HomeMy WebLinkAboutRIGDEN FARM, 9TH FILING, PARKSIDE COMMONS - PDP - 56-98T - CORRESPONDENCE -Number: 19 Created: 5/12/2003
Raise or lower storm sewer where possible to eliminate the need for water main lowerings. Water mains may
not be raised by fittings unless air relief valves/vaults are to be installed. These will be considered on a case by
case basis.
Number: 20 Created: 5/12/2003
Provide concrete encasement on all sanitary and storm sewers which cross above or within 18-inches vertically
of a water main.
Number: 21 Created: 5/12/2003
4-inch fire lines must connect to the water main with a tee or saddle and a 4-inch gate valve. Fire lines 3-inch or
larger must be constructed with D.I.P. Cleary define this on the utility plans.
Number: 22 Created: 5/12/2003
Detail sheet has a detail for subdrains. Where are sub drains being installed? Provide all information for every
water main lowerings (i.e. volume of gravity blocks, sizes of fittings, length of pipe between fittings, etc.).
Department: Zoning Issue Contact: Jenny Nuckols
Topic: Zoning
Number: 8 Created: 5/8/2003
Building envelope/dimensions are being shown for all buildings except bldg H - pleawe not them on this bldga s
well
Number: 9 Created: 5/8/2003
Note HC ramps and provide/show patterned/striped crosswalks at entrances into the development off of Kansas
and Rockford Dr
Number: 10 Created: 5/8/2003
Are the crosswalks internal to the site going to be painted striping or enhanced/patterned concrete - please
clarify
Number: 11 Created: 5/8/2003
Page 2 of 2 of the final plat - Tract A contains the drive aisles, Tract C contains bldgs/envelopes A,B,F,G and H.
Which tracts are bldgs C,D,E,K,J and I located in?
Be sure and return all of your redlined plans when you re -submit.
If you have any questions regarding these issues or any other issues related to this project,
please feel free to c 1 me at (970) 221-6750.
Y urs Trul ,
roy Jone
City lann r
Page 10
Number: 42 Created: 5/14/2003
Suggestion: The 28' drive aisle widths seem to be overkill for internal drives and will induce speeding. Please
consider a width of 24', and increase the landscaping, which would allow the units fronting the drive aisles to
have more greenery or larger porch.
Number: 44 Created: 5/15/2003
Please relocate the midblock access ramps on Rockford to align with the north side of the driveway into Parkside
West development and relocate the midblock ramps on Kansas to align with the walkway spine between Bldgs A
and B.
Department: Water Wastewater Issue Contact: Jeff Hill
Topic: General
Number: 24 Created: 5/12/2003
Maintain 10 feet of separation between water/sewer lines and all mail kiosk, electric services/transformers, trash
enclosures, light poles, etc.
See site, landscape and utility plans for other comments.
Topic: Landscape
Number: 23 Created: 5/12/2003
Include a note to maintain a 5 feet minimum separation between shrubs and all water/sewer lines. Maintain the
required landscape/utility separation distances on the landscape plans.
Topic: Plat
Number: 13 Created: 5/12/2003
Curb stops and meter pits may not be located in building envelopes.
Department: Water Wastewater Issue Contact: Roger Buffington
Topic: Utility plans
Number: 31 Created: 5/13/2003
The location of gas and electric meters appear to conflict with location of domestic water services and fire.lines.
This puts four underground services in very close proximity to each other which sets up a hazardous situation.
Number: 32 Created: 5/13/2003
Extend the water and sewer mains between Bldgs H and I to connect with the mains in Rockford Drive.
Eliminate the sewer between Bldgs J and K.
Department: Water Wastewater Issue Contact: Jeff Hill
Topic: Utility plans
Number: 14 Created: 5/12/2003
Place all curb stops within 2 feet of meter pits. Meter pits and curb stops may not be located in hardscaped
surfaces (i.e. driveways, sidewalks, etc.). Place meter pits adjacent to drives and roadways.
Number: 15 Created: 5/12/2003
Maintain 10 feet minimum separation between water/sewer services and permanent structures (i.e. trash
enclosures, entry signage, etc.). Maintain 5 feet separation between water/sewer lines and curb and gutters. No
water services are permitted on dead-end mains beyond the last fire hydrant.
