD29 UNADJUSTED DATUM IS REQUIRED FOR ANY PURPOSE,
THE FOLLOWING EQUATION SHOULD BE USED: NGVD29 UNADJUSTED
= NAVD88 - X.XX'.
Response: The benchmark statement now matches the above format.
Comment Number: 10 Comment Originated:
01/04/2017: Please change the legal description as marked. See redlines.
Response: The legal description has been updated as marked.
Comment Number: 11 Comment Originated:
01/04/2017: All benchmark statements must match on all sheets.
Response: The benchmark statement now match on all sheets.
Comment Number: 12 Comment Originated:
01/04/2017: There are line over text issues. See redlines.
Response: Line over text issues have been resolved.
Comment Number: 13 Comment Originated:
01 /04/2017: There is text that needs to be masked. Mask all text in hatched
areas. See redlines.
Response: All applicable text has been masked.
Comment Number: 14 Comment Originated:
01/04/2017: The Horizontal Control Plan (Sheet 4 C2.0) is numbered
incorrectly.
Response: The Horizontal Control Plan is now labeled properly.
Comment Number: 15 Comment Originated:
01/04/2017: Please tie the coordinate values shown for utilities to the project
boundary. We would prefer that this be done by adding property corner values
to each sheet, or showing the property corner values on the horizontal control
plans and adding a note to each sheet with coordinate values.
Response: The coordinates of the property corners have been added.
01/04/2017
01/04/2017
01/04/2017
01/04/2017
01/04/2017
01/04/2017
Comment Number: 16
Comment Originated:
01/04/2017
01/04/2017: There are sheet numbering issues. See redlines.
Response: The sheet number issues have been resolved.
Topic: Landscape Plans
Comment Number: 4
Comment Originated:
01/04/2017
01/04/2017: There are line over text issues. See redlines.
Response: Line over text issues corrected. See sheet A1.2
Topic: Site Plan
Comment Number: 1
Comment Originated:
01/04/2017
01/04/2017: Please add a legal description for the project property.
Response: Legal description added, see sheet A1.1
Comment Number: 2
Comment Originated:
01/04/2017
01/04/2017: There are line over text issues. See redlines.
Response: Line over text issues corrected. See sheet A1.1
Comment Number: 3
Comment Originated:
01/04/2017
Response: This note was added to the requested sheets.
Comment Number: 6 Comment Originated: 12/23/2016
12/23/2016: In the Drainage Report, in the 2nd paragraph of I.B, discuss the
site's location within the City -regulated 100-year Old Town Basin floodplain.
Response: The site's location within the 100-year Old Town Basin floodplain has been discussed in the
drainage plan.
Comment Number: 7 Comment Originated: 12/23/2016
12/23/2016: In the Drainage Report, reference the FEMA FIRM Panel #, and
include a copy with the site highlighted or outlined.
Response: The FEMA FIRM Panel has been added to the drainage report.
Comment Number: 8
Comment Originated: 12/23/2016
12/23/2016: In the Drainage Report, describe the buildings location within the
floodplain, and its proposed use.
Response: The building location with the floodplain has been added to the drainage report.
Comment Number: 9 Comment Originated: 12/23/2016
12/23/2016: Please be reminded that if the existing buildings are remodeled, a
floodplain use permit will be required. If the cost of the remodel is equal to or
greater than 50% of the value of the existing structures (land costs are not
included in the valuation), the building will have to be brought into compliance
with the safety requirements of the City's floodplain regulations.
Response: Noted — this will be evaluated when cost of remodel is known.
Department: Technical Services
Contact: Jeff County, 970-221-6588, *county Cfcgov.com
Topic: Building Elevations
Comment Number: 5 Comment Originated: 01/04/2017
01/04/2017: There are text over text issues. See redlines.
Response: Text over text issues fixed. See sheets A5.1, A5.2, A5.3
Comment Number: 6 Comment Originated: 01/04/2017
01/04/2017: There are line over text issues. See redlines.
Response: Text over line issues fixed. See sheets A5.1, A5.2, A5.3.
Topic: Construction Drawings
Comment Number: 7 Comment Originated: 01/04/2017
01/04/2017: The titles need to match the other plan sets.
