29 Issue Contact. Katie Moore
Utilities must be installed underground and, if located in an alley, shall be in
place prior to the completion of alley surfacing. 3.3.2 (d) 7. 1 have confirmed
with Qwest that telephone service has not been undergrounded. (Cable TV has
been undergrounded.) Conduit needs to be provided and has not been
addressed on the plans.
34 Issue Contact: Katie Moore
Plat: Please correct statement of ownership and subdivision; the sentence
reading "all easements as shown..." should be a separate note not under any
other heading.
35 Issue Contact: Katie Moore
General note: background lines will need to be darker to be reproduced.
36 Issue Contact: Katie Moore
Alley Plan and Profile:
For the 16' cross-section, the cross slope as shown is 4.2%. The maximum
allowable cross slope is 4.0% (1.02.03.14 c). Please correct. Also, please add
note as shown: grade to match existing grades (typ).
Please clarify symbols for existing and proposed point elevations. It looks like
there are 3 symbols that are getting mixed up.
Please provide additional point elevations as requested on the plans.
Please see plans for additional comments.
37 Issue Contact: Katie Moore
Please add note to utility plans as discussed: Submit revised utility plans if
subdrain system is required.
Stormwater Utility
31 Issue Contact: Basil Hamdan
Stormwater is now ready for mylars. Grade tie in has been resolved.
32 Issue Contact: Basil Hamdan
Please submit two additional signed and stamped copies of drainage report for
signature.
Water Wastewater
33
Ready for mylars
2 of 3
Issue Contact: Jeff Hill
STAFF PROJECT REVIEW
S.L.C. COMPANY Date: 6/20/2001
STEWART & ASSOC.
103 S. MELDRUM ST.
FT. COLLINS, CO 80522
Staff has reviewed your submittal for 208 and 214 PETERSON, REPLAT #43-00, and we
offer the following comments:
ISSUES:
Current Planning
38
Issue Contact: Cameron Gloss
Site Plan -bedroom count
If basements are to remain part of the proposal, the site plan note needs to be
changed to reflect that these are 3-bedroom units, with 1 bedroom upstairs and
2 in the basement.
39 Issue Contact: Cameron Gloss
Floor Plan -Redwood Deck still shown
The site plans were changed to reflect the previous comment about
encroachments into easements, but the new building floor plans show a
"redwood deck" within the easements. Please remove the encroaching portion
of the deck frorrr the floor plans.
40 Issue Contact: Cameron Gloss
Review Process
As soon as all of the following issues are satisfactorily addressed, the
application will be scheduled for an Administrative Hearing. A minimum of two
weeks notice is required prior to the hearing.
Engineering
10
Issue Contact: Katie Moore
Drainage Plan:
Please show that flows from side yards and driveways abutting the paved and
newly graded sections of the alley are not impeded by the new
grading/pavement.
Please show locations of driveway connections to the alley.
The current level of detail is insufficient.