Number: 16 Created: 5/12/2003
All existing stubs must be used or abandoned at the mains. Clearly define all abandonment procedures.
Number: 17 Created: 5/12/2003
Clearly define all connections to existing and proposed water and sewer mains. Show and label all tees, elbows,
thrust blocks, gate valves, etc. All water mains and fire lines 3-inch diameter or greater must be constructed
with D.I.P. (Ductile Iron Pipe). Clearly define this on the utility plans and label distances between all fittings.
Number: 18 Created: 5/12/2003
Shift water and sewer mains so that the manholes are located on center lines of drives and streets. Provide
stationing of sanitary sewer services from the downstream manholes on the sanitary sewer profile sheet. List all
inverts which enter or exit a manhole including services. Do not extend sanitary sewer mains beyond last
service unless it is to facilitate future development.
Page 9
development is to install the Drake Road storm sewer then this project would be dependent on that development
in order to complete its construction.
Please explain what the storm sewer stub on the north side of the property for. Please remove if not needed.
Topic: Erosion Control
Number: 12
May 9, 2003
Created: 5/9/2003
Please remove the Larimer County Urban Street Standards notes on plan sheet 2 under " Grading and Erosion
Control Notes".
Please put City of Fort Collins standard erosion control notes on the erosion control plan, Sheet # 5.
What will protect downstream areas (inlets) from the construction of Kansas Drive?
Please put a note on the plan (Sheet #5) that all disturbed areas are to be seeded and mulched (per your report).
Please provide an erosion control surety calculation.
Topic: Grading
Number: 96 Created: 5/23/2003
It is not clear why the site was graded with a pan around the whole perimeter. It would be preferable to have
most of the site drain to the center of the plan, with the outside buildings sheet flowing out over sidewalks,if you
avoid concentrated runoff then chases would not be needed.
Topic: Plat
Number: 33 Created: 5/13/2003
Please describe a minimum 20-foot wide drainage easement width for any storm line proposed on the site. Keep
storm lines at least 10 feet away from building envelope.
Topic: Utility plans
Number: 25 Created: 5/12/2003
Please call out the size and type of all existing storm sewers on the utility plans.
The current storm sewer alignment shows the line going under a trash enclosure. Please make sure that it is
moved such that the line is within a 20 foot easement and not under the trash enclosure.
The storm sewer connection on Limon Drive will necessitate a cut into an existing street, please specify street
patch extent on the plans.
Please specify which lines will be built by this project and which one will be done "by others" on the utility plans.
What happens if the ones to be built "by others" are not built at the time this project goes to construction ?
Department: Transportation Planning Issue Contact: Tom Reiff
Topic: Transportation
Number: 38 Created: 5/14/2003
Please replace the high volume driveways off of Kansas and Rockford Drive with Type 1 driveways as described
in the LCUASS (dwg. 706 & 1601).
Number: 39 Created: 5/14/2003
Limon and Kansas Drive have previously been identified as connector local streets with combined parking / bike
lanes. These streets will need to be striped to include an 11 foot combined park / bike lane. Please include a
single illustration in the utility details sheet depicting this striping plan and add to the notes. The notes should
also indicate that a single 8° striped line will delineate the combined park / bike lane.
Number: 40 Created: 5/14/2003
Additional access ramps need to be added to the plan at the intersections of Drake Road and Minnesota Drive.
(see red lines) The directional ramps should align as much as possible with the sidewalk to accommodate the
visually impaired, and the ramps should be as wide as the sidewalks.
Page 8
Number: 76 Created: 5/20/2003
If any of the curb chases end up being allowed show the sidewalk chase and the curb chase going out all the
way to the curb line.
Department: Light & Power Issue Contact: Monica Moore
Topic: General
Number: 1 Created: 5/6/2003
Since this site appears to be very. tight, a utility coordination meeting is strongly recommended.
Number: 2 Created: 5/6/2003
Electric facilities will need to be coordinated with the City of Fort Collins early on so that they can be shown on
the utility plans.
Transformer and meter locations as well as electric line placement will be required to be shown on utility plans.
Number: 4 Created: 5/6/2003
Existing and proposed streetlighting must be shown on both the utility plans and the landscape plans.
