HomeMy WebLinkAboutTRAILHEAD VILLAGE TOWNHOMES - PDP - 43-02C - CORRESPONDENCE - (3)The fire lane shall have appropriate maintenance agreements that are legally binding and
enforceable, and be designated on the plat as an Emergency Access Easement. The
minimum required width of 20 feet shall be maintained throughout the length of the fire lane.
Number: 78 Created: 3/30/2006
[3/30/06] TURNING RADII: PFA acknowledges applicant's comment that minimum turning
radii throughout the tracts is 25 feet inside, 50 feet outside.
Number: 79 Created: 3/30/2006
[3/30/06] ADDRESSING: Address numerals and building letters shall be visible from the
street fronting the property, and posted with a minimum of six-inch (6) numerals on a
contrasting background. (Bronze numerals on brown brick are not acceptable). In addition,
each individual unit shall also display its appropriate address numeral on both the "front" and
"rear' of the unit.
Number: 80 Created: 3/30/2006
[3/30/06] WATER SUPPLY: Fire hydrant(s) are required. Minimum spacing and flow
requirements for this project are 1,500 gpm at 20 psi residual pressure, spaced not further
than 300 feet to the building, on 600-foot centers thereafter;
Department: Transportation Planning Issue Contact: Kurt Ravenschlag
Number: 66 Created: 3/29/2006
[3/29/06] Place any sidewalk outside of ROW in a public access easement.
Department: Zoning Issue Contact: Jenny Nuckols
Topic: ZONING
Number: 3 Created: 10/21 /2005
[3/22106]
[10/21/05] One handicap parking space needs to be van accessible and signed as such.
Van accessible spaces are an overall width of 16'.
3-22-06 PLEASE NOTE ON THE SITE PLAN WHICH SPACE WILL BE VAN ACCESSIBLE
Number: 7 Created: 10/24/2005
[3/22/06]
[10/24/05) Page 3 of 3 - elevations - note building height, building materials and colors
3-22-06 Please note material colors
Be sure and return all of your redlined plans when you bring revisions to us. You will not
need to do another formal round of review. Please address the comments above and work
with the reviewers individually to resolve. Once I hear back from everyone that they are OK
with the plans, I will be ready to schedule the public hearing (administrative) for you.
If you have any questions regarding these issues or any other issues related to this project,
please feel free to call me at (970) 221-6206.
Sincerely,
AA neWeln
P
City Planner
Page 4
Number: 61 Created: 3/29/2006
[3/29/061 (PH) For any utility stubs that will be existing, please change the line type to
existing and label as existing per Trail Head.
Department: Light & Power Issue Contact: Alan Rutz
Topic: General
Number: 50 Created: 3/27/2006
[3/27/06] Continue to show the electric meter locations on the Overall Utility Plans. Please
remove the electric lines. They will not be installed as shown on the Utility Plans.
Number: 51 Created: 3/27/2006
[3/27/06] Streetlights are not installed on private drives unless requested by the developer.
Number: 52 Created: 3/27/2006
[3/27/06] An electronic submittal, AutoCAD drawing, is required for the electric design.
Drawing should consist of site plan, utility and landscape plans. Email drawing to
arutz@fcgov.com
Number: 53 Created: 3/27/2006
[3/27/06] Please relocate the following electric meters. On Overall Utility Plan Sheet G9 of
G20. For Building A move meter to east end of building. For Building C move meter to east
end of building. The gas meters will need to be moved to the west side of these buildings.
Department: Natural Resources Issue Contact: Doug Moore
Topic: Preliminary Landscape Plan
Number: 54 Created: 3/28/2006
[3/28/06] Existing trees and buffer didn't print on plan and irrigated bluegrass seed or sod is
incorectly shown within the buffer where native species need to be planned. Please also
provide a native see schedule.
Department: PFA Issue Contact: Carle Dann
Topic: Fire
Number: 76 Created: 3/30/2006
[3/30/06] SECONDARY ACCESS LANES: PFA acknowledges the two lanes shown to
provide secondary access and are designated for "Emergency Vehicles Only'. These two
easements shall be constructed of an all-weather driving surface (asphalt or concrete) that
can support the weight of fire apparatus. The applicant said they would install a gate and
Knox Lock at each of these access lanes; however, PFA would prefer signage only, and if
private vehicles begin using the emergency access drives as a public street, then install a
gate and Knox Lock. (All specifications for fire lanes shall apply to these two Emergency
Access Easements; see comment 77 for information.)