Response: The title is now consistent with the other plan sets.
Comment Number: 8 Comment Originated: 01/04/2017
01/04/2017: Some of the sheet titles in the sheet index do not match the sheet
titles on the noted sheets. See redlines.
Response: The sheet titles now match the sheet index.
Comment Number: 9
Comment Originated: 01/04/2017
01/04/2017: Please provide the following information for the Benchmark
Statement in the EXACT format shown below.
PROJECT DATUM: NAVD88
BENCHMARK # w/ DESCRIPTION
ELEVATION:
BENCHMARK # w/ DESCRIPTION
Magnolia and Olive. While it is relatively clear that runoff from the southern
portion of the alley is routed to Magnolia thru the proposed curb and gutter, it is
not clear what happens in the northern portion of the alley where the proposed
paving stops. It is important to show that runoff from this northern section is
properly routed and will not cause adverse impact to adjacent properties.
Response: Drainage calculations for the alley have been added to the rational method spreadsheets. See
Section IV of the drainage report for discussion on alley drainage and its effect on adjacent properties.
Contact: Jesse Schlam, 970-218-2932, 1schiam@fcgov.com
Topic: Erosion Control
Comment Number: 10 Comment Originated: 12/27/2016
12/27/2016: The site disturbs more than 10,000 sq. ft., therefore Erosion and
Sediment Control Materials need to be submitted for FDP. The erosion control
requirements are in the Stormwater Design Criteria under the Amendments of
Volume 3 Chapter 7 Section 1.3.3. Current Erosion Control Materials
Submitted do not meet requirements. Please submit; an Erosion Control Plan
(Based upon redlines), an Erosion Control Report (Based upon redline
comments), and an Escrow / Security Calculation (Not submitted). If you need
clarification concerning the erosion control section, or if there are any questions
please contact Jesse Schlam 970-218-2932 or email @ ischlam@fcgov.com
Response: The Erosion Control Plan and Report have been updated per comments.
Contact: Mark Taylor, 970-416-2494, mtaylor@fcgov.com
Topic: Floodplain
Comment Number: 1
Comment Originated: 12/23/2016
12/23/2016: On the Site Plan, show the floodway boundary and label the
floodway and the flood fringe.
Response: F000dway and flood fringe shown and labeled on site plan. See sheet Al
Comment Number: 2
Comment Originated: 12/23/2016
12/23/2016: On the Site Plan, add a note stating that Critical Facilities, as
defined in Section 10-16 of City Code, are prohibited.
Response: Note added. See sheet A1.1
Comment Number: 3
Comment Originated: 12/23/2016
12/23/2016: On Sheets C3.0, C4.0 and C5.0 of the Utility Plans, add a note
stating that a floodplain use permit will be required before beginning any
construction activities (remodel the existing building, driveways, sidewalks,
parking lot, utility work, landscaping, etc.) in the City -regulated 100-year
floodplain.
Response: This note was added to the requested sheets.
Comment Number: 4
Comment Originated: 12/23/2016
12/23/2016: On Sheets C3.0, C4.0 and C5.0 of the Utility Plans, add a note
stating that a no -rise certification will be required before beginning any work
(driveways, sidewalks, utility work, landscaping, etc.) in the City -regulated
100-year floodway.
Response: This note was added to the requested sheets.
Comment Number: 5
Comment Originated: 12/23/2016
12/23/2016: On Sheets C3.0, C4.0 and C5.0 of the Utility Plans, add a note
stating that storage of equipment and materials is not allowed within the
100-year floodway.
Comment Number: 10
Comment Originated: 01/03/2017
01 /03/2017: The following comments relate to changes/edits to project
drawings:
Response: See individual comments for responses.
Comment Number: 11 Comment Originated: 01/03/2017
01 /03/2017: Please provide a project data table on the site plan. See electronic
example of the types of information that should be presented on this drawing:
Response: Data table provided. See sheet A1.1
Comment Number: 12 Comment Originated: 01/03/2017
01/03/2017: Please add the standard City site plan and landscaping notes to
each respective drawing. An electronic copy of these notes will be emailed with
the final comment letter.
