HomeMy WebLinkAboutPVH MEDICAL OFFICE BUILDING & PARKING STRUCTURE - PDP - 14-07 - CORRESPONDENCE -Comments from Current Planning:
1. As we discussed, be sure that exiting vehicles have a clear sight line of
pedestrians on the sidewalk. These walks should swing as far away from the
edge of the parking structure as possible. Landscaping, raised planters, seat
walls and the like should be placed on either side of the exit lanes to keep
pedestrians from hugging the wall and thereby not becoming visible for exiting
vehicles. I will provide draft regulations that will soon be incorporated into the
Land Use Code for projects located in the Transit Oriented Development
Overlay District under separate cover.
2. Will all 15 handicap parking spaces be located on the ground floor level? Or,
will they be distributed throughout all four levels? Please indicate how these
spaces will be distributed.
3. Please indicate where on the ground floor level the bicycle parking will be
located.
4. For the M.O.B., please consider adding more bicycle parking.
5. Please add a greater variety of plant material to the north edge of the parking
structure.
6. Along the south property line of the M.O.B., a privacy fence is needed to
screen the parking lot.
7. Staff remains concerned about the quality of the pedestrian experience along
the public streets at the edge of the parking garage. The architectural
elevations indicate that there will be "custom metal security screen." Please
provide more detail or a sample of this material. We hope that security can
be achieved without sacrificing an active and interesting pedestrian
environment. Walking along a long blank wall is dispiriting and will
discourage pedestrian activity.
8. Regarding the M.O.B., Staff is concerned about introducing the "cement
board panel' on portions of the upper level. This material appears inferior to
the materials used on the balance of the structure. Although the fourth level
is stepped back, it will still be visible. Quality materials should be used
consistently for the full height of the building. (By way of background, both
Pine Street Lofts and the Larimer County Office Building have been criticized
for use of dissimilar and inferior materials on their upper levels.)
9. Please consider offering a view perspective from the nearest residential
property looking northeast to the south and west elevations of the parking
structure.
Page 8
Be sure and return all of your redlined plans when you re -submit.
If you have any questions regarding these issues or any other issues related to this
project, please feel free to call me at (970) 221-6750.
Sincerely,
Ted Shepard
Chief Planner
Page 9
Number: 53 Created: 6/15/2007
[6/15/07] City records indicate that the existing water service to 1045 Garfield is a f-
inch.
Number: 54 Created: 6/15/2007
[6/15/07] To the south of the M.O.B., it is indicated that there is an 8-inch stub going
north out of the existing MH. Is this based on field observation? (City records don't
show this stub.)
Department: Zoning Issue Contact: Peter Barnes
Topic: Zoning
Number: 1 Created: 5/22/2007
[5/22/07] Parking lot lights along the south side of the surface parking lot for the
MOB should have backside, drop down shields
Number: 2 Created: 5/22/2007
[5/22/07] Building distances are shown to curb or sidewalk. Show the distances
from building to property lines also.
Number: 3 Created: 5/22/2007
[5/22/07] Since the parking structure stalls are all sized for employee parking rather
than general parking, Adequate signage will have to be placed at the entrances and
throughout the structure indicating that parking is for employees only. Indicate this
on plan.
Number: 4 Created: 5/22/2007
[5/22/07] A 6' high solid fence is required along the south lot line of the MOB parking
lot.
Number: 5 Created: 5/22/2007
[5/22/07] 10% of the interior of the MOB parking lot must be landscape islands.
What is the percentage? There is a 10' wide area in the MOB lot with the handicap
spaces on both sides of this area. Is this 10' wide area to be landscaped. The plan
doesn't indicate what the surface of this strip is.
Number: 6 Created: 5/22/2007
[5/22/07] Landscape plan needs a specific landscape legend, not a "representative
plant list", and plan needs to indicate what is being planted.
Number: 7 Created: 5/22/2007
[5/22/07] Is there going to be a trash enclosure for the MOB? If so, show location
on site plan and detail of materials.