Number: 5 Created: 5/6/2003
Street trees must maintain minimum clearances to streetlights
(45-ft for shade trees and 15-ft for ornamental trees.)
Number: 6 Created: 5/6/2003
Building G might be problematic to provide electric service to and still maintain clearances to other utilities.
Number: 7 Created: 5/6/2003
Electric facilities must maintain minimum clearances to other utilities. A 10-ft separation is required from water,
sewer and stormdrain. A 4-ft separation is required from gas. Transformer locations must be located within 10-ft
of a paved surface.
Department: Natural Resources Issue Contact: Doug Moore
Topic: General
Number: 43 Created: 5/14/2003
No issues.
Department: Police Issue Contact: Joseph Gerdom
Topic: General
Number: 37 Created: 5/13/2003
Lighting:
Several fixtures listed in the Luminaire schedule don't appear to be on plan.
Trash enclosures - insufficient lighting. Located near Bldgs A, F, H, J. Lighting levels need to be 0.5 -0.7fc
around all sides of enclosures.
Parking between Bldgs I & J plus spaces north of Bldg G is below 0.5fc.
Entrance lighting: Need 1.Ofc at driveways to Rockford and Kansas.
Landscape/Lighting conflict: The three (3) R175 fixtures around Bldg B need to be moved - or the plant materials
- to avoid conflict (shown well within the circumference of the Burr Oak). To lesser degree at southeast corner of
Bldg F.
Department: Stormwater Utility Issue Contact: Basil Harridan
Topic: Drainage Plan
Number: 27 Created: 5/12/2003
Please add a hydrology summary table on the plan.
Please provide an analysis as to what drainage flows were designed by the Rigden Filing 6 plan to be coming
from this site. How do the flows actually compare to those that were assumed by that overall drainage master
plan for this site only. The discharges from the master plan quoted in the report represent discharges that are for
a larger area than that of your site.
Topic: Drake Road Storm Drain
Number: 26 Created: 5/12/2003
It is not clear fro this set of plans what will be installed by the overall Rigden Farms developer and what storm
lines will be installed by this development. Please call this out on the utility plans. If the Rigden Farms overall
Page 7
Number: 89 Created: 5/20/2003
Need to show the limits of removal for the street intersection that is to be removed on Limon. Provide tie in
points and elevations as needed to show what is to be done here. It should be a straight grade across the
intersection so no flowline design is needed as long as that is what remains.
Topic: Landscape
Number: 68
Notes 10 and 25 conflict.
Created: 5/20/2003
Number: 69 Created: 5/20/2003
Note 23 states that the trees are to be planted a minimum of 5 feet from the backs of walks in public row. The
parkways except for Drake Road are only 6 feet wide. This would place the tree 6 inches behind the curb head.
Don't believe that will work and is not what we want.
Topic: Plat
Number: 60 Created: 5/20/2003
Correct title of plat to match other documents: Rigden Farm 9`h Filing - Parkside Commons.
Number: 61 Created: 5/20/2003
Need to add the private drive maintenance note.
Number: 62 Created: 5/20/2003
Correct the dedication statement, maintenance guarantee statement, notice of other documents statement,
attorney certification statement, approved as to form city engineer statement, and planning approval statement.
Number: 63 Created: 5/20/2003
Need to dedicate Kansas with this project.
Number: 64 Created: 5/20/2003
Remove the word private from note 1. The property cannot be private access easements or private open space.
Number:65 Created: 5/20/2003 C
Need to provide the minimum 9 foot easement behind the row on Limon, Kansas and Rockford. Do not appear
to have that on Limon. Provide the additional easements as discussed in the utility coordination meeting.
Number: 66 Created: 5/20/2003
Tract B is not labeled.
Number: 67 Created: 5/20/2003
More than likely when the row stub is vacated the whole area will be retained as an easement. If the entire area
is retained as an easement then this plat will need to vacate the area with in the building envelope.
Topic: Site plan
Number: 70 Created: 5/20/2003
Use type I driveways and show concrete to the property line at the driveway entrances.
Number: 71 Created: 5/20/2003
The easements shown do not match what is being shown on the plat.