Response: City standard site plan and landscape plan notes added. See sheets A1.1 & A1.2
Comment Number: 13
Comment Originated: 01/03/2017
01/03/2017: On the site plan, please dimension and label the following dimensions:
- Setback from the front property line to the closest point on the building or front
porch.
- Setback from the alley to the nearest parking stall.
- Side setbacks from side property lines to the nearest building walls.
- Width of the two front driveways and the southern walkway leading to the
primary front entrance.
Response: Dimensions added. See sheet A1.1
Comment Number: 14
Comment Originated: 01/03/2017
01/03/2017: Please update the landscape plan to include the information from
the on -site tree audit with the City foresters. Please label each tree (or number
with a corresponding table) the species, size, condition, and mitigation value for
each tree, and that each tree will be protected in place.
Response: Information from on -site tree audit added to Landscape Plan. See sheet A1.2
Comment Number: 16
Comment Originated: 01/03/2017
01/03/2017: Add a note/arrow on the site plan that the alley from the northern
property line to Magnolia Street is to be paved as part of the project.
Response: Note / arrow added to site plan. See sheet A1.1
Department: Stormwater Engineering
Contact: Dan Mogen, 970-224-6192, dmogen@fcqov.com
Topic: General
Comment Number: 11
Comment Originated: 12/30/2016
12/30/2016: Please see redlined plans and drainage report.
Response: The redlines from the Utility Plan and drainage report have been Addressed.
Comment Number: 12 Comment Originated: 12/30/2016
12/30/2016: For final, the depth required to reach well -draining soils will need
to be specified for the dry well.
Response: The dry well is to be 8' deep due to the well -draining soils being below the water table. The
infiltration calculations in Appendix B were based on an 3/10/17 email from Soilogic (attached).
Comment Number: 13 Comment Originated: 01/05/2017
01/05/2017: Please document the change in runoff due to the proposed alley
paving and provide discussion of how runoff from the alley will reach either
Comment Number: 4 Comment Originated: 01/03/2017
01/03/2017: For the modification request relating to group home maximum
number of residents and separation requirements, please specify an exact
number of maximum residents (excluding supervisors/staff). For the group home
separation distance, please provide any information on the name of the other
nearby group home, its number of residents, and the population served. Part of
staff6s analysis of the modification request will likely include if/how the types of
group home residents and services differ, their on -site or nearby management
services and practices, and the recent history of the two sites6 concurrent
operation.
Response: See modification request for this detailed information (information within floor area modification)
Comment Number: 5 Comment Originated: 01/03/2017
01/03/2017: Although there is no bike parking requirement for group homes,
what is your experience with families and bike usage? Does it make sense to
provide indoor or outdoor bike storage space for residents?
Response: Enclosed bike storage will be provided in existing shed on -site.
Comment Number: 6 Comment Originated: 01/03/2017
01/03/2017: Information should be provided on the maximum number of adult
driving residents per family. Parking rates are determined by the number of
on -site employees or managers, and the number of driving adults. Its likely the
6-8 spaces currently shown meet this requirement, but we will need to verify
once the number of driving adults is known.
Response: This is addressed in the modification request. There are seven families with 50% of guests
having vehicles, requiring 4 parking spaces for guests and one for resident manager for total of 5. 8
parking stalls have been provided.
Comment Number: 7 Comment Originated: 01/03/2017
01/03/2017: One parking space must be designated for handicap use. This stall
dimension must be a minimum of 13-feet wide and marked with a sign. Given
the necessary stall dimensions and need to provide a space as close as
possible to accessible entrances, it likely makes the most sense to designate
the southeast driveway as the handicap parking spot.
Response: Southeast parking space designated and sized for ADA parking. See Sheet A1.1
Comment Number: 8 Comment Originated: 01/03/2017
01/03/2017: If the rear parking area remains its current size of 6 spaces or
more, a rear setback of 5-feet from the alley is required. Adjustments will also
be needed to meet parking lot perimeter screening. Landscaping should be
placed in front of each stall for its full length to help block headlights and within
the 5-foot setback area between the alley and parking stalls.
Response: 5'-0" setback provided. Landscaping added to bring design into compliance.
