HomeMy WebLinkAboutPOUDRE VALLEY HOSPITAL A-WING REPLACEMENT - FDP - FDP150013 - CORRESPONDENCE - PHOTOMETRIC PLAN (4)schedule indicates that these fixtures will be flush -mount with flat -lens, the cut sheet calls out "surface -mount." Please re -affirm the former. For the S-6, the quantity is still not indicated. The Gotham is a new fixture versus the Bega. Please provide a cut -sheet. Please indicate the LED count. Please indicate the Kevin. While the luminaire description states "recessed, " please add "and flush -mount. " Staff is concerned about the use of the 14 Exterior Surface Mounted Decorative Luminous Cubes that are to be attached to the north surface of the canopy along Doctors Lane. These fixtures are redundant and, like the S-4's on Hospital Lane, do not appear serve any practical purpose. The sides appear to be exposed and unshielded. Illumination in this area will be sufficiently provided by the two S-3's and the ten S-6's as well as roadway lighting on Doctors Lane. The illuminance plan shows no foot-candle measurements under these fixtures. Staff finds no compelling reason for these fixtures. For practicality and sustainability, these fixtures should be deleted. Thank you for responding to our comments to eliminate this fixture. Please let me know if you have any questions or concerns about these comments Sincerely: tiAiL� Ted Shepard Chief Planner 9 For the S-2 fixtures: quantity is 4. Please indicate in a separate line that the LED count is 20. Same comments apply as to color temperature as for the S-1's. Indicate that the lumens are 20,950. Please select color: bronze. For the S-2, the quantity is still not indicated. The LED count, while described in the Luminaire line, is still not listed separately thus requiring the cut sheet to accompany the plan sheet. There is no response to the request to lower the Kelvin. The color bronze has not been selected. Staff requests that the Kelvin temperature be lowered to 3,000. For the S-3 fixtures: quantity is 7. Indicate in a separate line that the LED count is 18. Per the cut sheet, indicate that the color temperature is 4,000. Please indicate lumens (1,150 or 1,610). Please select color: bronze. For the S-3, the quantity is still not indicated. The LED count, while described in the Luminaire line, is still not listed separately thus requiring the cut sheet to accompany the plan sheet. There is no response to the request to lower the Kelvin. The color bronze has not been selected. Staff requests that the Kelvin temperature be lowered to 3, 000. The four S-4 fixtures along Hospital Lane are redundant as they are located between public roadway lighting and parking lot lighting. By being placed in the parkway, there is a potential conflict with the street trees. Illuminating the parkway under street trees is not necessary. These four fixtures should be eliminated as they serve no purpose. For the S-4, the quantity is still not listed. The quantity should be two. While the plan sheet indicates that the fixtures have been eliminated along Hospital Lane, there is still an extraneous reference on the plan sheet calling out S4. Please reconcile. There is no response to reduce the Kelvin from 4,100 to 3, 000 For the remaining two S-4's, in the courtyard, please indicate the new quantity: 2. Due to issues related with brightness, please reduce these from the 4,100K to the 3,000K. Indicate the lumens: 950. Select a color: bronze. (The cut sheet does not provide the number of LED lamps per fixture. If known, please provide) There is no response to reduce the Kelvin from 4,100 to 3, 000 and no response to indicate the lumens and no response to select the color.' bronze. For the S-5's, quantity: 3. By selecting the 3K, please indicate the lumens: 1,310 — 1,317. Select a color: bronze. For the S-5, the quantity is still not listed and lumens are not listed and the color, bronze, has not been selected. For the S-6's, quantity: 22. Please indicate the LED count (cut sheet does not provide). It appears that the 3K has been selected. Indicate the lumens: 1,300. While the E Planning, Development and City of Transportation Services Current Planning Fort Collins 281 N. College Ave. PO Box 580 Fort Collins, CO 80522-0580 970.221.6750 970.224.6134 - fax June 26, 2015 — Staff Response to Revised Plans dated June 16, 201 �aricorrecenTe'g g via e-mail on June 23, 2015. Staff Responses are in Italics Below May 13, 2015 Angie Milewski: BHA Design 1603 Oakridge Drive Fort Collins, CO 80525 RE: PVH A -wing Comments Dear Angie, In reviewing the revised plans, the Planning Department has no remaining comments on the site plan, landscape plan and architectural elevations. Staff, however, has reviewed and has comments on the revised Lighting Plan. Because this is one of the first, large-scale, institutional applications of exterior LED lighting, the Plan has been carefully scrutinized. In summary, there are two places where there is redundant lighting and should be eliminated. The Schedule is missing information and selections. Please note the following comments: For the S-1 fixtures: indicate that the quantity is 16. Please indicate in a separate line that the LED count is 20. Per the cut sheet, please select the lowest possible color temperature. The cut sheet indicates that 4,000K is the lowest. If there is a lower color temperature, please select the lowest possible as new exterior LED lighting is in dramatic contrast to public roadway lighting and the City has received complaints about their brightness. Indicate the lumens are 19,862. Please select color: bronze as this color most closely conforms with and blends in with the exterior building materials and colors. For the S-1, the quantity is still not indicated. The LED count, while described in the Luminaire line, is still not listed separately thus requiring the cut sheet to accompany the plan sheet. There is no response to the request to lower the Kelvin. The color bronze has not been selected. In order for these plans to be approved, Staff requests that the Kelvin temperature be lowered to 3,000. 1