Number: 103 Created: 4 / 21 / 2006
[4 / 21 / 06) Substitute updated detail for the 1-1 / 2" water meter pit detail.
This completes staff (and outside reviewing agencies) review.and comments
at this time. Red -lined plan from City departments are included with this
comment letter. Additional comments and red -lined plans may be
forthcoming. Another round of staff review is necessary. This proposal is
subject to the 90-day revision re -submittal requirement (from the date
of this comment letter, being April 26, 2005) as set forth in Section
2.2.11(A) of the Land Use Code. Be sure and return all red -lined plans
when you re -submit. The number of copies of each document to re -submit
is shown on the attached Revisions Routing Sheet.
If you have any questions regarding these issues or any other issues related
to this project, please feel free to call me at (970)221-6341.
Yours Truly,
/)WRZW
teve Olt
City Planner
cc: Sheri Wamhoff
Arcodev Architects
inSITE Engineering
Current Planning File #56-98AI
Page 6
Department: Stormwater-Water-Wastewater Issue
Contact: Basil Hamdan
Topic: Erosion Control
Number: 97 Created: 4/ 18/2006
[4/ 18/06] April 18, 2006
1. Please replace the erosion control notes on plan sheet #6 with the most
recent City of Fort Collins notes.
2. If there is a DA, the erosion control surety should beset at $1,000.
Department: Stormwater-Water-Wastewater Issue
Contact: Roger Buffington
Topic: Landscape plan
Number: 83 Created: 1 / 25 / 2006
[4/21/061
[2/28/06]
[1/25/06] Revise landscape plan to reflect correct utility line/service line
locations.
Department: Stormwater-Water-Wastewater Issue
Contact: Basil Hamdan
Topic: Stormwater
Number: 94 Created: 3 / 1 / 2006
[4/ 17/06]
The revision done to sheet C 19 of the Kimley-Horn plans should be labeled
separately and revision number 3 and bubbled out clearly so it can be
identified.
The dedication by separate document for the area where the inlet is being
stubbed out should be finalized prior to plans signature.
Department: Stormwater-Water-Wastewater Issue
Contact: Roger Buffington
Topic: Water/WW
Number: 17 Created: 11 / 8 / 2005
[4/21/06]
[2 / 28/ 06]
[ 1 / 25/ 06]
[ 11 / 8/ 05] Provide utility easement for the re -located fire hydrant.
Number: 102 Created: 4 / 21 / 2006
14/21/06] When will the Kimley-Horn plans be revised to reflect these
utility plan revisions?
Page 5
Number: 78 Created: 1 / 24 / 2006
[4/ 18/06] The borders on 1601 and 1602 are missing and 701 is stretched
out. Please fix.
[3 / 1 / 06] The details were added, but need some help. The line weights will
not reproduce well and they are not really readable.
[1/24/06] Add the following details to the plans: 701, 1601 and 1602 these
will be used to replace any existing damaged curb, gutter or sidewalk or
curb, gutter and sidewalk damaged during construction.
Department: Engineering Issue Contact: Dan
DeLaughter
Topic: General
Number: 98 Created: 4/ 18/2006
[4/ 18/06] Please add the Final Plat to the Sheet index.
Topic: Site Plan
Number: 99 Created: 4/ 18/2006
[4/ 18/06] On the Site Plan, landscaping along Custer Dr. is shown as "by
others." If this is existing please label as such. If not existing, please
indicate who the "others" refers to.
Department: Light & Power Issue Contact: Monica Moore
Topic: Utility plans
Number: 96 Created: 3 / 29 / 2006
[3/29/06] No comments.
Department: PFA Issue Contact: Carie Dann
Topic: fire
Number: 95 Created: 3/3/2006
[4/ 19/06] Address numerals will be required on only the Grease Monkey
building; however, we still request numerals on both the east and west side
of the building, minimum of six inches in height and on a contrasting
background.
[3/3/06] PFA requests that address numerals be posted on both the west
and east sides of the Grease Monkey building, and the west side of the car -
wash structure.
Number: 100 Created: 4/ 19/2006
[4/ 19/06] WATER SUPPLY: Fire hydrant location is within 300 feet of the
structures; applicant needs to ensure the minimum flow requirement of
1,500 gallons per minute at 20 pounds per square inch residual is met.
Number: 101 Created: 4/ 19/2006
[4/ 19/06] HMIA: A hazardous materials impact analysis must be submitted
to the Planning Department and Fire Department. Contact Carie Dann at
Poudre Fire Authority for more information.
Page 4
[ 1 / 24 / 06] This sheet has not yet been submitted for review. This revision
will need to be approved before or at the same time this project is approved.
[1 l/ 14/051 For the removal of the storm drain inlet - the original plans
(sheet C 19) needs to be revised to show this change. These plans also need
to be revised to show the new inlet and manhole that you are proposing.
