Loading...
HomeMy WebLinkAboutPAVILION SHOPPING CENTER (4366 S. COLLEGE) WTE, VERIZON - PDP - 21-00A - CORRESPONDENCE -Be sure and return all of your redlined plans when you re -submit. If you have questions regarding these issues or any other issues related to this project, ple a feel free to call me at (970) 221-6750. Yo rs Truly TR1OY JO S City Planner 2 of 2 l 4a STAFF PROJECT REVIEW Cih of fort Collins WALKER COMMERCIAL Date: 09/19/2001 RALPH WALKER 7354 S. EAGLE ST. ENGLEWOOD. CO 80112 Staff has reviewed your submittal for PAVILION SHOPPING CENTER (4366 S. COLLEGE) WTE,VERIZON #21-OOA, and we offer the following comments: ISSUES: Current Planning 4 Issue Contact. Troy Jones As discussed in our meeting on September 13, this application should actually be a minor amendment, and it should be coordinated with the latest approval of the ground mounted equipment enclosue area. The said latest approval is a recently approved minor amendment by Spectra Site. A copy of this enlarged site plan area was given to you when we met in person on September 13. Please revise your proposal to coordinate with said approved layout. Light & Power 2 Issue Contact. Alan Rutz Contact Alan Rutz at Light & Power immediately with load requirements and proposed service line location. The transformer located at the corner of the building is three phase 277/480 volts. The transformer located approx 200' north of site is three phase 120/208 volts. This is the transformer that Nextel is connecting to. This transformer only has room for one new secondary service line. This new service line will need to be sized to accommodate load from both Verizon and Nextel. Natural Resources 3 Issue Contact. Doug Moore No Issues - Zoning No comments 1 of 2 Issue Contact: Jenny Nuckols