HomeMy WebLinkAboutRIGDEN FARM, PARKSIDE EAST - PDP - 56-98F - CORRESPONDENCE -x. There should be a 24" x 36" sheet depicting the site in context with its surroundings, This should show both Parkside P.D.P.s and the surrounding a'-V" streets and prcels. Label this drawing "context diagram." y. There needs to be a chart on the landscape plan that gives the total numberof each species of tree proposed. The total number specified must comply with the standards as specified in 3.2.1(D)(3). z. Combine the two plats provided for this P.D.P. into one plat. Ensure that the plat does not use the "Secretary of the Planning and Zoning Board" signature block, but rather uses the "Director of Planning" signature block. Be sure and return all your redlined plans when you resubmit. If you have any questions about these or any other issues related to this project please feel free to call be at 221-6750. You truly, Troy Jones City Planner M requirement to rework the layour of the clubhouse with regard to the front yard area west of the building. See the sketch attached to the redlined site plan. (4) As shown, the southern fa§ade of the clubhouse does not satisfy the minimum wall articulation requirements of 3.5.3(0)(2)(a) which requires that building bays shall be visually established, at least every 30 feet, by architectural features such as columns, ribs or pilasters, piers and fenestration patterns. (5) The western and southern facades of the clubhouse shall be subdivided and porportioned using features such as windows, entrances, arcades, arbors, awnings, or treilage with vines along no less than 50% of the fagade, as required by 3.5.3(D)(3). (6) The stone waincot feature, or some other recognizable "base" treatment must be used on all facades as required by 3.5.3(D)(6)(a). t. I recommend that you postpone the P&Z hearing for the density modifications so you can include requests for the two other modifications that it appears you will need, namely: (1) Section 3.6.2(L)(2)(e) where it requires the intersections of. private driveswith public streets to use the "New Driveway Approach" design from the Engineering Department standards, and (2) Section 3.5.3(B)(2)(b) which requires that the clubhouse be no more than 15 feet from the adjacent street right-of-way. u. These two Parkside P.D.P.s may trigger Drake Road improvements. Schedule the issue with the Engineering Department to be discussed at the weekly Transportation Coordination meeting to determine if Drake improvements are needed with this development. v. The existing conditions page shows the proposed layout of the two P.D.P.s. Take off proposed conditions. w. In the areas where the parking spaces are adjacent to sidewalks, the width of the sidewalksmust be increased to 6 feet [3.2.2(L)(4)]. 5 n. Show dimensions on elevations. Label all building materials on elevations. Specify a pallet of -colors on the elevations. Show elevations of the multifamily garages. o. The multifamily garages must comply with 3.5.2(F)(2) of the LUC. Until we see elevations of the garages, we cannot determine if the proposed garages comply. p. Connect the on -site sidewalks directly to the street sidewalk along Des Moines Drive as required in 3.5.2(C)(1) of the LUC. See Current Planning Redlines. q. Section 3.2.2(B) of the LUC states, "The parking and circulation system within each development shall accommodate the movement of vehicles, bicycles, pedestrians, and transit, throughout the proposed development and to and from surrounding areas, safely and conveniently, and shall contribute to the attractiveness of the development." You need to detach the sidewalks from the curb on both sides of the drive aisle just south of the clubhouse in order to adequately satisfy this standard. If you move buildings B and C both 5 feet south, you will gain some space toprovide a detached sidewalkat the drive aisle location. r. Provide clubhouse elevations on a full sized sheet (24" x 36"). s. Section 4.4(E)(2)(a) specifies that all non-residential buildings permitted in the LMN zone shall meet the standards for Mixed -Use and Commercial Buildings in Section 3.5.3, therefore the following standards from 3.5.3 apply to the clubhouse: (1) Section 3.5.3(B)(2)(b) requires that the clubhouse be located 15 no more than 15 feet from the adjacent street right of way. You will need a modification to this standard if you would like to locate the clubhouse at this location on the site. (2) As shown, it appears that the southern elevation of the clubhouse does not satisfy 3.5.3(C) which specifies that "horizontal masses shall not exceed a height to width ratio of 1:3 without substantial variation in massing that includes a change in height and a projecting or recessed elements." (3) Section 3.5.3(D)(1) states that activity areas are to be tailored specifically to the site and its conext. This reiterates the 4 r >. to follow Section 3.6.2(L)(2)(f) which requires that no stormwater can be channelized across a sidewalk. * h. Buildings G, A, and C impact the neighbors and need landscape buffering as per 3.2.1(E)(1)(c)of the LUC. i. Section 3.2.1(E)(5) of the LUC requires that at least 6% of vehicular area of your parking lot consist of landscaped areas. Please calculate the area outlined in pink on the redlined site plan, then calculate the area of landscaped areas within that pink outline. Provide a diagram of the area from which you calculate the vehicular area and what areas you are considering to be landscaped within that area. Make sure the diagram reads clearly. The diagram can be a small detail on the site plan, or on a separate 8 Z x 11 sheet, but the vehicular area, and landscaped area within that vehicular area, should be depicted in the chart of data on the site plan. Section 3.2.1(E)(6) states that landscape screening is required on all sides of trash enclosures