HomeMy WebLinkAboutDUTCH BROTHERS COFFEE DRIVE-THROUGH - FDP - FDP160018 - CORRESPONDENCE -Topic: Construction L,,awings
Comment Number: 6 Comment Originated: 05/09/2016
05/09/2016: There are line over text issues. See redlines.
Topic: Landscape Plans
Comment Number: 3 Comment Originated: 05/09/2016
05/09/2016: There are line over text issues. See redlines.
Topic: Lighting Plan
Comment Number: 4
05/09/2016: No comments.
Topic: Site Plan
Comment Originated: 05/09/2016
Comment Number: 1 Comment Originated: 05/09/2016
05/09/2016: Some of the easement descriptions shown are incorrect. If they
are going to stay on the plan, they should match what is shown on the
Subdivision Plat.
Comment Number: 2 Comment Originated: 05/09/2016
05/09/2016: There are line over text issues. See redlines.
Department: Water -Wastewater Engineering
Contact: Wes Lamarque, 970-416-2418, wlamargue@fcgov.com
Topic: General
Comment Number: 1
05/10/2016: No comments.
Comment Originated: 05/10/2016
n
http://zeus.fcgov.,,in/utils-procedures/files/EngWikiMikiPdfs/L,, -1 Form.pdf
Comment Number: 3 Comment Originated: 05/10/2016
05/10/2016: Contact Light and Power Engineering to coordinate the
transformer and electric meter locations, please show the locations on the utility
plans.
Comment Number: 4 Comment Originated: 05/10/2016
05/10/2016: Electric Capacity Fee, Building Site charges and any system
modification charges necessary will apply to this development.
Comment Number: 5
Comment Originated: 05/10/2016
05/10/2016: A 40 feet separation on both sides of the light is required between
canopy trees and streetlights. A 15 feet separation on both sides of the light is
required between ornamental trees and streetlights.
Comment Number: 6 Comment Originated: 05/10/2016
05/10/2016: Transformer locations shall be within 10' of a paved surface and
must have a minimum of an 8' clearance from the front side and a 3' clearance
around the sides and rear. (1000 kVA up to 2500 kVA requires 4' around the
sides and rear.)
Comment Number: 7 Comment Originated: 05/10/2016
05/10/2016: Please contact Light & Power Engineering if you have any
questions at 221-6700. Please reference our policies, development charge
processes, and use our fee estimator at
http://www.fcgov.com/utilities/business/builders-and-developers.
Department: Stormwater Engineering
Contact: Jesse Schlam, 970-218-2932, ischlam@fcqov.com
Topic: Erosion Control
Comment Number: 1 Comment Originated: 05/10/2016
05/10/2016: No Comment issues resolved with prior submittal.
Contact: Wes Lamarque, 970-416-2418, wlamargue@fcgov.com
Topic: General
Comment Number: 2
Comment Originated: 05/10/2016
05/10/2016: Please label underdrain to be 2-inches above subgrade on the
porous paver detail.
Comment Number: 3 Comment Originated: 05/10/2016
05/10/2016: Please include the drainage plan in the Utility Plan set.
Department: Technical Services
Contact: Jeff County, 970-221-6588,
Topic: Building Elevations
Comment Number: 5
05/09/2016: No comments.
icounty@fcqov.com
Comment Originated: 05/09/2016
3
Comment Number: 5
�,omment Originated: 05/10/2016
05/10/2016: On the Lighting Plan, for fixture CC, under Description, the
Description appears to be incomplete.
Comment Number: 6 Comment Originated:
05/10/2016: On the Lighting Plan, there are 14 CC's indicated in the Schedule
but only 13 shown on the plan. It appears that CC-19 is missing or only a
quantity of 13 is intended. Please verify and correct as necessary.
Comment Number: 7 Comment Originated:
05/10/2016: Repeat Comment: On the Lighting Plan, please add a note that
clearly specifies that fixtures DID must be equipped and installed with "Flush
Mount and Flat Lens."
Department: Engineering Development Review
Contact: Marc Ragasa, 970.221.6603, mragasa@fcgov.com
Topic: General
05/10/2016
05/10/2016
Comment Number: 1 Comment Originated: 05/11/2016
05/11/2016: Add project title " Dutch Bros Coffee to Individual title block sheets
Comment Number: 2 Comment Originated: 05/11/2016
05/11/2016: Update the drainage and erosion control study date to the most
recent in 19 of the General Notes and 2 of the Storm Drainage Notes.
Comment Number: 3 Comment Originated: 05/11/2016
05/11/2016: As shown on the Utility Plans, the fire lane is only about 17' wide.
The building envelope extends into the drive aisle and reduces the overall width
of the emergency access easement. Per conversations with PFA, Bear
Mountain Drive will be sufficient to provide fire access to the building.
Comment Number: 4
Comment Originated: 05/11/2016
05/11/2016: On the horizontal Control Plan, it may be a good idea to include a
concrete band/collar to the north and south of the pavers so they stay in place
and butt up against asphalt.
Comment Number: 5
Comment Originated: 05/11/2016
05/11/2016: The Fire Access Road Sign has been updated. Please use the
revised detail.
Comment Number: 6 Comment Originated: 05/11/2016
05/11/2016: Move the signature block on Sheet 8 to the lower right corner.
Department: Light And Power
Contact: Coy Althoff, CAlthoff@fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 05/10/2016
05/10/2016: Light & Power can serve this property with the requested single
phase electric service.
Comment Number: 2 Comment Originated: 05/10/2016
05/10/2016: Please provide a one line diagram and a C-1 form to Light and
Power Engineering. The C-1 form can be found at:
2
City of
�F6r-t Collins
Community Development and
Neighborhood Services
281 North College Avenue
PO Box 580
Fort Collins, CO 80522
970.221.6750
970.224.6134 - fax
fcgov.com/deve/opmentrev/*ew
May 18, 2016
Nate Frary
729 Oklahoma St
Kennewick, WA 99336
RE: Dutch Brothers Coffee Drive -Through, FDP160018, Round Number 1
Please see the following summary of comments from City staff and outside reviewing
agencies for your submittal of the above referenced project. If you have questions about
any comments, you may contact the individual commenter or direct your questions through
the Project Planner, Ted Shepard, at 970-221-6343 ortshepard@fcgov.com.
Comment Summary:
Department: Planning Services
Contact: Ted Shepard, 970-221-6343, tshepard@fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 05/10/2016
05/10/2016: On the Site Plan, please indicate how many cars can be stacked
behind the Menu Board without impacting the private north -south drive.
Comment Number: 2 Comment Originated:
05/10/2016: On the Site Plan, for Site Plan Note number 11, please add that the
bike rack must be permanently anchored "to concrete and not interfere with
walkways and landscaping."
Comment Number: 3 Comment Originated:
05/10/2016: Please make double sure that the sloping mansard is of sufficient
height to totally screen the roof -mounted mechanical equipment. If after
installation, this equipment is not screened from the two public streets, it
becomes very difficult to mitigate after the fact.
Comment Number: 4
05/10/2016
05/10/2016
Comment Originated: 05/10/2016
05/10/2016: On the Lighting Plan, the Schedule indicates that the Light Loss
Factor for fixtures CC and DID is 0.74 and 0.65 respectively. These must be
recalibrated for a Light Loss Factor of 1.00. This may require the Illuminance
Plan to be adjusted.