Number: 72 Created: 5/20/2003
Change the midblock crossings on Rockford and Kansas as indicated by Tom Rieff.
Number: 73 Created: 5/20/2003
Show the installation of the midblock ramps on Limon to match the ramp locations across the street and the dips
in the curb and gutter that should have been done when the curb and gutter was built.
Number: 74 Created: 5/20/2003
No trash enclosures are to be placed over the utilities in utility easements.
Number: 75 Created: 5/20/2003
The pan around the outside of the site needs to go away.
Page 6
Number: 94 Created: 5/20/2003
See additional comments on the plans.
Number: 95
See returned check list.
Created: 5/20/2003
Topic: Kansas Design
Number: 78 Created: 5/20/2003
In accordance with LCUASS centerline station is required. Until a meeting with the various Engineering firms
interested in this issue is held to determine what the final requirements for submittal will be the following is what
is being required. For Arterials and Collectors - the existing criteria remains in place. Centerline stationing is to
be provided along with the required x-sections every 50 feet. For Residential and Local Streets - in lieu of
providing centerline stationing flowline stationing can be used if actual x-sections of the roadway at the beginning
of a horizontal curve, end of a horizontal curve, and additional x-sections be provided if there are other elevation
changes, grade changes and street width changes that occur within the horizontal curve. Also need to identify
the location of beginnings and endings of horizontal curves with elevations noted on the profile and plan view.
Since this roadway is a local roadway flowline station can be used if the above information is provided.
Number: 79 Created: 5/20/2003
Need to show the removal limits for the existing intersection.
Number: 80 Created: 5/20/2003
Need to coordinate the design of Kansas with the Drake/Ziegler plans. This set shows different elevations at the
PCR on Kansas than the other plans do. Also the plans differ in where the improvements will tie together.
Number: 81 Created: 5/20/2003
The cross pan at Drake and Kansas will only be a 6 foot crosspan as that is the requirements of which the Drake
Road plans were designed under. You are correct that the current standard would be a 10 foot pan.
Number: 82 Created: 5/20/2003
Need to show that the minimum slope going into the inlet is .50%. Per Section 7.4.13.4 even within a sag vertical
curve located at the flowline the minimum slope needs to be maintained.
Number: 83 Created: 5/20/2003
The vertical curves need to meet minimum length requirements. See figures 7-17 and 7-18 for minimum design
requirements. Design speed for this roadway since it is a connector local is 30 mph, which means that for the
algebraic grade differences shown the minimum length of crest and sag curves is 90 feet.
Number: 84 Created: 5/20/2003
If curb chases are used need to show the location and size of them on the plan and profile.
Number: 85 Created: 5/20/2003
Provide intersection elevations in accordance with detail 7-27. Missing elevations and need to provide the
transition elevation and identify its location.
Number: 86 Created: 5/20/2003
Show a type III barricade at the end of Limon Street. If one doesn't already exists it needs to be installed.
Number: 87 Created: 5/20/2003
The slope on Limon where you are removing curb and gutter and installing the new street intersection does not
match the approved plans. Need to put the new c&g in and the x-pan in with the slope that was approved (match
the approved plans as much as possible). Can not install all the c&g you are showing as Limon has not been
designed past the PCR. Can not put in c&g that has not been designed.
Number: 88 Created: 5/20/2003
Need to provide centerline information for Limon and existing Kansas. Need to be able to determine that the
intersections are meeting criteria and align properly thru the intersection. Will need elevations for this full
intersection.
Page 5
Number: 47 Created: 5/20/2003
A very limited amount of drainage is allowed to go out the driveway. The eastern driveway has more drainage
going out it than allowed. Revise the grading and get the drainage to the interior inlet or to the street by a
different method.
Number: 48 Created: 5/20/2003
The drainage swales/ pans that border the site need to be removed. The drainage needs to be handled in
another way. Non concentrated flows can go over the landscaping and across the sidewalk out to the street
Concentrated flows should be directed to and picked up by area inlets or into the internal drainage system.
Sidewalk chases and curb cuts shall be limited. Please work with stormwater.
Number: 49 Created: 5/20/2003
Need to coordinate a bunch of work with the Drake/ Ziegler plans. Any work within Drake Road or that affects
the curb, gutter or pavement must be shown as a part of the Drake Road plans and constructed with that
construction. Need to work with JR eng to get the items incorporated into the plans and work with Matt Baker to
pay for the cost of the installation of those items.
