HomeMy WebLinkAboutTURNING POINT PLAT - PDP - 12-99 - CORRESPONDENCE - FIRE AUTHORITY REQUIREMENTSPROJECT
COMMENT SHEET
City of Fart Collins
Current Plannine
DATE: July 6, 1999 TO: PFA
PROJECT: #12-99 Turning Point Plat — PDP — LUC Type I
All comments must be received by Troy Jones no later than the staff
review meeting:
Wednesday, July 21, 1999 d
VHJUL221999 D
Date
REQUIRED ACCESS: B
Q Y
A fire lane is required; this fire lane shall be visible by painting an signage, an
maintained unobstructed. A fire lane plan shall be submitted for approval prior to
installation.
ADDRESS NUMERALS
Address numerals shall be visible from the street fronting the property, and posted with a
minimum of 6 inch numerals on a contrasting background. (Bronze numerals on brown
brick are not acceptable).
WATER SUPPLY
Fire hydrants are required with a maximum spacing of 600 feet along an approved
roadway. Each hydrant must be capable of delivering 1500 gallons of water per minute
at a residual pressure of 20 psi.. Hydrants shall be of an approved type as defined by the
water department and the fire department. No building can be greater than 300 feet
from a fire hydrant.
SPRINKLER REQUIREMENTS:
This building is required to be fire sprinklered based on the use.
7- Ze -?I
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
_Plat Site
Utility _Redline Utility
_Drainage Report _Other
_Landscape
Commi. ry Planning and Environmental rvices
Current Planning
City of Fort Collins
Rebecca Spears July 29, 1999
RB&B Architects
315 E. Mountain Ave.
Fort Collins, CO 80524
One of the department's comment sheets was misplaced for the Turning Point Plat, and has
recently surfaced. Please see the attached comment sheet from the Poudre Fire Authority.