HomeMy WebLinkAboutTRAILHEAD VILLAGE TOWNHOMES - PDP - 43-02C - CORRESPONDENCE - (5)[3/30/06] TURNING RADII: PFA acknowledges applicant's comment that minimum turning
radii throughtout the tracts is 25 feet inside, 50 feet outside.
Number: 79 Created: 3/30/2006
[3/30/06] ADDRESSING: Address numerals and building letters shall be visible from the
street fronting the property, and posted with a minimum of six-inch (6) numerals on a
contrasting background. (Bronze numerals on brown brick are not acceptable). In addition,
each individual unit shall also display its appropriate address numeral on both the "front" and
"rear" of the unit.
Number: 80 Created: 3/30/2006
[3/30/06] WATER SUPPLY: Fire hydrant(s) are required. Minimum spacing and flow
requirements for this project are 1,500 gpm at 20 psi residual pressure, spaced not further
than 300 feet to the building, on 600-foot centers thereafter;
Department: Transportation Planning Issue Contact: Kurt Ravenschlag
Topic: Preliminary Landscape Plan
Number: 66 Created: 3/29/2006
[3/29/06] Place any sidewalk outside of ROW in a public access easement.
Department: Zoning Issue Contact: Jenny Nuckols
Topic: ZONING
Number: 3 Created: 10/21 /2005
[3/22/06]
[10/21/05] One handicap parking space needs to be van accessible and signed as such.
Van accessible spaces are an overall width of 16'.
3-22-06 PLEASE NOTE ON THE SITE PLAN WHICH SPACE WILL BE VAN ACCESSIBLE
Number: 7 Created: 10/24/2005
[3/22/06]
[10/24/05] Page 3 of 3 - elevations - note building height, building materials and colors
3-22-06 Please note material colors
Be sure and return all of your redlined plans when you re -submit.
If you have any questions regarding these issues or any other issues related to this project,
please feel free to call me at (970) 221-6750.
Sincerely,
Anne Aspen
City Planner
Page 5
Department: Light & Power Issue Contact: Alan Rutz
Topic: General
Number: 50 Created: 3/27/2006
[3/27/06] Continue to show the electric meter locations on the Overall Utility Plans. Please
remove the electric lines. They will not be installed as shown on the Utility Plans.
Number: 51 Created: 3/27/2006
[3/27/06] Streetlights are not installed on private drives unless requested by the developer.
Number: 52 Created: 3/27/2006
[3/27/06] An electronic submittal, AutoCAD drawing, is required for the electric design.
Drawing should consist of site plan, utility and landscape plans. Email drawing to
arutz@fcgov.com
Number: 53 Created: 3/27/2006
[3/27/06] Please relocate the following electric meters. On Overall Utility Plan Sheet G9 of
G20. For Building A move meter to east end of building. For Building C move meter to east
end of building. The gas meters will need to be moved to the west side of these buildings.
Department: Natural Resources Issue Contact: Doug Moore
Topic: Preliminary Landscape Plan
Number: 54 Created: 3/28/2006
[3/28/06] Existing trees and buffer didn't print on plan and irrigated bluegrass seed or sod is
incorectly shown within the buffer where native species need to be planned. Please also
provide a native see schedule.
Department: PFA Issue Contact: Carie Dann
Topic: Fire
Number: 76 Created: 3/30/2006
[3/30/06] SECONDARY ACCESS LANES: PFA acknowledges the two lanes shown to
provide secondary access and are designated for "Emergency Vehicles Only". These two
easements shall be constructed of an all-weather driving surface (asphalt or concrete) that
can support the weight of fire apparatus. The applicant said they would install a gate and
Knox Lock at each of these access lanes; however, PFA would prefer signage only, and if
private vehicles begin using the emergency access drives as a public street, then install a
gate and Knox Lock. (All specifications for fire lanes shall apply to these two Emergency
Access Easements; see comment 77 for information.)
Number: 77 Created: 3/30/2006
[3/30/06] FIRE LANE: A fire lane is required throughout all drive aisles in Tracts F and G,
and Green Lake Court and Flagstaff Court. The fire lane shall be visible by painting and
signage, and maintained unobstructed. A fire lane plan shall be submitted for approval prior
to installation. The fire lane shall be a flat, hard, all-weather driving surface (asphalt or
concrete) capable of supporting fire apparatus weights. Compacted road base shall be used
only for temporary fire lanes or at construction sites.
The fire lane shall have appropriate maintenance agreements that are legally binding and
enforceable, and be designated on the plat as an Emergency Access Easement. The
minimum required width of 20 feet shall be maintained throughout the length of the fire lane.
Number: 78
Created: 3/30/2006
Page 4
[3/29/06] Property lines are shown encroaching the Western Gas easement. No structures
may be located in the easement, including footings
Number: 57 Created: 3/29/2006
[3/29/06] (PH) Please modify the Tract descriptions to say "PUBLIC access easement, not
just "access easement."
Number: 62 Created: 3/29/2006
[3/29/06] Horizontal control plan is not showing any labels or dimensions.
Number: 67 Created: 3/29/2006
[3/29/06] (PH) Your key maps are still showing the old layout.
Topic: grading plan
Number: 58 Created: 3/29/2006
[3/29/06] (PH) Please clarify hatch patterns on the sidewalk and on the streets.
Number: 65 Created: 3/29/2006
[3/29/06] (PH) The area on the west end of Green Lake Ct. appears to exceed the
allowable drainage from a private drive onto a public ROW. The limit is 750 s.f.