Number: 50 Created: 5/20/2003
This project will have extensive street cut fees and repairs. Once all the utilities, curb cuts and repairs are shown
correctly (per the utility coordination meeting there will be some different connections than are shown now) I can
have the plans reviewed and can identify the types and limits of patching to be done. Some areas will be
required to be milled and overlayed as a part of the patching. The street cut fees are tripled for cutting into a
street that is less than 5 years old. Which will apply to all the existing streets around this site.
Number: 51 Created: 5/20/2003
This site is dependent on Drake Road improvements occurring before work can occur on this site. If for some
reason the Drake Road work is not proceeding and this project is ready to build then it will need to incorporate
the needed improvements (storm sewer ad water line) into this plan set and build them.
Number: 52 Created: 5/20/2003
May not meet the minimum cover requirements over the stormsewer line. You meet it now, but have not shown
the concrete encasement - with that it may not meet it. How thick is the concrete encasement?
Number: 53 Created: 5/20/2003
Only install the sidewalk on your block. Label the sidewalk on the west side of Kansas as future. It needs to be
shown so that the curb depressions for the ramps get put in the proper place when it is built.
Number: 54 Created: 5/20/2003
High groundwater was not encountered, subdrains are not required. Remove subdrain detail or provide a
subdrain report and design. The outlet will need to be above the 100 yr water elevation.
Number: 55 Created: 5/20/2003
We do not want the trash enclosures within the easement areas or over utilities. They are structures.
Number: 56 Created: 5/20/2003
Change the midblock crossings on Rockford and Kansas as indicated by Tom Rieff.
Number: 57 Created: 5/20/2003
Show the installation of the midblock ramps on Limon to match the ramp locations across the street and the dips
in the curb and gutter that should have been done when the curb and gutter was built.
Number: 58 Created: 5/20/2003
Show ramps at the intersections going across Drake.
Number: 59 Created: 5/20/2003
Add patching note to the plans where street cuts are shown. Limits of street cut are approximate. Final limits
are to be determined in the field by the City Engineering Inspector. All repairs to be in accordance with City
street repair standards.
Number: 77 Created: 5/20/2003
Make changes to the general notes as shown. Add the missing general note, and missing
construction note. Indicate that the variance to drawing 19-03 is approved.
Page 4
Number: 111 Created: 5/28/2003
The proposed new segment of Kansas Drive needs to be dedicated as part of this plat.
Number: 112 Created: 5/28/2003
In accordance with Section 2.2.11(A) of the LUC, revisions based on these comments must be submitted to the
Current Planning Department within 90 days. See the" total" line on the attached revision routing sheet for the
number of copies of the various documents that will need to be resubmitted.
Number: 113 Created: 5/28/2003
The °front° and °rear° elevations are labeled incorrectly. The front is typically the elevation that faces on opens
directly onto the street. The rear elevation typically faces the internal portion of the lot.
Number: 114 Created: 5/28/2003
Calculate the net acreage in accordance with 3.8.18 of the Land Use Code now that the Kansas right-of-way is
within the project boundary. State the project's density based on the new net residential acreage. The overall
density of the residential land within the MMN zone must be 10 units per net acre, however, individual filings
such as this can be as low as 7 units per net acre of residential land, so long as the density range listed on the
overall development plan is satisfied [4.5(D)(1)(a) of the LUC).
Department: Engineering Issue Contact: Sheri Wamhoff
Topic: Details
Number: 90 Created: 5/20/2003
Need to remove old details and use current details. Also remove details showing corner ramps as all ramps
within the row will be directional ramps. If the corner ramps are to be used on -site label the detail for on -site use.
Number: 91 Created: 5/20/2003
Make changes to the typical x-section. It needs to be labeled as a connector local, and it needs to have vertical
curb and gutter (which is what the plans and profile sheets said it was). The x-section is to be two 10 foot travel
lanes and two 11 foot bike and parking lanes with a solid white channelizing line 8 inches wide between the
travel lanes and the bike, parking lanes. Need to note that this is to be provided. The parkway is to be 6 feet
wide and is not a landscape and utility easement as it is within the row. Identify that the x-slope on the street is
2.0% to 3.0%. Need to identify the range since a constant 2% x-slope is not being provided on the street.