except the side where the opening for access is located. Please add this required landscaping to the areas around the trash enclosures. k. Show curb, gutter and sidewalks of surrounding streets (even if they are existing) on both the site plans and landscape plans with standard line thickness. As submitted they are way too light where shown. I. A lighting plan is required showing all exterior lighting on the site including any proposed pole mounted lights and wall mounted lights. Section 3.2.4 of the LUC requires: • Light sources shall be concealed and fully shielded and shall feature sharp cut-off capability so as to minimize up -light, spill - light, glare and unnecessary diffusion on adjacent property, • Maximum lighting levels shall not exceed 10 foot candles, • Light sources shall minimize contrast (high pressure sodium or incandescent are preferred), • Minimum light levels shall be obtained in various areas in accordance with the chart in 3.2.4(C). m. Specify on the site plan in a general note that not all buildings will be painted the same color. Provide color samples of at least two different color \ schemes for the buildings. Take from shades already established in the neighborhood (the historic farm house) as required in 3.5.1(G). and because the clubhouse is to serve not only residents of this POP, but residents of Parkside West, the elements and features of how the clubhouse relates visually and functionally to the intersection of Limon & Rigden is of utmost importance. Currently what you have proposed for the layout of the parking and pedestrian areas west of the clubhouse do not meet the above standard. The pedestrian crossing of the internal parking lot drive aisle is not safe and convenient, and the location of the row of parking at the visual terminus of the entry and Limon Drive is arguably not contributing to the attractiveness of the development. One way you could satisfy this standard would be to relocate or eliminate the 5 parking stalls directly west of the clubhouse, pull the clubhouse building west (closer to the curb), and enhance the pedestrian crossing. See the recommended layout sketch attached to the Current Planning redlines of the site plan. c. Section 3.2.2(C)(5)(b) of the LUC specifies that the pedestrian crossing of the drive aisle in front of the club house "shall emphasize and place priority on pedestrian access and safety," and that "the material and layout of the pedestrian access shall be continuous as it crosses the driveway, with a break in continuity of the driveway paving and not in the pedestrian access way." As proposed this crossing does not comply with the above standard. d. Section 3.2.2(D)(1) requires that "pedestrians and vehicles shall be separated through provision of sidewalk or walkway." As proposed, the pedestrian traffic coming to the club house it forced to navigate around a row of parked cars and therefore does not satisfy this standard. e. Full Tree Stocking is required in all landscaped areas within 50 feet of any building. Full Tree Stocking is formal and informal groupings of trees spaced at 30 to 40 foot spacing intervals. See section 3.2.1(D)(1)(c) of the LUC. See the redlined landscape plan from the Current Planning Department for locations of where the P.D.P is not satisfying this requirement. f. Section 3.2.2(D) requires the layout of the parking lot to be safe, efficient, convenient and attractive. As proposed staff does not believe the parking lot configuration is efficient and convenient unless the emergency access points are opened up for vehicular traffic movement. g. Section 3.6.2(L)(2)(e) of the LUC requires that intersections of private drives and public streets be made by using the "New Driveway Approach" design from the Engineering Department's standards. The LaGrange project across the street was granted a modification to this standard. Keep in mind that if you seek and are granted a modification on this issue, you still have 2 Commu, - v Planning and Environmental F vices Current Pi`anning Citv of Fort Collins STAFF REVIEW COMMENTS Donald Leffler Design Development 2627 Redwing Road, Suite 350 Fort Collins, CO 80526 I October 9, 2000 Staff has reviewed your submittal for Parkside East at Rigden Farm, and we offer the following comments: COMMENTS: 1. Water and Sewer Utility Department, Stormwater Utility Department, City Forester, Water Conservation, Transportation Planning, Zoning, Natural Resources, Poudre Fire Authority, AT&T Cable, Light & Power, Advance Planning, Post Office, Building Inspection, Park Planning, Streets, Traffic Operations, Right -of -Way Planning, Water Conservation: a. Please seethe attached comment sheets and/or redlined plans from these departments and agencies. 2. Current Planning: a. Section 2.2.11 of the Land Use Code requires that an applicant submit revisions based on this letter within 90 days or the project application becomes null and void. Your response to the City's concerns is due by January 7, 2001. A 30 day extension to this deadline is available. All requests for an extension should be directed to the Current Planning Director. If remaining issues are those that do not require plan revisions, a status report verifying continuing efforts toward resolving the issues is required within the same timeline. b. Section 3.2.2(B) of the LUC states, "The parking and circulation system within each development shall accommodate the movement of vehicles, bicycles, pedestrians, and transit, throughout the proposed development and to and from surrounding areas, safely and conveniently, and shall contribute to the attractiveness of the development." Because the clubhouse terminates the view of Limon Drive looking East and the entry drive's view, 281 North College Avenue • PO. Box 580 • Fort Collins, CO 80522-0580 • (970) 221-6750 0 FAX (970) 416-2020