Department: Stormwater-Water-Wastewater Issue
Contact: Roger Buffington
Topic: Landscape plan
Number: 83 Created: 1 /25/2006
12/28/061
[1/25/06] Revise landscape plan to reflect correct utility line/service line
locations.
Number: 88 Created: 2/28/2006
12/28/06] Revise tree placements to comply with separation distances from
water/sewer mains and services.
Department: Stormwater-Water-Wastewater Issue
Contact: Basil Hamdan
Topic: Stormwater
Number: 94 Created: 3/ 1 /2006
[3/1/06] Please provide revisions to the originally approved utility plans by
Kimley Horn and Associates for this site. This can be done at final.
Please dedicate a drainage easement for the new inlet being proposed, and it
connection to the existing line. Easement should be at least 20 feet wide.
Department: Stormwater-Water-Wastewater Issue
Contact: Roger Buffington
Topic: Water/WW
Number: 17 Created: 11 /8/2005
[2/28/061
[1/25/061
[11/8/05] Provide utility easement for the re -located fire hydrant.
Number: 81 Created: 1 /25/2006
[2/28/06] See water service and meter pit standard details. Curb stop
must be in a landscaped area but also must be within two feet of the meter
pit. Easement must extend from the water main to, the area around the
curb stop. If no reasonable landscaped area is available, curb stop/meter
pit may be in sidewalk (but NOT in drive or parking area).
[1/25/06] Show curb stop and meter pit on the 3/4" water service. Must
be in a landscaped area. Curb stop must be within easement.
Be sure and return all red -lined plans if/when you re -submit prior to the
administrative public hearing, scheduled for Tuesday, March 21st at 10:30
a.m. Another submittal is not needed until Final Compliance.
Page 5
Number: 63 Created: 1 /24/2006
[3/ 1 /06] Most of general note 47 has been included. Note 48 is not
showing up.
[1/24/061 Provide general notes 47 and 48. Indicate that there are no
private streets to maintain and that no variances were granted.
Number: 66 Created: 1 /24/2006
[3/ 1 /06] Please make sure to update this as future sets are submitted.
[ 1 /24/061 Final plans will need to list current month and year under the
title and legal.
Number: 68 Created: 1 /24/2006
[3/ 1 /06] These can be found in appendix E - You have added the General
Notes, but are still missing the Construction Notes.
[ 1 /24/061 Provide the applicable General Construction notes.
Number: 71 Created: 1 /24/2006
[3/ 1 /06] The tree wells have been shown, but they are not dimensioned
any place. Provide dimensions so that the tree well locations can be placed.
[ 1 /24/06] Need to show the new tree wells on the utility plans. Need
dimensions and information on where they are to be located and what type
of tree grates are to be installed. How are these to be watered?
Number: 74 Created: 1 /24/2006
[3/ 1/06] Missing the first sentence of this note on the plans. Also please
show street cut lines so that it is clear to the contractor which locations will
require street cuts.
[ 1 /24/061 Add the following note to the utility plans regarding street cuts.
Limits of street cut are approximate. Final limits are to be determined in
the field by the City Engineering Inspector. All repairs to be in accordance
with City street repair standards.
Number: 76 Created: 1 /24/2006
[3/ 1 /06] Notes below the new construction has not been added.
[ 1 /24/061 For the storm pipe note that the new manholes design is
provided on Sheet C 19 of Rigden Farm 8th Filing - the Shops at Rigden
Farm utility plans.
Number: 78 Created: 1 /24/2006
[3/1/06] The details were added, but need some help. The line weights will
not reproduce well and they are not really readable.
[1/24/06] Add the following details to the plans: 701, 1601 and 1602 these
will be used to replace any existing damaged curb, gutter or sidewalk or
curb, gutter and sidewalk damaged during construction.
Page 4
Department: Engineering Issue Contact: Sheri Wamhoff
Topic: General
Number: 41 Created: 11 / 14/2005
[3/ 1 /06] Sheet C 19 needs to be revised by Kin -ley Horn or completely
redrawn (everythingneeds to be provided and the engineering company will
need to sign off on the design) so that the existing sheet can be replaced
with the revised or new sheet. This needs to be submitted with the Final
Compliance submittal.
[ 1 /24/06] This sheet has not yet been submitted for review. This revision
will need to be approved before or at the same time this project is approved.
[ 11 / 14/051 For the removal of the storm drain inlet - the original plans
(sheet C 19) needs to. be revised to show this change. These plans also need
to be revised to show the new inlet and manhole that you are proposing.