Page 7
Department: Stormwater-Water-Wastewaterlssue Contact: Wes Lamarque
Topic: Stormwater
Number: 43 Created: 6/14/2007
[6/14/07] City Stormwater staff can not support the variance to quantity detention at
this time. Please look into several detention alternatives as well as any other
reasoning to not providing detention and please schedule a meeting with us to
discuss.
Number: 44 Created: 6/14/2007
[6/14/07] Please provide a drainage easement for the water quality swale around
the parking structure and for the stormceptor.
Number: 45 Created: 6/14/2007
[6/14/07] Please provide documentation on the stormceptor so City staff can
determine the level of water quality mitigation that is being achieved and if it will be
acceptable.
Number: 46 Created: 6/15/2007
[6/15/07] Please see other comments on the redlined plans and report.
Department: Stormwater-Water-Wastewaterlssue Contact: Roger Buffington
Topic: Water/Wastewater
Number: 47 Created: 6/15/2007
[6/15/07] Use tapping saddles for new fire line/fire hydrant connections to existing
water mains
Number: 48 Created: 6/15/2007
[6/15/07] Place meter pits within 2 feet of curb stops (see standard details).
Number: 49 Created: 6/15/2007
[6/15/07] On the parking garage, explain the uses of the domestic water/sewer
connections.
Number: 50 Created: 6/15/2007
[6/15/07] At Doctor's Lane, the valve shown on the west side of the 12-inch main is
a valve for the irrigation service. From that location, the irrigation service jogs to the
north and back to the west where it connects to the curb stop/meter pit.
Number: 51 Created: 6/15/2007
[6/15/07] Add water/sewer service details to the parking structure plans.
Number: 52 Created: 6/15/2007
[6/15/07] On south side of Garfield, a water line stub is shown at the existing drive.
If not used, this stub must be abandoned at the main.
Page 6
Number: 35 Created: 6/13/2007
[6/13/071 The Site and Landscape Plans shall reflect all revisions to sidewalks,
ramps, bus pads, easements etc... as requested on the Utility Plan redlines.
Number: 36 Created: 6/13/2007
[6/13/071 The Landscape Plan shall clearly indicate all trees to be removed and
protected along Garfield and Lemay and should match the information being shown
on the Demolition Plan prepared by Stantec.
Topic: Technical Services
Number: 37 Created: 6/13/2007
[6/13/07] Please correct a typo in the curve data on the Plat. The title in ownership
statement is incorrect.
Number: 38 Created: 6/13/2007
[6/13/07] The outer boundary needs to exclude Garfield Street. Show how Garfield
was dedicated (can't dedicate what already exists)
Number: 39 Created: 6/13/2007
[6/13/07] Text over line issues - see redlines for clarification.
Number: 40 Created: 6/13/2007
[6/13/07] Please hatch or hi -light the new ROW dedication area on the Plat.
Number: 41 Created: 6/13/2007
[6/13/07] Show the dimension for the utility easement on Lot 1 and label on Lot 2.
Department: PFA Issue Contact: Carle Dann
Topic: Fire
Number: 42 Created: 6/13/2007
[6/13/071 PFA has no comments or concerns at this time.
Department: Traffic Operations Issue Contact: Ward Stanford
Topic: Traffic
Number: 55 Created: 6/15/2007
There's significant northbound left turn increases at Lemay/Garfield, Lemay/Doctors.
Reviewing the Synchro queue depths at these locations leaves me lacking
confidence in Synchro's evaluation of those queue lengths, especially at Garfield.
Please provide an alternative analysis of the possible queues and available stacking
depth at these two locations.
Page 5
[6/13/07] NE: Sidewalk widening improvements are not being shown on Garfield.
The old monolithic curb, gutter and sidewalk along Garfield cannot be saw cut to
reconstruct a wider sidewalk. If the entire walk is to be reconstructed, new standard
vertical curb and gutter must also be reconstructed. Two options are available: Add
and additional 4 feet minimum of new concrete walk to the existing attached walk or
remove the existing curb, gutter and sidewalk and reconstruct with standard vertical
curb and gutter and new attached 6.5 foot attached sidewalk. The sidewalk may
taper and become narrower than 6.5 feet in locations where existing trees are to be
protected. Please clearly indicate these locations on the plan. Please consult with
Angie of BHA Design for further clarification.