Number: 77 Created: 3/30/2006
[3/30/06] FIRE LANE: A fire lane is required throughout all drive aisles in Tracts F and G,
and Green Lake Court and Flagstaff Court. The fire lane shall be visible by painting and
signage, and maintained unobstructed. A fire lane plan shall be submitted for approval prior
to installation. The fire lane shall be a flat, hard, all-weather driving surface (asphalt or
concrete) capable of supporting fire apparatus weights. Compacted road base shall be used
only for temporary fire lanes or at construction sites.
Page 3
Number: 55 Created: 3/29/2006
[3/29/06] Provide ELCO, Boxelder, and Western Gas signature blocks on the plat.
Number: 56 Created: 3/29/2006
[3/29/06] Property lines are shown encroaching into the Western Gas easement. No
structures may be located in the easement, including footings.
Number: 57 Created: 3/29/2006
[3/29/06] (PH) Please modify the Tract descriptions to say "PUBLIC access easement, not
just "access easement."
Number: 62 Created: 3/29/2006
[3/29/06] Horizontal control plan is not showing any labels or dimensions.
Number: 67 Created: 3/29/2006
[3/29/06) (PH) Your key maps are still showing the old layout.
Topic: grading plan
Number: 58 Created: 3/29/2006
[3/29/06] (PH) Please clarify hatch patterns on the sidewalk and on the streets.
Number: 65 Created: 3/29/2006
[3/29/06] (PH) The area on the west end of Green Lake Ct. appears to exceed the
allowable drainage from a private drive onto a public ROW. The limit is 750 s.f.
Topic: Landscape plan
Number: 70 Created: 3/29/2006
[3/29/06] Please check with Excel that you're maintaining enough separation from street
trees.
Number: 71 Created: 3/29/2006
[3/29/06] (PH) Please label utility lines on the landscape plan. Also, label and dimension all
easements.
Topic: Technical Services
Number: 74 Created: 3/29/2006
[3/29/06] Tech. Services Comments:
1. Boundaries close. Boundaries do not match Trail Head plat. (Does this plat change the
south line of Lot 7/B18?)
2. Suggestion that line and curve tables be moved to the cover sheet.
3. Tracts should be emergency access also.
Topic: utility plan
Number: 59 Created: 3/29/2006
[3/29/06] Please check with utilities that you have adequate separations. Along Campfire
Dr., only 3' between gas and water services. Along Vine Dr., only 5' between gas and
electric mains.
Number: 60 Created: 3/29/2006
[3/29/06] (PH) Label and dimension easements and ROW.
Page 2
STAFF PROJECT REVIEW
City of Fort Collins
VF RIPLEY Date: 03/31/2006
AMY JOHNSON/CATHY MATHIS
401 WEST MOUNTAIN AVENUE, SUITE 201
FORT COLLINS, CO 80521
Staff has reviewed your submittal for TRAILHEAD VILLAGE TOWNHOMES PDP - TYPE I,
and we offer the following comments:
ISSUES:
Department: Current Planning Issue Contact: Anne Aspen
Topic: General
Number: 69 Created: 3/29/2006
[3/29/06] 1 think the sidewalk solution works well, as does the new parking lot layout.
Thanks for your time and effort to address these issues.
Topic: Architectural Elevations
Number: 72 Created: 3/29/2006
[3/29/06] Please submit material spec boards or label elevations with colors. Refer to
4.4(E)(4)(d) for more detail. Remember too that per 4.4(E)(4)( c) there need to be at least 3
distinctly different designs.
Topic. Landscape plan
Number: 73 Created: 3/29/2006
[3/29/06] The ring walkway is technically a major walkway spine and as such, needs to be
lined on both sides with trees. Since the project is right up against the property line, there is
little room to provide this. Perhaps you could add a few crabapples on the residential side.
Number: 75 Created: 3/29/2006
[3/29/06) The parking that faces the existing trees and buffer needs to be screened. Again,
since the project is right up against the property line, this may be challenging. Screening
can either be taller shrubs or a combination fence and landscaping. My suggestion would
be to change the parking spaces to compact dimensions and use shrubs for screening so
that the view out to the trees is minimally obstructed.
Number: 81 Created: 3/31/2006
[3/31/06] Ensure that the proposed street trees are properly spaced and not in the required
utility separation areas.
Topic: Lighting Plan
Number: 68 Created: 3/29/2006
[3/29/06] The lighting plan is beautiful! 1 wish I had a gold star sticker to put on it. Good
fixture_ choices, good lighting levels, and good shielding. Bravo!!
Department: Engineering Issue Contact: Dan DelLaughter
Topic. General
Number: 32 Created: 11 /1 /2005
(3/29/06]
[11/1/05] See redlines for additional minor revisions.