HomeMy WebLinkAboutTURNING POINT PLAT - PDP - 12-99 - CORRESPONDENCE - (11)REVISION
COMMENT SHEET
DATE: August 12, 1999 TO: Engineering
PROJECT: #12-99 Turning Point — Type 1 (LUC)
All comments must be received by Troy Jones no later than the
staff review meeting:
Wednesday, August 25, 1999
❑ No Comment
Do-�rroblems or Concerns (see below or attached)
Z . ��...� ,cam*-�s� s� a►.o �.
n
Date:
HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
.o Plat i�Site Drainage Report _ Ofher
)-11-Utilily TA.
REVISION
COMMENT SHEET
DATE: August 12, 1999 DEPT: Water/Wastewater
PROJECT: # 12-99 Turning Point -Type 1 (LUC)
All comments must be received by Troy Jones no later than the staff
review meeting:
Wednesday, August 25, 1999
➢ As previously indicated, label all existing mains with name of ownership.
➢ The 20-inch water main in West Plum Street is a steel line. Change the note on
the utility plans concerning the tapping procedures to read "Install 20"x20"x6"
welded tapping saddle with T.B. and 6"gate valve on existing 20" steel water
main. Repair coating with approved materials and methods".
➢ See site plans for other comments.
Date: S - Signature:
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
_ Plat X Site _ Drainage Report _Other
X Utility X Redline Utility _ Landscape
City of Fort Collins
REVISION
COMMENT SHEET
DATE: August 12, 1999 TO: PFA
PROJECT: #12-99 Turning Point- Type 1 (LUC)
All comments must be received by Troy Jones no later tl
staff review meeting:
Wednesday, August 25,199 s ,�
A�61
❑ No Comment ey
Fg/ Problems or Concerns (see below or attached)
REQUIRED ACCESS:
the
8 ,9997
Afire lane is required for this project. This fire lane shall be visible by painting and/or
signage, and maintained unobstructed. The PFA will accept a minimum width of 12 feet
for this project's fire lane.
ADDRESS NUMERALS
Address numerals shall be visible from the street fronting the property, and posted with a
minimum of 6 inch numerals on a contrasting background. (Bronze numerals on brown
brick are not acceptable).
WATER SUPPLY
Fire hydrants are required with a maximum spacing of 600 feet along an approved
roadway. Each hydrant must be capable of delivering 1500 gallons of water per minute
at a residual pressure of 20 psi.. Hydrants shall be of an approved type as defined by the
water department and the fire department. No commercial building can be greater
than 300 feet from a fire hydrant.
SPRINKLER REQUIREMENTS:
This project is required to be fire sprinklered.
Date:
CHECK HERE IF YOU TO RECIIVE COPIES OF REVISIONS
_ Plat Site _ Drainage Report _ Other
Utility _ Redline Utility _ landscape
Commu. Planning and Environmental' vices
Current Planning
City of Fort Collins
STAFF REVIEW COMMENTS
Rebecca Spears
RB&B Architects
315 E. Mountain Ave.
Fort Collins, CO 80524
August 31, 1999
Staff reviewed the Submittal of the Turning Point Plat, and would like to offer the following
comments:
COMMENTS:
1. Water and Sewer Utility Department:
a. See the attached comment sheet and redlined Utility Plans from Water/Wastewater.
2. Engineering Department:.
a. Please see the attached comment sheet and redlined Utility Plans from the Engineering
Department.
3. Transportation Planning / Advance Planning:
a. As discussed in our meeting on August 26th, the sidewalk shall be an 8 foot wide
attached sidewalk with no required setback for the fence from the edge of the walk.
4. City Forester:
a. Please provide drip irrigation for the landscaping outside of the fence.
5. Current Planning:
a.. Because there are only a few outstanding issues, we can go ahead and schedule you for a
Type 1 hearing. I will call you to coordinate.
b. We will need to see revised plans based on the outstanding comments prior to hearing,
but will not need to go through a formal submittal and review process. When you bring
in these revisions, please ask the person at the counter to take them straight to me, and I .
will route them to Engineering and Water/Wastewater.
c. Please submit 3 copies of all plans that have any changes from the last submittal.
If you have any questions about these or any other issues related to this project please feel free to
call be at 221-6750.
Yors truly, 4
l
Troy Jones
City Planner
281 North College Avenue • P.O. Box 580 • Fort Collins, CO 80522-0580 • (970) 221-6750 • FAX (970) 416-2020