HomeMy WebLinkAboutUNION PLACE/REVIVE - COMBINED MJA/FDP - FDP140032 - CORRESPONDENCE -requirements for streets, sLI eetscapes, alleys and easements as set forth in this oection and landscape
plans as set forth in Section 3.2.1. The alternative lot plan shall clearly identify and discuss the
modifications and alternatives proposed and the ways in which the plan will equally well or better
accomplish the purpose of this Subsection (E) than would a plan which complies with the standards of this
Subsection (E).
Review Criteria. To approve an alternative lot plan, the decision maker must first find that the proposed
alternative plan accomplishes the purpose of this Subsection (E) as well as, or better than, a lot plan which
complies with the standard of this Subsection. In reviewing the proposed alternative plan, the decision
maker shall take into account whether the lot plan provides screening and protection of the lots adjacent to
the arterial street from noise, light and other negative impacts of the arterial street equally well or better than
a plan which complies with the standard of this Subsection (E).
3. The proposed development project is subject to a Type 1 review and public hearing, the decision maker
for Type 1 hearings is an Administrative Hearing Officer. The applicant for this development request is
not required to hold a neighborhood meeting for a Type 1 hearing, but if you would like to have one to
notify your neighbors of the proposal, please let me know and I can help you in setting a date, time and
location for a meeting. Neighborhood Meetings are a great way to get public feedback and avoid
potential hiccups that may occur later in the review process.
4. Please see the Development Review Guide at www.fcgov.com/drg. This online guide features a color
coded flowchart with comprehensive, easy to read information on each step in the process. This guide
includes links to just about every resource you need during development review.
5. This development proposal will be subject to all applicable standards of the Fort Collins Land Use Code
(LUC), including Article 3 General Development Standards. The entire LUC is available for your review on
the web at http://www.colocode.com/ftcollinsllanduselbegin.htm.
6. If this proposal is unable to satisfy any of the requirements set forth in the LUC, a Modification of Standard
Request will need to be submitted with your formal development proposal. Please see Section 2.8.2 of
the LUC'for more information on criteria to apply for a Modification of Standard.
7. Please see the Submittal Requirements and Checklist at:
hUp://www.fcgov.com/developmentreview/applications.php.
8. The request will be subject to the Development Review Fee Schedule that is available in the Community
Development and Neighborhood Services office. The fees are due at the time of submittal of the required
documents for the appropriate development review process by City staff and affected outside reviewing
agencies. Also, the required Transportation Development Review Fee must be paid at time of submittal.
9. When you are ready to submit your formal plans, please make an appointment with Community
Development and Neighborhood Services at (970)221-6750.
2. The City's Transportation Development Review Fee (TDRF) is due at the time of submittal. For additional
information on these fees, please see: http://www.fcgov.com/engineering/dev-review.php
3. Any damaged curb, gutter and sidewalk existing prior to construction, as well as streets, sidewalks,
curbs and gutters, destroyed, damaged or removed due to construction of this project, shall be replaced
or restored to City of Fort Collins standards at the Developer's expense prior to the acceptance of
completed improvements and/or prior to the issuance of the first Certificate of Occupancy.
4. Please contact the City's Traffic Engineer, Joe Olson (224-6062) to schedule a scoping meeting and
determine if a traffic study update is needed for this project. In addition, please contact Transportation
Planning for their requirements as well.
5. Any public improvements must be designed and built in accordance with the Larimer County Urban Area
Street Standards (LCUASS). They are available online at:
hftp://www.larimer.org/engineering/GMARdStds/UrbanSt.htm
6. This project is responsible for dedicating any right-of-way and easements that are necessary for this
project. With the change from multi-family/commercial to single family, there may be a need for additional
utility services from the utility providers that require utility easement dedication.
7. Changes to the utility services requiring street cuts to Mason Street or Willox Lane would be subject to a
street cut permit and pavement impact penalty fees due to the condition of these streets being new.
8. Construction plans (or revisions to the construction plans of record) may be required.
9. A Development Agreement or an amendment to the development agreement, may be required and
recorded once the project is finalized with recordation costs paid for by the applicant. A note on the
replat stating that the development agreement for Union Place Subdivision shall apply to this replat may
satisfy the need to amend the development agreement or require a new development agreement.
