Loading...
HomeMy WebLinkAboutMANSION PARK - PDP - 24-00B - CORRESPONDENCE - CITY STAFF (4)Troy_ Jones Mansion Park Page 1 From: Monica Moore To: Troy Jones Date: 11/6/02 7:36AM Subject: Mansion Park Troy - I show that you are going to be discussing Mansion Park this morning at your staff review. Unfortunately, have a prior committment and will not be able to make it. One major point to make note of is that they will have to coordinate early on the electric layout for this project. We will require electric facilities, including transformer and meter locations to be shown on the overall utility plan. Also they had talked about wanting to Master Meter each of the mulitfamily buildings. This is NOT something the utility permits. One of the other discussions we have had with Sear Brown regarding this project is joint trench with gas. We did a pilot project of this in several developments and found this to be not only an installation and maintenance nightmare, but more importantly it was shown to be a safety issue for our crews. As such, this practice has been discontinued. Finally, their landscape plan does not show street trees adhering to minimum distances from streetlights. These are pretty much all the comments I have at this point. Thanks again. Monica Moore Electric Utility Project Manager