Anne,
I noticed an issue with this change that unfortunately I didn't see until after the staff review meeting this
morning. They are showing both electric & gas meters located between the buildings, which is where the
electric meters must be located. However, there is only 5 ft. between the side of each building and the lot line
making it impossible to locate both utilities meters between the buildings and maintain the required minimum of
3 ft. between the gas and electric service line trenches. We encourage the gas meters to be located on the
opposite ends of the buildings to resolve this conflict.
I have entered this comment in DMs.