Number: 92 Created: 5/20/2003
Need to provide the following details in addition to the ones that need to be updated as indicated on the plans:
Sleeve locations #1202
Sidewalk detail # 1602
Standard sidewalk # 1601
Pedestrian ramp # 1606
Access ramp scoring # 1607
Number: 93 Created: 5/20/2003
If underwalk drains can not be avoided and are allowed detail #709 will also be needed.
Topic: General
Number: 34 Created: 5/13/2003
Naming - This should follow the same naming convention that the other did. It should be called Rigden Farm 9'h
Filing - parkside commons and should be changed on all documents.
Number: 45 Created: 5/20/2003
The driveways can not be high volume driveways, they need to be standard curb cuts, per the traffic study they
do not meet high volume requirements.
Number: 46 Created: 5/20/2003
Need to identify how and where the curb and gutter on the on site driveways end, as the driveway cuts within the
row do not have a curb. Concentrated flow is not allowed out of the driveways, thus from the highpoint in the
driveway there is to be no curb and gutter, just a concrete or asphalt edge so sheet flow occurs. (See next
comment regarding the amount of flow allowed out a driveway)
Page 3
street light. As specified in Section 3.2.1(K) of the Land Use Code, tree/utility separations shall not be used as a
means of avoiding the planting of required street trees.
Number: 99 Created: 5/27/2003
Electric Vaults, if pad mounted, should integrate landscape screening in accordance with Section 3.2.1(E)(6) of
the LUC.
Number: 100 Created: 5/27/2003
Specify the materials of the trash enclosures. The enclosures need to be incorporated into the overall design
theme of the buildings and landsccape so that no attention is attracted to the functions by use of screening
materials that are different or inferior to principal materials of the building and landscape. The enclosure
(whether made from fencing or walls material) must provide plant material in conjunction with the enclosure's wall
in accordance with 3.2.1(E)(1)(d) of the LUC. Such screening shall be established on all sides of trash collection
enclosures except where an opening is required for access in accordance with Section 3.2.1(E)(6) of the LUC.
Number: 101 Created: 5/27/2003
An additional tree needs to be integrated between buildings C and D in or near the vehicular area, at the
southeast corner of building A, between building J and K in or near the vehicular area, and between buildings I
and J in or near the vehicular area to satisfy the full tree stocking requirment in accordance with 3.2.1(D)(1)(c) of
the LUC.
Number: 102 Created: 5/27/2003
Does each and every unit have at least a single car garage accessible to the unit? If not, bike racks must be
provided in accordance with 3.2.2(C)(4) of the LUC.
Number: 103 Created: 5/27/2003
Crosswalks internal to the site must use the material of the sidewalk as it crosses the vehicular area as required
in section 3.2.2(C)(5)(b) of the LUC.
Number: 105 Created: 5/27/2003
Replace the "Planning and Zoning Board" approval block on the plat with the "Director of Planning" signature
block.
Number: 106 Created: 5/27/2003
The block directly south of this site is being planned as a charter school, and is currently in the planning stages.
I recommend that you carefully coordinate any street cuts with that development, to combine efforts, and
potentially reduce the chance of more street cuts than necessary. Steve Steinbecker at 207-0424 is the point of
contact for the school application. Also Jim Sell Design at 484-1921 is potentially working on a development
plan west of tract U, and they were the land planners for the filing that created the streets in the first place, so
you may want to coordinate with them.
Number: 107 Created: 5/27/2003
The drive aisles internal to your site are designed at 28 feet wide. You can make them that wide if you want to,
but they don't need to be that wide. I recommend making them narrower and providing more landscaped areas.
Section 3.2.2(L)(1) specifies that the drive aisle width can be as narrow as 20 feet wide when parking spaces are
served on one side of the drive aisle, and can be as narrow as 24 feet when parking spaces are served on both
sides of the drive aisle. This is not to be confused with the requirement that in instances when garage doors face
each other (such as across a drive aisle from one another), the garage doors themselves need to be 28 feet
apart from one another, but the drive aisle width itself can be the widths mentioned above.