See sheets A1.1 & A1.2
Comment Number: 9 Comment Originated: 01/03/2017
01 /03/2017: Repeat comment with Environmental Planning: Identify on the site
plan the location of any existing outdoor lighting or any newly -proposed lighting.
If new lighting or light fixtures are proposed, we will need catalog cut -sheets of
the light fixture details. All light fixtures must fully -shield the light source and be
down -directional.
Response: Existing lighting locations identified. No new lighting, only relocated due to existing fence
being moved 4'-0".
> IFC 507.5 and PFA Policy: Hydrants to provide 1,500 gpm at 20 psi residual
pressure, spaced not further than 300 feet to the building.
Response: Noted, the fire sprinkler system is existing, and the on -site use isn't changing.
Comment Number: 3
Comment Originated: 12/29/2016
12/29/2016: WAYFINDING
As previously indicated in prior conversations, it's critical that police, fire, and
ambulance personal are able to quickly and efficiently locate individuals in the
event of an emergency. With 7 families in residence, it's still unclear how this
problem will be mitigated. A plan will need to be submitted to PFA for review
and approval. This plan my include a system of wayfinding signs directing
personnel to the correct entrance or entrances, or it may include an operational
component involving on -site staff. In any event, the operational plan or means of
wayfinding will need to be dependable and consistent so as to be reliable for
any call to 911. Further details are required.
Response: Plan is being developed and will be submitted to PFA for review and approval.
Comment Number: 4
Comment Originated: 12/29/2016
12/29/2016: GATING
It's not clear if or how gating will control access to different parts of the facility
but should they be in the path of fire access, they may need to be fitted with an
approved lock, such as a Knox Padlock. Additional information is requested.
Response: The front of the building is accessible (no gates present). The gates in the backyard fence will
only have latches, not locks.
Department: Planning Services
Contact: Ryan Mounce, 970-224-6186, rmounce@fcqov.com
Topic: General
Comment Number: 1
Comment Originated: 01/03/2017
01/03/2017: Please edit the modification request narrative for floor area to
include the specific requirement for maximum floor area permitted (7,600 sf on
a 19,000 lot), and the current size of the structure (listed as 8,974 sf on the
application).
Response: Modification request edited to reflect this.
Comment Number: 2 Comment Originated: 01/03/2017
01/03/2017: Verify what amount of the building square footage falls on the rear
half of the lot so the rear lot floor area ratio can be found. There is a Land Use
Code requirement that would limit the size of a new structure to 33% of the size
of the rear half of the lot, or 3,135 sf. If the existing building exceeds this size on
the rear half, a separate modification request for this standard must also be
submitted.
Response: The rear lot floor area ration is acceptable, no modification request required.
See chart sheet A1.1 for Rear Lot FAR
Comment Number: 3
Comment Originated: 01/03/2017
01/03/2017: Verify the height of the building walls and eaves at their closest
points to the side lot lines. This information is needed to determine if a
modification is required for maximum wall height at the side lot setbacks. If the
existing building is located at the 5-foot side yard setback, the maximum
building height is limited to 18-ft in height.
Response: A very limited area encroaches on the maximum wall height at the side lot setback.
This information will be included in the modification request.
Response: The sidewalk chase is to be reconstructed using Fort Collins Detail D-1013.
Department: Light And Power
Contact: Tyler Siegmund, 970-416-2772, tsiegmund@fc-qov.com
Topic: General
Comment Number: 1
Comment Originated: 01/03/2017
01/03/2017: If the applicant anticipates any changes to the existing electric
services then electric development and system modification charges may apply.
Please contact Light and Power Engineering if changes are anticipated.
Response: Noted
Comment Number: 2 Comment Originated: 01/03/2017
01/03/2017: Please contact Tyler Siegmund at Light & Power Engineering if
you have any questions at 970.416.2772. Please reference our policies,
construction practices, development charge processes, and use our fee
estimator at http://www.fcgov,com/utilities/business/builders-and-developers
Response: Noted
Department: Outside Agencies
Contact: Ryan Mounce, 970-224-6186, rmounce@fcqov.com
Topic: General
Comment Number: 1
Comment Originated: 01/03/2017
01/03/2017: Note from Don Kapperman, Comcast, 970-567-0245:
Applicant will need to place 2" conduit from house out to Comcast pedestal for
service (see attachment).