Topic: Landscape plan
Number: 70 Created: 3/29/2006
[3/29/06] Please check with Excel that you're maintaining enough separation from street
trees.
Number: 71 Created: 3/29/2006
[3/29/06] (PH) Please label utility lines on the landscape plan. Also, label and dimension all
easements.
Topic: Technical Services
Number: 74 Created: 3/29/2006
[3/29/06] Tech. Services Comments:
1. Boundaries close. Boundaries do not match Trail Head plat. (Does this plat change the
south line of Lot 7/618?)
2. Suggestion that line and curve tables be moved to the cover sheet.
3. Tracts should be emergency access also.
Topic: utility plan
Number: 59 Created: 3/29/2006
[3/29/06] Please check with utilities that you have adequate separations. Along Campfire
Dr., only 3' between gas and water services. Along Vine Dr., only 5' between gas and
electric mains.
Number: 60 Created: 3/29/2006
[3129/06] (PH) Label and dimension easements and ROW.
Number: 61 Created: 3/29/2006
[3/29/06] (PH) For any utility stubs that will be existing, please change the linetype to
existing and label as existing per Trail Head.
Page 3
A permit must be obtained from the City Forester before any trees or shrubs as noted on this
plan are planted, pruned or removed on the public right-of-way. This includes zones
between the sidewalk and curb, medians, and other City property. This permit shall approve
the location and species to be planted. Failure to obtain this permit may result in replacing
or relocating trees and a hold on certificate of occupancy.
The developer shall contact the City Forester to inspect all street tree plantings at the
completion of each phase of the development. All trees need to have been installed as
shown on the landscape plan. Approval of street tree planting is required before final
approval of each phase. Failure to obtain approval by the City Forester for street trees in a
phase shall result in a hold on certificate of occupancy for future phases of the
development."
Please see redlines for additional comments.
Number: 69 Created: 3/29/2006
[3/29/06] 1 think the sidewalk solution works well, as does the new parking lot layout.
Thanks for your time and effort to address these issues.
Number: 75 Created: 3/29/2006
[3/29/061 The parking that faces the existing trees and buffer needs to be screened. Again
since the project is right up against the property line, this may be challenging. Screening
e-
can either be taller shrubs or a combination fence and landscaping. My suggestion would
o1,10
tea,
be to change the parking spaces to compact dimensions and use shrubs for screening so
that the view out to the trees is minimally obstructed.
A'4-�
Topic: Landscape plan
Number: 73 Created: 3/29/2006
[3/29/06] The ring walkway is technically a major walkway spine and as such, needs to be
goJ'
" }y
lined on both sides with trees. Since the project is right up against the property line, there is,oL"��
little room to provide this. Perhaps you could add a few crabapples on the residential side.�c'
Number: 81 Created: 3/31 /2006
[3/31/061 Ensure that the proposed street trees are properly spaced and not in the required
utility separation areas.
Topic: Lighting Plan
Number: 68 Created: 3/29/2006
[3/29/061 The lighting plan is beautiful! I wish I had a gold star sticker to put on it. Good
fixture choices, good lighting levels, and good shielding. Bravo!!
Department: Engineering Issue Contact: Dan DeLaughter
Topic: General
Number: 32 Created: 11 /1 /2005
[3/29/06]
[11/1/05] See redlines for additional minor revisions
Number: 55 Created: 3/29/2006
[3/29/06] Provide ELCO, Boxelder, and Western Gas signature blocks on the plat.
Number: 56
Created: 3/29/2006
Page 2
STAFF PROJECT REVIEW
City of Fort Collins
VF RIPLEY Date: 04/10/2006
AMY JOHNSON/CATHY MATHIS
401 WEST MOUNTAIN AVENUE, SUITE 201
FORT COLLINS, CO 80521
Staff has reviewed your submittal for TRAILHEAD VILLAGE TOWNHOMES PDP - TYPE I,
and we offer the following comments:
ISSUES:
Department: Current Planning Issue Contact: Anne Aspen
Topic: Architectural Elevations
Number: 72 Created: 3/29/2006
[3/29/06] Please submit material spec boards or label elevations with colors. Refer to
4.4(E)(4)(d) for more detail. Remember too that per 4.4(E)(4)( c) there need to be at least 3
` distinctly different designs.
�L Topitt: General
Number: 33 Created: 11/1/2005
[4/10/0€1 Has this been addressed? Please contact Megan to resolve any remaining
issues.
[11/1/05] The County Assessor comments that:
Title of plat is Trail Head Townhomes--differentfrom Trailhead Village Townhomes. Also,
Tract F is not labelled on the plat.
Megan Harrity 498-7065
Number:34 Created:11/1/2005
[4110106] The plat still shows building envelopes that overlap at the C.Orttprs, preventing Xcel
from being able to run gas lines to the buildings.
[11/1/05] Xcel Energy comments:
"Appears best way to serve townhomes would be one service to each building complex with
all meters at one end of the building. Customer would need to run fuel lines through other
units to get to meter location.
No way to serve Building F Units 29-32. Building envelopes prevent gas service lines from
being installed at ends of building.
Same thing with Building D between units 18 and 19.
Number: 48 Created: 11 /4/2005
[4/10/06] The notes have not been added. Please add. Also, Summit Ash is also not on
the approved street tree list. Please select a tree that is or, the list. A list will be returned
with Forestry redlines.
[11/4/05] Tim Buchanan the City Forester comments as follows:
"Along Green Lake Court the street tree used is Fall Gold Ash. This species is no longer on
the City Street Tree List. The applicant needs to change these trees to Marshall Ash or
another approved street tree species.