Number: 44 Created: 11 / 14/2005
[3/ 1 /06] [ 1 /24/061 [ 11 / 14/05] See utility plan check sheet for additional
comments and requirements.
Number: 45 Created: 11 / 14/2005
[3/ 1 /06] Easements by separate document are needed as follows: A utility
easement for the relocation of the fire hydrant. A utility easement for the
meter pit for the grease monkey building (as shown it is being placed
outside of the existing easement area). A drainage easement for the storm
drainage inlet. Please let me know if you have questions regarding format or
the processing. These will need to be provided prior to our approval of these
utility plans.
[1/24/061 I provided a copy of the dedication documents, information sheet
and application form. There is a $250 processing fee (plus filing fees) for
this document.
[ 11 / 14/051 An easement by separate document is needed for the relocation
of the fire hydrant.
Number: 61 Created: 1 /24/2006
[3/ 1 /06] Per the site plan the light pole is now being removed, not relocated.
Please adjust note on utility plans.
[1 /24/061 It has not been identified where the light pole is to be relocated
to.
Number: 62 Created: 1 /24/2006
[3/ 1 /06] Per Stormwater there is a letter. Please reference the name and
date of this letter in the general note.
[ 1 /24/061 The general notes indicate that there was not a drainage and
erosion control report or letter for this project. That seems a little strange.
If there is a report the name and date of that report or letter needs to be
referenced in general note # 19.
Page 3
L
Current Planning
* Because of the prominence of the south elevation of Grease Monkey to
Custer Drive there must be additional building articulation done to that
elevation. Depending on what is happening right inside that wall, could
high windows be included on that elevation? If not, then additional
masonry must be included to soften the EIFS massing. The south
elevation should reflect more the north elevation of that building.
Number: 93 Created: 3/ 1 /2006
[3/1/06) An administrative public hearing for the Project Development Plan
has been scheduled for Tuesday, March 21st, at 1O:30 a.m. in conference
room A, 281 North College Avenue.
Topic: Landscape plan
Number: 86 Created: 2/28/2006
[2/28/061 On the Landscape Plan, the leader line for the screen wall on the
southeast corner of the car wash building is not aligned correctly.
Number: 87 Created: 2/28/2006
[2/28/061 There is one shrub that is "floating" in the drive area between
landscaped areas south of the 2 buildings.
Number: 89 Created: 2/28/2006
[2/28/061 A label on the Landscape Plan shows 25 Colorgreen Junipers to
form a hedge along the south side of the drive area on -site, next to Custer
Drive. Graphically, on the Landscape Plan, there are only 24 Junipers
shown in that area. To visually enclose the vehicle use area there should
actually be 26 Junipers (please see the red -lined Landscape Plan). The
shrubs need only to maintain a 4' separation from the gas line that crosses
that area.
Topic: Site Plan
Number: 90 Created: 2/28/2006
[2/28/061 There are several leader lines on the Site Plan that either end at
"nothing" or are not tied to a label. Please see the red -lined Site Plan.
Page 2
STAFF PROJECT REVIEW
City of Fort Collins
Automotive Development Group Date: 03/03/2006
c/o Jody Newton
360 Happy Canyon Road
Castle Rock, CO 80104
Staff has reviewed your submittal for RIGDEN FARM, STH FILING, LOT 5,
GREASE MONKEY/CAR WASH - PDP, TYPE 1 REVIEW, and we offer the
following comments:
ISSUES:
Department: Current Planning Issue Contact: Steve Olt
Topic: Building Elevations
Number: 91 Created: 2/28/2006
[2/28/061 The south elevation of the Grease Monkey building has a
significant presence to Custer Drive. Additional masonry and/or high level
windows must be incorporated on this elevation.
Topic: General
Number: 92 Created: 3/ 1 /2006
13/ 1 /06] The following comments were expressed at staff review on
Wednesday, March 1st:
Water/Wastewater
* Additional easements are needed for the curb stop/meter pit and the
relocated fire hydrants.
* The location of the curb stop/meter pit must be resolved with the Final
Compliance submittal.
Stormwater
* Necessary easements must be provided with the Final Compliance
submittal.
* As requested, the necessary revisions to Sheet C 19 of the utility plans
can and must be addressed with the Final Compliance submittal.
En ' eering
* Necessary easements to be dedicated must be provided with the Final
Compliance submittal.