Response: A note has been added to sheet C2.0 to place 2" conduit for telephone service.
Department: PFA
Contact: Jim Lynxwiler, 970-416-2869, jlynxwiler@poudre-fire.org
Topic: General
Comment Number: 1 Comment Originated: 12/29/2016
12/29/2016: GENERAL FIRE ACCESS
Perimeter fire access is required to within 150ft of all exterior portions of the
facility. Perimeter access is lacking by approximately 100ft; however, as it is
equipped with a fire sprinkler system and sprinkler heads are being upgraded
to a quick reaction type, the out of access condition is considered acceptable.
Please note: A two inch copper fire line is noted on the plans. Fire supply lines
are typically 4" or 6" and hydraulic calculations will need to support the 2" line.
Please contact Assistant Fire Marshal, Joe Jaramillo with any fire sprinkler
related questions at 970-416-2868.
Response: Noted, the fire sprinkler system is existing, and the on -site use isn't changing.
Comment Number: 2
Comment Originated: 12/29/2016
12/29/2016: WATER SUPPLY
There are hydrants to the north and south of the facility on Sherwood meeting
minimum hydrant location requirements, however it is unknown if those meet
required flow specifications. It's the responsibility of the applicant to verify
volume and pressure. Code Language provided below:
city engineers. Per 2/23/17 email from Mark Ragasa (attached). The roll-over curb now matches LCUASS
Detail 702
Comment Number: 11
Comment Originated: 01/03/2017
01/03/2017: How will the proposed alley flowline tie into the existing flowline in
South Sherwood Street? Will the new driveway be reconstructed?
Response: The access to the alley will be reconstructed to match the flowline of the alley.
Department: Environmental Planning
Contact: Rebecca Everette, 970-416-2625, rverette@fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 12/28/2016
12/28/2016: Please add all relevant standard notes to the site and landscape
plans. City of Fort Collins standard notes can be found here:
http://www.fcgov.com/developmentreview/pdf/C FC-Standard-Notes. pdf
In particular, please add the Site Plan Notes, Tree Protection Notes, General
Landscape Notes, and Floodplain and Floodway Notes.
Response: All relevant standard notes have been added to the site and landscape plans. See sheets
A1.1 & A1.2.
Comment Number: 2 Comment Originated: 12/28/2016
12/28/2016: Please add the following note to the site plan, horizontal control
plan, grading plan, and drainage and erosion control plan: "All existing trees to be protected in place."
Response: Note added to site plan. See sheet A1.1, C2.0, C3.0, and C4.0.
Comment Number: 3
Comment Originated: 12/28/2016
12/28/2016: Is any new exterior lighting proposed as part of this project? If so,
please provide a photometric plan and manufacturer cut sheets for all proposed
light fixtures. Staff recommends LED light fixtures with a color temperature of
3000 degrees Kelvin or less, and light fixtures must be full -cutoff and
down -directional.
Response: No new lighting proposed. Existing lighting on a current fence will be relocated to new fence
approx.. 4'-6" away.
Department: Forestry
Contact: Molly Roche, , mroche@fcqov.com
Topic: Landscape Plans
Comment Number: 1
Comment Originated: 01/05/2017
01 /04/2017:
Please include Tree Inventory information (species, size, and condition) on the
Landscape Plans.
Response: Tree Inventory information provided. See sheet A1.2.
Department: Internal Services
Contact: Ryan Mounce, 970-224-6186, rmounce@fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 01/03/2017
01/03/2017: Comment from Clint Wood, Streets, 970-416-2173:
Repair existing sidewalk chase and curb to LCUASS standards (NE corner of
parcel #2).
to overhang into the public ROW. If this is needed for parking numbers, the
driveway will need to be expanded. If it will not be used, the driveway will need
to be removed.
Response: The existing parking spot in the northeast corner is to be expanded and the access to remain.