10. A Development Construction Permit (DCP) or an excavation permit maybe needed prior to starting any
work on the site in addition to the aforementioned street cut permit.
11. The original Union Place development plan obtained a reduction in fees due to a portion of the project
being designated as affordable housing. Should the percentage of affordable housing designation
change with the replat and depending on the process (new PDP vs. major amendment), fees that weren't
collected with the original Union Place may need to be paid back to the City, including the TDRF).
Current Planning
Contact: Jason Holland, 970-224.6126, jhollandPfcgov.com
1. The project will be a Major Amendment of the approved plans, and subject to P&Z review and approval if
more than 50 multi -family units are proposed. Please refer to the Multi -family standards in 3.8.30 of the
code. The code was recently changed to include this 50 unit threshold.
2. Subsection E of 3.2.6: Lots having a front or rear lot line that abuts an arterial street shall have a minimum
depth of one hundred fifty (150) feet.
Alternative Compliance. Upon request by the applicant, the decision maker may approve an alternative lot
plan that does not meet this 150' standard if the alternative lot plan includes additional buffering or
screening that will, in the judgment of the decision maker, protect such lots from the noise, light and other
potential negative impacts of the arterial street as well as, or better than, a plan which complies with the
150' standard of this subsection.
Procedure. Alternative lot plans shall be prepared and submitted in accordance with the submittal
treatment is needed. Thib project volunteered to install LID before it was required which is something
that should be rewarded.
4. A revised grading plan is required and it must be prepared by a professional engineer registered in
Colorado.
5. The city wide Stormwater development fee (PIF) is $6,390.00/acre ($0.1467/sq.-ft.) for new impervious
area over 350 sq.-ft., and there is a $1,045.00/acre ($0.024/sq.-ft.) review fee. No fee is charged for
existing impervious area. These fees are to be paid at the time each building permit is issued.
Information on fees can be found on the City's web site at
http://www.fcgov.com/utilities/business/builders-and-developers/plant-investment-development-fees or
by contacting Jean Pakech at 221-6375. There is also an erosion control escrow required before the
Development Construction permit is issued. The amount of the escrow is determined by the design
engineer, and is based on the site disturbance area, cost of the measures, or a minimum amount in
accordance with the Fort Collins Stormwater Manual.
6. The design of this site must conform to the drainage basin design of the Dry Creek Master Drainage Plan
as well the Fort Collins Stormwater Criteria Manual.
Department: Fire Authority
Contact: Jim Lynxwiler, 970.416.2869, ilvnxwiler(&poudre-fire.orq
1. RESIDENTIAL HYDRANT REQUIREMENTS: Within the Urban Growth Area, hydrants to provide 1,000
gpm at 20 psi residual pressure, spaced not further than 400 feet to the building, on 800-foot centers
thereafter.
2006 International Fire Code 508.1 and Appendix B
2. DEAD-END FIRE LANES
Dead-end fire apparatus access roads cannot exceed 660 feet in length. Dead-end fire access roads in
excess of 150 feet in length shall be provided with an approved area for turning around fire apparatus.
FCLUC 3.6.2(B)2006; International Fire Code 503.2.5 and Appendix D
3. PREMISE IDENTIFICATION
New and existing buildings shall be plainly identified. Address numbers shall be visible from the street
fronting the property, plainly visible, and posted with a minimum of six-inch numerals on a contrasting
background.
2006 International Fire Code 505.1
Department: Environmental Planning
Contact: Lindsay Ex, 970.224.6143, lexOfcgov.com
With respect to landscaping and design, the City of Fort Collins Land Use Code, in Article 3.2.1 (E)(2)(3),
requires that you use native plants and grasses in your landscaping or re landscaping and reduce
bluegrass lawns as much as possible.
Department: Engineering Development Review
Contact: Marc Virata, 970.221.6567, mvirata(a.fcgov.com
1. Larimer County Road Impact Fees and Street Oversizing Fees are due at the time of building permit.
Please contact Matt Baker at 224-6108 if you have any questions.
3. LUC 3.5.2(E) These Garage standards do apply.
4. LUC 3.2.2(K)(1)(c) Single -Family Detached: For each single-family dwelling there shall be one (1) parking
space on lots with greater than forty (40) feet of street frontage or two (2) parking spaces on lots with forty
(40) feet or less of street frontage.