Number: 28 Created: 6/13/2007
[6/13/07] NE: Please show ADA access across the access driveway off of Garfield
and call out standard ramps with LCUASS detail.
Number: 29 Created: 6/13/2007
[6/13/07] NE: Please label all public access, utility and drainage easements (or any
combination of) consistent with the Plat.
Number: 30 Created: 6/13/2007
[6/13/07] NE: The sidewalk along Lemay shall be detached where possible and a
minimum of 6 feet in width. The sidewalk may become attached only where existing
trees are to be protected and the attached portion shall be at least 8 feet in width.
Please clearly show this on the plans.
Number: 31 Created: 6/13/2007
[6/13/07] NE: The bus shelter pad will need to be reconstructed with the new
sidewalk. The dimensions of the pad shall meet the minimum requirements
provided with the redlines and a 6 foot sidewalk shall be located behind the shelter.
Number: 32 Created: 6/13/2007
[6/13/07] NE: Please show the limits of street cut needed to make the storm drain
connection on Lemay and provide the standard street cut note provided on the utility
plan sheet.
Number: 33 Created: 6/13/2007
[6/13/07] NE: It was my understanding from the conceptual review meeting that an
emergency access easement would be needed in the parking area for PFA access.
Please clarify with PFA and show the E.A.E. as needed. If needed it shall be
dedicated on the Plat prepared by Stantec.
Number: 34 Created: 6/13/2007
[6/13/07] NE: Please provide all LCUASS and applicable on -site standard details
with the final plan submittal. See redlines for additional comments related to drafting
and/or labeling.
Page 4
Two options are available: Add an additional 4 feet minimum of new concrete walk to
the existing attached walk or remove the existing curb, gutter and sidewalk and
reconstruct with standard vertical curb and gutter and new 6.5 foot attached
sidewalk. The sidewalk may taper and become narrower than 6.5 feet in locations
where existing trees are to be protected. Please clearly indicate these locations on
the plan.
Number: 20 Created: 6/13/2007
[6/13/07] Stantec: Please label and dimension the limits of ROW on Garfield Ave.
Show and label the limits of street cuts needed for utility connections and add the
standard street cut note provided to the applicable plan sheet.
Number: 21 Created: 6/13/2007
[6/13/07] Stantec: Please provide cross sections of the parkway, sidewalk and
street as indicated on the Grading Plan redlines. Perimeter drains may need to be
located with drainage easements. Please consult with the Stormwater Utility staff
reviewer for this project.
Number: 22 Created: 6/13/2007
[6/13/07] Stantec: If you decide to locate sidewalks within public access easements
rather than dedicating additional ROW, please clearly show and label these
easements on the Plat. Clearly indicate which easements are for public access,
utilities or drainage or any combination thereof.
Number: 23 Created: 6/13/2007
[6/13/07] Stantec: Garfield shall be shown as dedicated ROW on the Plat rather
than a part of the Plated property boundary. See redlines for clarification.
Number: 24 Created: 6/13/2007
[6/13/07] Stantec: A shared access easement is proposed to be re -dedicated for Lot
2 access off of Garfield. Half is being dedicated by this Plat but the off -site half must
be by separate document. Please submit the deed of dedication for this off -site
easement.
Number: 25 Created: 6/13/2007
[6/13/07] NE: Please update the month & year under the title with your next
submittal and provide contact info for all owners, developer and consultants on the
cover sheet.
Number: 26 Created: 6/13/2007
[6/13/07] NE: It appears there are a couple general notes that have been deleted.
Standard general notes should number to 48. Please review and add as needed.
List all variance requests for sidewalks and utility easement widths.
Number: 27
Created: 6/13/2007
Page 3
[6/13/07] Stantec: The easements shown on the Plat and Utility Plans need better
clarification. The labels are inconsistent and don't match. Please review all of the
proposed easements and identify if they are for utilities, public access or drainage or
a combination of the three. Make sure that easement widths and labeling are
consistent on all of the drawings and that they match the Plat.