Comment Number: 4 Comment Originated: 01/03/2017
01/03/2017: Setback requirements for public alleys will need to be a minimum
of 3' from the ROW. It appears that the first parking setback is less than 3'.
Please adjust the parking lot design to meet this minimum setback requirement.
Response: The parking lot design has been modified. See sheet A1.1 & civil drawings for new parking lot
layout.
Comment Number: 5 Comment Originated: 01/03/2017
01/03/2017: Per the Land Use Code, all overhead utilities must be undergrounded. If this can't be done, a
modification of standard is needed and utility conduits will need to be provided.
Response: The existing overhead utilities appear to be already undergrounded, if not the overhead utilities
will need to be undergrounded. Per 3/15/17 email from Mark Ragasa (attached) if the utilities are already
undergrounded no other actions are required.
Comment Number: 6 Comment Originated: 01/03/2017
01/03/2017: Please label all ROW lines clearly.
Response: All ROW lines have been clearly label on the Site and Utility Plans.
Comment Number: 7 Comment Originated: 01/03/2017
01/03/2017: The existing sidewalk chase along South Sherwood Street
currently does not meet City standards. This sidewalk chase may need to be
replaced to meet standards.
Response: The sidewalk chase is to be reconstructed using Fort Collins Detail D-10B.
Comment Number: 8 Comment Originated: 01/03/2017
01/03/2017: Please provide spot elevations at the dry well, the swale and the
chase to ensure that drainage is being adequately conveyed.
Response: Spot elevations have been added to the dry well, swale, and chase.
Comment Number: 9 Comment Originated: 01/03/2017
01/03/2017: Please work with Stormwater to determine what the requirements
will be for the proposed drywell. This may need to be within a drainage
easement.
Response: Per Dan Mogen at the comment review meeting, a drainage easement will not be needed for
the proposed drywell.
Comment Number: 10 Comment Originated: 01/03/2017
01/03/2017: The alley design will need more work. Minimum flowlines are
0.5%. Minimum cross slopes are 2%. The rollover cur b and gutter that needs to
be used is LCUASS Detail 702. The alley should be designed to accommodate
a 20' cross section from back of curb to back of curb (concrete border).
Currently only a 15' cross section is being proposed.
Response: The alley design has been updated with a minimum flowline slope of 0.5%, a minimum
cross -slope of 1.5%, and a cross section of 19'. The variances from the comment have been approved by
Fort Collins
Community Development and
Neighborhood Services
281 North College Avenue
PO Box 580
Fort Collins, CO 80522
970.221.6750
970.224.6134 - fax
fcgov. com/developmentreview
January 26, 2017
Annette Zacharias
FAITH FAMILY HOSPITALITY
300 E OAK ST
Fort Collins, CO 80524
RE: Faith Family Hospitality Transitional House, PDP160044, Round Number 1
Please see the following summary of comments from City staff and outside reviewing
agencies for your submittal of the above referenced project. If you have questions about
any comments, you may contact the individual commenter or direct your questions through
the Project Planner, Ryan Mounce, at 970-224-6186 or rmounce@fcgov.com.
Comment Summary:
Department: Engineering Development Review
Contact: Marc Ragasa, 970.221.6603, mragasa@fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 01/03/2017
01/03/2017: Please refer to redlines for various Utility Plan comments and
cleanup.
Response: The redlines from the Utility Plan have been addressed.
Comment Number: 2
Comment Originated: 01/03/2017
01/03/2017: Will the project be proposing to replat the property? This project is
responsible for dedicating the required easements needed for this site. A 9'
Utility Easement along South Sherwood Street and an 8' Utility Easement along
the alley are required. Also, plans show a fire service crossing lot lines. A utility
easement is needed for this to occur.
Response: The property will not be replated. A 9' Utility Easement along South Sherwood Street and an
8" Utility Easement along the alley will be dedicated per separate document. A utility easement will also be
dedicated for the fire service line crossing the property line. (See attached legal descriptions.)
Comment Number: 3 Comment Originated: 01/03/2017
01/03/2017: Will vehicles be using the existing driveway at the northeast
portion of the project? Currently a driveway exists, however the existing
driveway isn't deep enough. Vehicles parked within that paved service appear