Number: 45 Created: 11 / 14/2005
[4/ 18/06] The meter pit is now included in an easement and the easement
for the storm inlet has been received, but the easement for the fire hydrant
must be submitted and appropriate TDRF and filing fees for both paid to
engineering. Also, please update the site and landscape plans to include the
new easements.
[3 / 1 / 06] Easements by separate document are needed as follows: A utility
easement for the relocation of the fire hydrant. A utility easement for the
meter pit for the grease monkey building (as shown it is being placed
outside of the existing easement area). A drainage easement for the storm
drainage inlet. Please let me know if you have questions regarding format or
the processing. These will need to be provided prior to our approval of these
utility plans.
[ 1 / 24 / 06] I provided a copy of the dedication documents, information sheet
and application form. There is a $250 processing fee (plus filing fees) for
this document.
[ 1.1 / 14/ 05] An easement by separate document is needed for the relocation
of the fire hydrant.
Number: 61 Created: 1 / 24 / 2006
[4/ 18/06] Please change the line type to existing.
[3 / 1 / 06] Per the site plan the light pole is now being removed not relocated.
Please adjust note on utility plans.
[ 1 / 24 / 06] It has not been identified where the light pole is to be relocated
to.
Number: 66 Created: 1 / 24 / 2006
[4/ 18/06]
[3/ l/06] Please make sure to update this as future sets are submitted.
[ 1 / 24 / 06] Final plans will need to list current month and year under the
title and legal.
Number: 68 Created: 1 / 24 / 2006
[4/ 18/06] Repeat
[3/ 1/06] These can be found in appendix E - You have added the General
Notes, but are still missing the Construction Notes.
[1/24/06] Provide the applicable General Construction notes.
Page 3
Topic: General
Number: 109 Created: 4/25/2006
[4/25/06] The following comments were expressed at City staff review on
Wednesday, April 19, 2006:
Stormwater
a. The Kimley-Horn utility plans must be revised.
Water/ Wastewater
a. Are the necessary easements going to be dedicated and, if so, how?
Engineering
a. An off -site easement is needed for the fire hydrant relocation.
b. The fees for the necessary easements must be paid.
Poudre Fire Authority
a. A HAZMATS Study must be submitted to the Poudre Fire Authority for
review.
Topic: Landscape plan
Number: 108 Created: 4/25/2006
[4/25/061 A couple of ornamental trees, 2 or 3, in the planting area along
the south side of the entry drive to the lube shop and car wash would be
appropriate to work as screening, in conjunction with the existing street
trees.
Topic: Transportation Planning
Number: 107 Created: 4/25/2006
[4/25/06] The crosswalk area from the Grease Monkey building to the
pedestrian walkway to the north should be raised, enhanced, or striped to
provide a clearly identified pedestrian crossing.
Department: Engineering Issue Contact: Sheri Wamhoff
Topic: General
Number: 41 Created: 11 / 14 / 2005
[4/18/06] Please refer to redlines for additional minor comments.
[3 / 1 / 06] Sheet C 19 needs to be revised by Kimley-Horn or completely
redrawn (everything needs to be provided and the engineering company will
need to sign off on the design) so that the existing sheet can be replaced
with the revised or new sheet. This needs to be submitted with the final
compliance submittal.
Page 2
STAFF PROJECT REVIEW
City of Fort Collins
Automotive Development Group Date: 04/25/2006
c/o Jody Newton
360 Happy Canyon Road
Castle Rock, CO. 80108
Staff has reviewed your submittal for RIGDEN FARM, 8TH FILING, LOT 59
GREASE MONKEY/CARWASH - FINAL PLANS, and we offer the following
comments:
ISSUES:
Department: Current Planning Issue Contact: Steve Olt
Topic: Building Elevations
Number: 105 Created: 4 / 25 / 2006
[4/25/06] What is the color of the proposed standing -seam metal roof?
That must be shown on the Exterior Elevations plan.
Number: 106 Created: 4 / 25 / 2006
[4/25/06] Staff still has a concern about the south elevation of the Grease
Monkey building. It is the side of the building with the most visual impact
on the entry to Rigden Farm, being Custer Drive. The north elevation,
internal to the shopping center, is all masonry while the south elevation has
a split between masonry and E.I.F.S. siding at a somewhat illogical place.
The masonry should continue up to the top trim on the gable section.
Topic: fire
Number: 104 Created: 4 / 25 / 2006
[4/25/06] The Poudre Fire Authority has indicated that an Emergency
Access Easement (EAE), or fire lane, for the shopping center, including this
lot/pad site, was to be included on the subdivision plat but was not done
so. A fire lane is needed on this site and would have to be dedicated through
separate document since this development request is not replatting the
property. Please contact Joe Jaramillo, at (970)416-2868, for information on
the fire lane need.