Number: 14 Created: 6/13/2007
[6/13/07] Stantec: Please clearly show and label the proposed ROW limits
consistent with the legend. The City recommends that new ROW be dedicated to
cover all of the new proposed sidewalks rather than dedicating public access
easements. Governmental immunity to lawsuits does not apply to sidewalks within
public access easements and the property owner may be at risk to any lawsuits
related to the sidewalk area. The sidewalk may be located in a public access
easement but the plans show that small portions of the sidewalk extend outside of
the easement. All curb ramps, cross -walks, utility poles, traffic signal poles and bus
shelters need to be within dedicated ROW.
Number: 15 Created: 6/13/2007
[6/13/07] Stantec: Please provide standard directional ramps at the Doctors Lane
intersection. Call out with standard LCUASS detail.
Number: 16 Created: 6/13/2007
[6/13/07] Stantec: The right turn lane into the parking structure needs to be shown
with its own separate plan and profile that meets the LCUASS Appendix E design
requirements. Please provide a design plan and profile from the north property line
to the south end of the driveway entrance to the parking structure. The drainage
being shown does not meet LCUASS standards. Drainage from the street shall be
directed to the new curb and gutter rather than being conveyed to a flow line in the
street. Please show a 2 percent cross slope extending all the way to the gutter flow
line. A pan may be needed at the driveway to convey the water south and back to
the existing gutter to the south.
Number: 17 Created: 6/13/2007
[6/13/071 Stantec: Per the site meeting with BHA, additional concrete walk shall be
placed on the backside of the traffic signal poles on both sides of the intersection
such that pedestrians can walk behind the poles. See redlines for clarification or
consult with Angie from BHA Design.
Number: 18 Created: 6/13/2007
[6/13/07] Stantec: Where the sidewalk needs to attach to the street on Lemay, the
min. width shall be 8 feet. Detached portions shall be a min. of 6 feet.
Number: 19 Created: 6/13/2007
[6/13/07] Stantec: The old monolithic curb, gutter and sidewalk along Garfield
cannot be saw cut to reconstruct a wider sidewalk. If the entire walk is to be
reconstructed, new standard vertical curb and gutter must also be reconstructed.
Page 2
has
STAFF PROJECT REVIEW
City of Fort Collins
ANGELA MILEWSKI Date: 06/19/2007
BHA DESIGN, INC.
1603 OAKRIDGE DRIVE
FORT COLLINS, CO 80525
Staff has reviewed your submittal for PVH MEDICAL OFFICE BUILDING AND
PARKING STRUCTURE PDP - TYPE II, and we offer the following comments:
ISSUES:
Department: Engineering Issue Contact: Randy Maizland
Topic: Engineering
Number: 8 Created: 6/13/2007
[6/13/07] Because we have two separate designs from different engineering firms
for the MOB and the parking structure, all under one PDP submittal, we would like all
of the plans combined into one single Utility Plan set under a master cover sheet.
The titles on all of the plans shall match the title on the Plat. Sub -titles may be used
for each separate design if needed. This will ensure that all of the plans are filed
correctly in the same location at the City.
Number: 9 Created: 6/13/2007
[6/13/07] Note — all structural construction drawings for the proposed pedestrian
bridges shall also be included with the Utility Plan set and part of this approval.
Please submit bridge drawings as soon as possible for review and include a sight
distance profile from Elizabeth to Robertson to verify that the bridge over Lemay will
not obstruct the view of the traffic signals. Some additional bridge construction
requirements have been provided on the red -lines.
Number: 10 Created: 6/13/2007
[6/13/07] Stantec: Please update the month & year under the title with your next
submittal and provide contact info for all owners, developer and consultants on the
cover sheet.
Number: 11 Created: 6/13/2007
[6/13/07] Stantec: The demolition plan needs to accurately reflect which trees along
Lemay will be protected and/or removed. Please consult with Angie at BHA Design
regarding a recent site visit with the City to determine sidewalk locations and
conflicts with existing trees to be saved.
Number: 12 Created: 6/13/2007
[6/13/07] Stantec: An additional ramp and detached sidewalk should be provided on
Robertson just north of the entrance into the parking structure. Show how this will
tie into the existing walk on Robertson to the north.
Number: 13
Created: 6/13/2007