Comment Number: 8
10/04/2016: No comments.
09/06/2016: No comments.
Topic: Lighting Plan
Comment Originated: 09/06/2016
Comment Number: 13 Comment Originated: 10/04/2016
10/04/2016: Please change the name to GRIT Athletics Training Facility.
Topic: Site Plan
Comment Number: 3
Comment Originated: 09/06/2016
10/04/2016: Please label the proposed easements, or show the recording
information if existing. See redlines.
09/06/2016: Some of the easement descriptions shown are incorrect. If they
are going to stay on the plan, they should match what is shown on the
Subdivision Plat.
Comment Number: 4
Comment Originated: 09/06/2016
10/04/2016: This has not been corrected.
09/06/2016: Some of the sheet titles in the sheet index do not match the sheet
titles on the noted sheets. See redlines.
Department: Water Conservation
Contact: Eric Olson, 970-221-6704, eolson@fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 09/06/2016
09/06/2016: Irrigation plans are required no later than at the time of building
permit. The irrigation plans must comply with the provisions outlined in Section
3.2.1(J) of the Land Use Code. Direct questions concerning irrigation
requirements to Eric Olson, at 221-6704 or eolson@fcgov.com
Department: Zoning
Contact: Ted Shepard, 970-221-6343, tshepard@fcgov.com
Topic: General
Comment Number: 2 Comment Originated: 09/10/2016
09/10/2016: If a new electrical transformer is needed, be sure to screen the
transformer so that it's not visible from the public street.
Carried Over: October 5, 2016:
If the transformer is located along the street, please screen to the extent reasonably feasible. If not able to be screened, please
consider contacting Light and Power and Art in Public Places in order to have the transformer painted by an approved artist.
Perhaps the theme of the artwork could directly relate to the athletic activities planned for the facility. The contact information for
the Art in Public Places program is Ellen Martin, 416-2789, emartin@fcgov.com.
0
' - Comment Num. 12 _.emment Originated: 09/07/2016
10/05/2016: Please compare downstream conveyance elements to show that
the peak flow does not increase.
09/07/2016: Please justify not detaining to the 2-year historic release rate. This
is to include modifying the City's SWMM Model to add the developed basins
and show that the peak flow in the creek does not increase.
Contact: Jesse Schlam, 970-218-2932, jschlam@fcqov.com
Topic: Erosion Control
Comment Number: 1 Comment Originated: 08/22/2016
08/22/2016: The site disturbs more than 10,000 sq. ft., therefore Erosion and
Sediment Control Materials need to be submitted for FDP. The erosion control
requirements are in the Stormwater Design Criteria under the Amendments of
Volume 3 Chapter 7 Section 1.3.3. Current Erosion Control Materials
Submitted do not meet requirements. Please submit; an Erosion Control Plan,
an Erosion Control Report, and an Escrow / Security Calculation. Also, based
upon the area of disturbance State permits for storm water will be required
since the site is over an acre. If you need clarification concerning the erosion
control section, or if there are any questions please contact Jesse Schlam
970-218-2932 or email @ jschiam@fcgov.com
Contact: Mark Taylor, 970-416-2494, mtaylor@fcqov.com
Topic: Floodplain
Comment Number: 3
Comment Originated: 08/31/2016
10/04/2016: 1 still have some concerns about the landscaping shown in the
floodway on the Landscape Plan. I have sent an email message discussing this
to the developer's project manager and engineer.
08/31/2016: On the Landscape Plan, two oak trees and a blue spruce tree are
show in the floodway. Any landscaping in the floodway must meet the
roughness coefficient (n-value) used in the Current Effective floodplain model.
Comment Number: 5 Comment Originated: 08/31/2016
10/04/2016: On the Utility Plan, the last few words of Note No. 9 should be 'in
the floodplain', rather than 'the the floodplain'.
08/31/2016: Please add a note to the Utility Plan and the Grading Plan that a
floodplain use permit must be approved prior to beginning any utility work,
grading, curb & gutter work, etc. in the floodplain.