LUC 3.2.2(K)(1)(a) Attached Dwellings:
Number of Bedrooms/Dwelling Unit Parking Spaces Per Dwelling Unit'
One bedroom or less = 1.5
Two bedroom = 1.75
Three bedroom = 2.0
Four bedroom and above = 2.5
5. LUC 3.2.1 A landscape plan is required, which includes but not limited to detached sidewalks and street
trees (see section for details). Please verify that utility locations will not conflict with landscape plan.
Department: Water -Wastewater Engineering
Contact: Roger Buffington, 970-221.6854, rbuffington(&fcgov.com
1. Water and sewer mains were previously installed within the site for the Union Place project. It appears
the number and sizes of buildings will be changing; therefore, utility plans need to be updated to
determine what adjustments will be needed.
2. Existing water and sewer service stubs must be used or abandoned at the main.
3. The water conservation standards for landscape and irrigation will apply. Information on these
requirements can be found at: http://www.fcgov.com/standards
4. Development fees and water rights will be due at building permit.
Department: Stormwater Engineering
Contact: Glen Schlueter, 970-224-6065, gschlueter( fcgov.com
1. The drainage design engineer needs to verify that with this revision the site design is still in compliance
with the approved drainage plan. Impervious area and drainage patterns must be consistent with the
approved plan, and if not the engineer needs to propose mitigation for the changes.
2. The detention and water quality treatment are being provided for in the onsite detention facilities which
also provides regional detention for the west side of North College Ave. The Stormwater Utility did cost
share in the regional detention facilities. The future storm drains will drain the site in the future. The
existing design uses percolation to drain the lower portion of the pond. So in the interim if the pond
holds water for more than 72 hours the water must be pumped out of the pond.
3. Low Impact Development (LID) requirements went into effect March 11, 2013. These require a higher
degree of water quality treatment for 50% of the new impervious area and 25% of new paved areas must
be pervious. Please contact Basil Hamdan at 224-6035 or bhamdan@fcgov.com for more information.
There is also more information on the EPA web site at: http://water.epa.gov/polwaste/green/bbfs,cfm?
goback=.gde_4605732_member_219392996. This site already has LID treatment methods included in
the original design so even though it does not meet the 50% requirement, no additional LID runoff
Community Development and
City of Neighborhood services
Fort Collins 261 North College Avenue
PO Box 580
Fort Collins, CO 80522
970.221.6760
970.224.6134 - fax
fcgovcom
June 05, 2013
Susan Mcfaddin
607 Cowan Street Al
Fort Collins, CO 60524
Re: Union Place Replat
Description of project: This is a request to replat lots within the Union Place subdivision located southwest
of the intersection of West Willox Lane and North Mason Street. The replat seeks to change the two
commercial sites (along the northern edge on Willox Lane) to single family lots and several blocks of
condos to single family attached. The site is located in the Service Commercial (C-S) Zone District. The
replat is subject to Administrative (Type 1) review.
Please see the following summary of comments regarding the project request referrenced above. The
comments offered informally by staff during the Conceptual Review will assist you in preparing the detailed
components of the project application. Modifications and additions to these comments may be made at the
time of formal review of this project. If you have any questions regarding these comments or the next steps in
the review process, you may contact the individual commenter or direct your questions through the Project
Planner, Jason Holland, at 970-224-6126 or jholland@fcgov.com.
Comment Summary:
Department: Zoning
Contact: Noah Beals, 970.416.2313, nbealsCa)fcgov.com
1. Land Use Code (LUC) Section 4.22(B)(2)(a) Single Family detached dwellings located on lots less than
6000 sq ft and Single Family attached dwellings are both permitted uses in the Service Community (CS)
zone district subject to a TYPE 1 review (public hearing with hearing officer).
Platting is also a TYPE 1 review.
2. LUC 3.5.2(D)
Setback from an Arterial Street (Willox) is 30ft
Setback from a Non -Arterial Street is 15ft
Setback side and rear property lines is 5ft except garages which are 8ft
By definition of single family attached these structures have Oft setback on the sides they are attached.
LUC 3.5.2(D)(4) Minimum lot width for single family detached is 50ft.
LUC 3.6.2(E) Lots that have a front or rear lot line that abuts an Arterial street shall have a minimum lot
depth of 150ft.