Number: 108 Created: 5/28/2003
Lighting fixture specifications were only provided for fixture "A175." Provide fixture specifications for fixtures B,
C, and R175. Ensure that the specifications for fixture R175 clarify that they are cut-off and down -directional.
Number: 109 Created: 5/28/2003
Joe Gerdom from the Police Department is concerned that the lighting levels are a little too dim at the driveway
intersections with the street. Coordinate the solution of this directly with Joe Gerdom at 416-2522.
Number: 110 Created: 5/28/2003
The color scheme rendered for Palette #1 does not seem to be the same colors as the color samples provided
for Palette #1. The rendered picture has a green body color, whereas the color sample has no green sample.
Please clarify your intentions.
Page 2
STAFF PROJECT REVIEW
City of Fort Collins
CITYSCAPE AN DESIGN, INC. Date: 05/28/2003
JOE CARTER
3555 STANFORD RD. #105
FT. COLLINS, CO 80525
Staff has reviewed your submittal for RIGDEN FARMS, PARKSIDE COMMONS —TRACT U—
TYPE I (LUC) 56-98T, and we offer the following comments:
ISSUES:
Department: Advance Planning Issue Contact: Clark Mapes
Topic: General
Number: 36 Created: 5/13/2003
I would like to have a conversation with the developer about allowing the architect to provide a little model
variation.
Department: Current Planning Issue Contact: Troy Jones
Topic: General
Number: 28 Created: 5/13/2003
We would like the name of all filings in the Rigden Farm development to be consistent. To that end, the official
name of this project needs to be changed on all drawings (including site plan, landscape plan, plat and utility
plans) to the following: "Rigden Farm, Filing 9, Parkside Commons".
Number: 29 Created: 5/13/2003
Based on discussions at the utility coordination meeting conducted on 4/30/03, it sounds like utility meters will
need to be integrated onto the west facades of buildings C, B, A, and K, and on the east facades of buildings E,
F, H, and I. These are all street facing facades, which requires that screening of those utility meters be
"incorporated into the overall design theme of the building and the landscape," and that "no attention is attracted
to the functions by use of screening materials that are different from or inferior to the principal materials of the
building and landscape," and that "the visual and acoustic impacts of these functions are fully contained and out
of view from adjacent properties and public streets.° [LUC 3.5.1(1)(2)] As shown on the elevations, the meters are
located on the facade with 2 doors on the end wall (labeled "6 plex right elevation"). If the meters are to be street
facing, they need to be shown on the end wall with a single door (labeled "6 plex left elevation"). From an
aesthetic perspective, it would be preferable to have the utility meter located on facades other than the street
facing facades, however if they are, adequate screening must be provided. An enclosure made of the same
materials of the building would successfully screen it from view. Landscaping material that is intended to act as
screening of the utility meters needs to be tall enough to do so. Please clarify how tall the landscaping will be
when used as screening. Such screening is also required in accordance with Section 3.2.1(E)(6) of the LUC.
Number: 30 Created: 5/13/2003
The Light & Power Utility has indicated that a duct bank is anticipated to be located beneath the parkway strip
between the curb of Drake Road and the street sidewalk. This is typically 30" to 42" deep. Trees can be planted
over the duct bank to satisfy street tree requirements, however, be sure to coordinate the trees species selection
and spacing with the design of the duct bank. Also, there is a large stormwater pipe in the Drake right-of-way.
Be sure that any revision to the layout continues to allow street trees along Drake to not conflict with the
placement of this stormdrain pipe.
Number: 97 Created: 5/27/2003
The plans show a concrete trickle pan adjacent to the sidewalk around the perimeter of the project. We
discussed this at staff review between the Engineering Department, Stormwater Utility, and the. Planning
Department, and we all agree this is not necessary and should be removed. It sounds as if there was perhaps a
misunderstanding that caused this element in the proposed design. Limited areas of yard can sheet flows across
sidewalks, and should in this case.
Number: 98 Created: 5/27/2003
Show street lights on the landscape plan. Street lights and street trees need to be coordinated. Canopy shade
trees require 40 feet of separation from street lights, however ornamental trees can be as close as 15 feet to a
Page 1