HomeMy WebLinkAboutPVH MEDICAL OFFICE BUILDING & PARKING STRUCTURE - PDP - 14-07 - CORRESPONDENCE - (4)Department: Stormwater-Water-Wastewater Issue Contact: Roger Buffington Topic: Water/Wastewater Number: 50 Created: 6/15/2007 [7/12/07] Delete the 12-inch main currently shown extending west from the main in Lemay. [6/15/07] At Doctor's Lane, the valve shown on the west side of the 12-inch main is a valve for the irrigation service. From that location, the irrigation service jogs to the north and back to the west where it connects to the curb stop/meter pit. Number: 51 Created: 6/15/2007 [7/12/07] Add the detail for the 2-inch meter pit which is being relocated for the irrigation service east of the parking garage. [6/15/07] Add water/sewer service details to the parking structure plans. Number: 54 Created: 6/15/2007 [7/12/07] Revise plan to show connection being made at MH. Include note to core drill opening in MH. [6/15/07] To the south of the M.O.B., it is indicated that there is an 8-inch stub going north out of the existing MH. Is this based on field observation? (City records don't show this stub.) Number: 61 Created: 7/12/2007 [7/12/07] Add notes requiring contractor to oordinate with Water Utilities regarding abandonment of water/sewer lines. (See redlines.) Number: 62 Created: 7/12/2007 [7/12/071 Add notes to remove the 1-inch curb stop and meter pit on the water service being abandoned. Number: 63 Created: 7/12/2007 [7/12/07] The 8-inch sewer in Robertson is VCP. The 6-inch service connection must be made by cutting a wye or tee into the sewer main. Add appropriate notes. Number: 64 Created: 7/12/2007 [7/12/07] Show the location of the sand/oil interceptor, and add standard detail. Page 3 [7/11/07] A letter of intent or signed deeds of dedication are needed for the access easement and temporary construction easement prior to scheduling a hearing. [6/13/07] Stantec: A shared access easement is proposed to be re -dedicated for Lot 2 access off of Garfield. Half is being dedicated by this Plat but the off -site half must be by separate document. Please submit the deed of dedication for this off -site easement. Number: 31 Created: 6/13/2007 [7/11/07] Please show additional dimensions around the bus shelter to verify Transit design guidelines are being met. [6/13/07] NE: The bus shelter pad will need to be reconstructed with the new sidewalk. The dimensions of the pad shall meet the minimum requirements provided with the redlines and a 6 foot sidewalk shall be located behind the shelter. Number: 57 Created: 7/11 /2007 [7/11/07] The title should be revised to reference the original PVH Plat. There are no existing plans titled PVH Lemay Campus West ... no Lemay Campus West to expand. See Technical Services comments. Number: 58 Created: 7/11 /2007 [7/11/07] The Plat and Pedestrian Bridge plans need to be added to the Utility Plan set and indicated on the cover sheet index. Number: 59 Created: 7/11 /2007 [7/11/07] See red -line comments regarding scannability issues (line over text, line weight etc... ) Topic: Engineering - Tech Services Number: 60 Created: 7/11 /2007 [7/11/07] Problem with name - there is no Lemay Campus west to expand on ? Department: Stormwater-Water-Wastewater Issue Contact: Wes Lamarque Topic: Stormwater Number: 56 Created: 7/10/2007 [7/10/07] Stormwater is ready for a hearing. Number: 65 Created: 7/13/2007 [7/13/07] Stantec: At final compliance, coordination needs to take place to determine the cross-section for the quantity and water quality detention swale to meet all storm water requirements and site needs. Number: 66 Created: 7/13/2007 [7/13/07] Stantec: Please revise the quantity detention calculations in the report. See redlines. Number: 67 Created: 7/13/2007 [7/13/071 Northern: The north -south drainage pan on the western edge of the site has a sump in it according to the spot elevations. Please revise to allow for positive drainage all the way to the new area inlet. Number: 68 [7/13/07] blank Created: 7/13/2007 Page 2 00 STAFF PROJECT REVIEW Citvof Fort Collins ANGELA MILEWSKI Date: 07/16/2007 BHA DESIGN, INC. 1603 OAKRIDGE DRIVE FORT COLLINS, CO 80525 Staff has reviewed your submittal for PVH MEDICAL OFFICE BUILDING AND PARKING STRUCTURE PDP - TYPE II, and we offer the following comments: ISSUES: Department: Engineering Issue Contact: Randy Maizland Topic: Engineering Number: 9 Created: 6/13/2007 [7/11/07] Ped bridge plans were not received until July 9th. Comments will be provided at a later date. No hearing shall be scheduled until a review of the pedestrian bridge plans has been completed. [6/13/07] Note — all structural construction drawings for the proposed pedestrian bridges shall also be included with the Utility Plan set and part of this approval. Please submit bridge drawings as soon as possible for review and include a sight distance profile from Elizabeth to Robertson to verify that the bridge over Lemay will not obstruct the view of the traffic signals. Some additional bridge construction requirements have been provided on the red- lines. Number: 15 Created: 6/13/2007 [7/11/07] The directional ramps are not adequately shown on the plans. Please clearly show the locations of the ramps and how they will line up with the crosswalks. [6/13/07] Stantec: Please provide standard directional ramps at the Doctors Lane intersection. Call out with standard LCUASS detail. Number: 16 Created: 6/13/2007 [7/11/07] Preliminary design appears to be acceptable. Additional elevation information and clarification is needed. Please see the red -line comments. Please provide at least one additional cross section at the center of the driveway. [6/13/071 Stantec: The right turn lane into the parking structure needs to be shown with its own separate plan and profile that meets the LCUASS Appendix E design requirements. Please provide a design plan and profile from the north property line to the south end of the driveway entrance to the parking structure. The drainage being shown does not meet LCUASS standards. Drainage from the street shall be directed to the new curb and gutter rather than being conveyed to a flow line in the street. Please show a 2 percent cross slope extending all the way to the gutter flow line. A pan may be needed at the driveway to convey the water south and back to the existing gutter to the south. Number: 20 Created: 6/13/2007 [7/11/07] Please label as Limits of Street Cut to be consistent with the street cut note. [6/13/07] Stantec: Please label and dimension the limits of ROW on Garfield Ave. Show and label the limits of street cuts needed for utility connections and add the standard street cut note provided to the applicable plan sheet. Number: 24 Created: 6/13/2007 Page I