Comment Number: 16 Comment Originated: 10/04/2016
10/04/2016: On the Drainage Plan, Note No. 3 and Note No. 5 essentially say
the same thing. One of them can be eliminated.
Comment Number: 17
Comment Originated: 10/04/2016
10/04/2016: Also on the Drainage Plan, please include 'Landscaping' and
'Water Quality' within the parentheses of Note No. 4
6�
approval by th( code official prior to installation.
8. Electric gate operators, where provided, shall be listed in accordance with
UL 325.
9. Gates intended for automatic operation shall be designed, constructed and
installed to comply with the requirements of ASTM F 2200.
Department: Planning Services
Contact: Ted Shepard, 970-221-6343, tshepard@fcgov.com
Topic: General
Comment Number: 6
Comment Originated: 09/07/2016
09/07/2016: A materials and color board will be needed for the public hearing.
Staff cautions that the with a large metal roof, the color must be earth tone or
neutral and not an accent color like green or blue.
Carried Over: October 5, 2016: The architectural elevations state that the colors
of the exterior materials has yet to be determined. Please note that colors will
need to be selected for the public hearing. Staff emphasizes that with a large
metal roof, the color must be an earth tone and not an accent color.
Contact: Tim Buchanan, 970-221-6361, tbuchanan@fcgov.com
Topic: Landscape Plans
Comment Number: 1 Comment Originated: 10/07/2016
10/07/2016:
It appears the number of Bur Oak and Linden listed should be reversed -four bur
oak and two lindens.
Comment Number: 2 Comment Originated: 10/07/2016
10/07/2016:
In the non -irrigated native grass the lindens are not low water use trees.
Kentucky coffee tree would be better adapted. Consider using coffee trees in
place of the lindens.
Comment Number: 3 Comment Originated: 10/07/2016
10/07/2016:
Contact the City Forester for an on -site meeting to obtain exiting trees. Label
the existing trees by species, size and condition.
Department: Stormwater Engineering
Contact: Dan Mogen, 970-224-6192, dmogen@fcgov.com
Topic: General
Comment Number: 11
Comment Originated: 09/07/2016
10/04/2016: For final, please submit variance request.
09/07/2016: 100% of the site needs to be treated for water quality. There is not
grandfathering of the impervious areas that are being added and modified.
4
08/29/2016:
The EAE is appropriately labeled on the proposed site plan; however the
proposed 20ft EAE is intended to connect to the public way. It is unclear if the
easement being proposed connects to the Frontage Rd. This easement shall
be dedicated by separate document.
Comment Number: 4
09/05/2016: FIRE LANE SIGNS
Comment Originated: 09/05/2016
The limits of the fire lane shall be fully defined. Fire lane sign locations should be
indicated on future plan sets and the applicant should also be advised that
additional signage may be required at time of field inspection or final CO. Code
language provided below.
> IFC D103.6: Where required by the fire code official, fire apparatus access
roads shall be marked with permanent NO PARKING - FIRE LANE signs
complying with Figure D103.6. Signs shall have a minimum dimension of 12
inches wide by 18 inches high and have red letters on a white reflective
background. Signs shall be posted on one or both sides of the fire apparatus
road as required by Section D103.6.1 or D103.6.2.
Comment Number: 7
09/08/2016: SECURITY GATES
Comment Originated: 09/08/2016
Due to overall fire accessibility relative to the three buildings served by the
cross -lot connecting drive, Poudre Fire Authority would not recommend gating
this drive. However, as this drive does not appear to be associated with any
emergency access easement, it does not appear that PFA can restrict gating.11
is unclear what advantage gating will provide for this site, but if the City of Fort
Collins will allow the access drive to be gated, PFA will require any gate design
to be reviewed and approved by the fire marshal prior to construction. Code
information provided below to aid in planning purposes.
> IFC 503.6: The installation of security gates across a fire apparatus access
road shall be approved by the fire chief. Where security gates are installed, they
shall have an approved means of emergency operation. The security gates and
the emergency operation shall be maintained operational at all times.
> IFC D103.5: Gates securing fire apparatus access roads shall comply with all
of the following criteria:
1. The minimum gate width for vehicle access shall be 20 feet.
2. Gates shall be of the swinging or sliding type.
3. Construction of gates shall be of materials that allow manual operation by one
person.
4. Gate components shall be maintained in an operative condition at all times
and replaced or repaired when defective.
5. Electric gates shall be equipped with a means of opening the gate by fire
department personnel for emergency access. Emergency opening devices shall
be approved by the fire code official.
6. Manual opening gates shall not be locked with an unapproved padlock, or
chain and padlock, unless they are capable of being opened by means of
forcible entry tools or when a key box containing the key(s) to the lock is
installed at the gate location.
Gate design and locking device specifications shall be submitted for
Comment Nun 2 )mment Originated: 09/07/2016
09/07/2016:
If the area to the back of the project is a low water use zone then using Bur Oak
for English Oak and Austrian Pine for Blue Spruce would provide better drought
tolerant species.
Department: Internal Services
Contact: Russell Hovland, 970-416-2341, rhovland@fcgov.com
Topic: Building Insp Plan Review
Comment Number: 1
O8/31/2016:
Pre -submittal meetings has been completed.
Department: Light And Power
Contact: Rob Irish, 970-224-61679 rirish@fcgov.com
Topic: General
Comment Number: 3
Comment Originated: 08/31/2016
Comment Originated: 09/07/2016
10/05/2016:
09/07/2016: A commercial service information form (C-1 form) and a one line
diagram for the commercial meter will need to be completed and submitted to
Light & Power Engineering. A link to the C-1 form is below: .
http://www.fcgov.com/utilities/business/builders-and-developers/development-fo
rms-guidelines-regulations
Comment Number: 5
Comment Originated: 09/07/2016
10/05/2016:
09/07/2016: If the applicant is planning on having anew transformer installed,
please show the proposed location on the Utility and Site plan. If the applicant
is planning on using the existing transformer please show the proposed route of
the secondary service.
Department: PFA
Contact: Jim Lynxwiler, 970416-2869, jlynxwiler@poudre-fire.org
Topic: General
Comment Number: 3
Comment Originated: 08/29/2016
EMERGENCY ACCESS EASEMENT
9/23/2016 The EAE along the north and west side of the building should be
widened to include the entire width of the drive aisle (eg. between the 'Concrete
Apron' and the parking area along the west side).
9/8/2016: based upon the city staff meeting of 9-7-16, the project team is aware
of this condition and is working to resolve it.
of
Fotrt Collins
Community Development and
Neighborhood Services
281 North College Avenue
PO Box 580
Fort Collins, CO 80522
970.221.6750
970.224.6134 - fax
tcgov. com/developmentreview
October 8, 2016
Cathy Mathis
TBGROUP
444 MOUNTAIN AVE
Fort Collins, CO 80513
RE: GRIT Athletics Facility, PDP160024, Round Number 2
Please see the following summary of comments from City staff and outside reviewing
agencies for your submittal of the above referenced project. If you have questions about
any comments, you may contact the individual commenter or direct your questions through
the Project Planner, Ted Shepard, at 970-221-6343 or tshepard@fcgov.com.
Comment Summary:
Department: Engineering Development Review
Contact: Katie Andrews, 970-221-6501, kandrews@fcqov.com
Topic: General
Comment Number: 7
10/03/2016: No more PDP level comments.
Department: Environmental Planning
Contact: Rebecca Everette, 970-416-2625, rverette@fcgov.com
Topic: General
Comment Number: 6
10/03/2016: Ready for hearing.
Department: Forestry
Contact: Tim Buchanan, 970-221-6361, tuchanan@fcgov.com
Topic: Landscape Plans
Comment Originated: 10/03/2016
Comment Originated: 10/03/2016
Comment Number: 1 Comment Originated: 09/07/2016
09/07/2016:
Contact the City Forester for an on -site meeting to obtain tree inventory and
mitigation information to include on the plans. Label exiting trees to retain.